![Azbil FRS100 Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/azbil/frs100/frs100_user-manual_3042612028.webp)
18
• False flame is detected at startup
Chapter 2. MOUNTING AND WIRING
Flame detection
(3)Start contacts OFF
POWER LED
Flame output
Start check completion
FLAME LED
Start check LED
Start contact (term.7-2)
Elapsed time
Start check (2s)
(1)Power ON
(2)Start contacts ON
No
Input status
FRS100 activity
Output activity
1
Power ON
Power is applied across terminals 1 and 2.
(POWER LED lights up)
Flame detection
Relay 2K is turned on by a false flame signal.
(FLAME LED lights up)
2
Start contacts ON
When the start contacts are closed power is applied
across terminals 7 and 2. The start check is carried
out, and relay 1K does not turn on because
a false flame is detected.
3
Start contacts OFF
Power across terminals 7 and 2 is cut off. The
FRS100 returns to standby status and waits for
the next start signal.
If the false flame signal is continuous, the FLAME
LED is also ON continuously.
Note: It is possible that relay 2K may turn ON when the power is turned on.