13
Chapter 3. MOUNTING AND WIRING
• Rotation of display unit
The display unit can be rotated 90˚ counterclockwise and 180˚ clock wise from the
state of factory shipment (see the figure shown below).
If the display is rotated beyond the range of movement stated above, the internal
connector may be disconnected, disabling the display unit.
clockwise
counterclockwise
Pipe or connected device
Location in
Straight pipe section for this device
relation to
For accuracy within
For accuracy
the MCF
specifications (±3 % FS)
within ±5 % FS
Tube fitting for air supply piping
Upstream
15D
5D
Tube dia.: 8 mm (internal dia.: 6 mm)
(MCF0080)
Downstream
Not needed
Not needed
Tube fitting for air supply piping
Upstream
5D
Not needed
Tube dia.: 12 mm (internal dia.: 8 mm)
(MCF0080)
Downstream
Not needed
Not needed
Tube fitting for air supply piping
Upstream
10D
5D
Tube dia.: 12 mm (internal dia.: 8 mm)
Tube dia.: 16 mm (internal dia.: 12 mm)
(MCF0150)
Downstream
Not needed
Not needed
Tube fitting for air supply piping
Upstream
20D
10D
Tube dia.: 16 mm (internal dia.: 12 mm)
(MCF0151)
Downstream
Not needed
Not needed
Tube fitting for air supply piping
Upstream
10D
8D
Tube dia.: 12 mm (internal dia.: 8 mm)
Tube dia.: 16 mm (internal dia.: 12 mm)
(MCF0250)
Downstream
5D
5D