Model selection guide
*1. Discontinuation date: Dec. 2011.
*2. Discontinuation date: March 2012.
*3. Please put "D" in
if inspection report is attached. Skip
if there is no inspec-
tion report.
3
Chapter 1. OVERVIEW AND PRODUCT CONFIGURATION
Model No.
Rated power supply
FRS100B100
-2
100 Vac 50/60Hz
FRS100B200
-2
200 Vac 50/60Hz
FRS100B104
-2
100 Vac 50/60Hz
FRS100B204
-2
200 Vac 50/60Hz
FRS100C100
-2
100 Vac 50/60Hz
FRS100C200
-2
200 Vac 50/60Hz
FRS100C300
-2
220 Vac 50/60Hz
FRS100C104
-2
100 Vac 50/60Hz
FRS100C204
-2
200 Vac 50/60Hz
FRS100C304
-2
220 Vac 50/60Hz
FRS100C150
-2
100 Vac 50/60Hz
FRS100C250
-2
200 Vac 50/60Hz
FRS100C350
-2
220 Vac 50/60Hz
FRS100C154
-2
100 Vac 50/60Hz
FRS100C254
-2
200 Vac 50/60Hz
FRS100C354
-2
220 Vac 50/60Hz
Power
consumption
3W max.
7W max.
7W max.
Flame failure
response
3 ±1 s
(when flame voltage is 2 V)
2 s max.
(when flame voltage is 2 V)
3 ±1 s
(when flame voltage is 4.2 V)
2 s max.
(when flame voltage is 4.2 V)
3 ±1 s
(when flame voltage is 3.5 V)
2 s max.
(when flame voltage is 3.5 V)
Flame detector
C7007A, C7008A
Flame Rod
C7012A*
2
, C7012C*
2
Ultraviolet Flame
Detector
A AUD15C
A AUD15C
Advanced Ultraviolet
Flame Detector
C7035A*
1
, C7027A*
1
Minipeeper Ultraviolet
Flame Detector
Model
Standard
model
High-sensitivity
model