Chapter 5.
SPECIFICATIONS
32
■
Specifications
* Discontinuation date: Dec. 2011.
Item
Specifications
Rated power supply
100 Vac 50/60 Hz
200 Vac 50/60 Hz
220 Vac 50/60 Hz
Allowable voltage
-15 to +10 % of rated voltage
Power consumption
FRS100B
-2: 3W max. FRS100C
-2: 7W max.
Contact ratings
250VA: terminal 3-4 for flame output 250 VA (1K and 2K)
: terminal 3-8 for start check output 250 VA (1K)
Flame sensitivity
Ignition detection level:
Flame voltage:
1 V or less
Flame-out detection level:
FRS100B
-2 flame voltage: 0.2 V or more
FRS100C
-2 flame voltage: 0.4 V or more
Recommended flame
Stable 2.0 Vdc or more
voltage
Flame signal output
Use at least 0.75 mm
2
wire, a max. of 10 m long, with IV (indoor vinyl) insulation.
Output terminals: A (-) and B (+) on body
Required input impedance of externally connected equipment: 100 k
Ω
min.
Ambient temperature
Stand-alone mounting:
-20 to +60 °C
Gang mounting (2 units or more):
-20 to +45 °C
Ambient humidity
90% RH 40 °C (without condensation)
Vibration resistance
4.9 m/s
2
max., 10 to 60 Hz for 2 h each in X, Y and Z directions (when directly
mounted on panel)
Insulation resistance
50 M
Ω
min. between terminals and ground terminal by 500 Vdc megger
Dielectric strength
No failure after applying 1500 Vac for 1min or 1800 Vac for 1 s between terminals
and ground terminal (excluding flame detector input of terminals 5 and 6)
Lightning-induced surge
10 kV, 1.2 x 50 µs (JEC-187, surge impedance 75
Ω
or more) when the following
surge absorber is attached to a power supply contact (terminal 2) and the ground
terminal:
• Recommended surge absorber: 83968019-001
Life
100,000 operations (at ordinary temperature and humidity, and rated voltage)
Body color
Gray
Mounting
Mounted on DIN rail or screw mounted (when using the FRS50A100 subbase)
Mass
FRS100B
-2: Approx. 270 g
FRS100C
-2: Approx. 270 g
FRS50A subbase :
Approx. 70 g
Optional parts
Subbase
Model No.: FRS50A100
(sold separately)
Lightning-induced surge absorber
Model No.: 83968019-001
Flame Simulator for Flame Rod
Model No.: 123514A
Flame Simulator for AUD100C/110C,
Model No.: FSP300C100