Display
Item
Contents
Initial User
value
level
UF- 1
User function
- - - -
1
definition 1
UF-2
User function
- - - -
1
definition 2
UF-3
User function
- - - -
1
definition 3
UF-4
User function
- - - -
1
definition 4
UF-5
User function
- - - -
1
definition 5
UF-6
User function
- - - -
1
definition 6
UF-7
User function
- - - -
1
definition 7
UF-8
User function
- - - -
1
definition 8
E4
Display
Item
Contents
Initial User
value
level
Ot 1. 1
to
Control output
0: Input of default
0
2
Ot2. 1
1 to 2, event output 1: MV1 (ON/OFF control output, time proportional
Ev 1. 1
to
1 to 3 operation
output,heat-side proportional output of heat/cool
Ev3. 1
type
control)
2: MV2 (cool-side proportional output of heat/cool
control)
3: Function 1 ((A and B) or (C and D))
4: Function 2 ((A or B) and (C or D))
5: Function 3 (A or B or C or D)
6: Function 4 (A and B and C and D)
Ot 1. 2
to
Control output
0: Normally open (OFF, 0)
14 to 15
2
Ot2. 2
1 to 2, event output 1: Normally close (ON, 1)
or
Ev 1. 2
to
1 to 3 output
2: Internal event 1
2 to 4
Ev3. 2
assignment A
3: Internal event 2
4: Internal event 3
5: Internal event 4
6: Internal event 5
7 to 13: Undefined
14: MV1
Ot 1. 3
to
Control output
15: MV2
0
2
Ot2. 3
1 to 2, event output 16 to 17: Undefined
Ev 1. 3
to
1 to 3 output
18: DI1
Ev3. 3
assignment B
19: DI2
20 to 25: Undefined
26: Internal contact 1
27: Internal contact 2
28: Internal contact 3
29 to 33: Undefined
Ot 1. 4
to
Control output
34: Communication DI1
0
2
Ot2. 4
1 to 2, event output 35: Communication DI2
Ev 1. 4
to
1 to 3 output
36: Communication DI3
Ev3. 4
assignment C
37: Communication DI4
38: MANUAL mode
39: READY mode
40: Invalid
41: During AT execution
42: During SP ramp
Ot 1. 5
to
Control output
43: Undefined
0
2
Ot2. 5
1 to 2 event output 44: Alarm is enabled.
Ev 1. 5
to
1 to 3 output
45: PV alarm is enabled.
Ev3. 5
assignment D
46: Undefined
47: mode key function selection status
48: Event output 1 status
49: Control output 1 status
Display
Item
Contents
Initial User
value
level
dI 1. 3
to
Internal contact
0: Normally open (OFF, 0)
2 to 4
2
dI3. 3
1 to 3
1: Normally close (ON, 1)
Input assignment A 2: DI1
3: DI2
4 to 9: Undefined
10: Internal event 1
11: Internal event 2
dI 1. 4
to
Internal contact
12: Internal event 3
0
2
dI3. 4
1 to 3
13: Internal event 4
Input assignment B 14: Internal event 5
15 to 17: Undefined
18: Communication DI1
19: Communication DI2
20: Communication DI3
dI 1. 5
to
Internal contact
21: Communication DI4
0
2
dI3. 5
1 to 3
22: MANUAL mode
Input assignment C 23: READY mode
24: Undefined
25: During AT execution
26: During SP ramp
27: Undefined
dI 1. 6
to
Internal contact
28: Alarm is enabled.
0
2
dI3. 6
1 to 3
29: PV alarm is enabled.
Input assignment D 30: Undefined
31: Mode key function selection status
32: Event output 1 status
33: Control output 1 status
dI 1. 7
to
Internal contact
Digits are called as 1st digit, 2nd digit, 3rd digit and
0000
2
dI3. 7
1 to 3
4th digit from the right end digit.
Polarity A to D
1st digit: Polarity A 0: Direct
0
(Polarity of input
1: Reverse
assignment A)
2nd digit: Polarity B
0
(Polarity of input
assignment B)
3rd digit: Polarity C
0
(Polarity of input
assignment C)
4th digit: Polarity D
0
(Polarity of input
assignment D)
dI 1. 8
to
Internal contact
0: Direct
0
2
dI3. 8
1 to 3 Polarity
1: Reverse
dI 1. 9
to
Internal contact
0: Every internal event
0
2
dI3. 9
1 to 3
1 to 5: Internal event numbers
Internal event
No.assignment
Display
Item
Contents
Initial User
value
level
Ot 1. 6
to
Control output 1 to Digits are called as 1st digit, 2nd digit, 3rd digit and
0000
2
Ot2. 6
2, event output 1 to 4th digit from the right end digit.
Ev 1. 6
to
2 Polarity A to D
Ev3. 6
1st digit: Polarity A 0: Direct
0
2nd digit: Polarity B 1: Reverse
0
3rd digit: Polarity C
0
4th digit: Polarity D
0
Ot 1. 7
to
Control output 1
0: Direct
0
2
Ot2. 7
to 2, event output 1: Reverse
Ev 1. 7
to
1 to 3
Ev3. 7
Polarity
Ot 1. 8
to
Control output 1
0: Disabled
0
2
Ot2. 8
to 2, event output 1: Enabled (Latch at ON)
Ev 1. 8
to
1 to 3
2: Enabled (Latch at OFF, except at the time of
Ev3. 8
Latch
initialization after power ON)
Display
Item
Contents
Initial User
value
level
Id0 1
ROM ID
0: fixed
-
2
Id02
ROM version 1
XX. XX (2 digits after decimal point)
-
2
Id03
ROM version 2
XX. XX (2 digits after decimal point)
-
2
Id04
SLP support
-
2
Information
Id05
EST support
-
2
version
Id06
Manufacturing
Year - 2000
-
2
date code (year)
Ex.: “3” means the year 2003.
Id07
Manufacturing
Month + Day
100
-
2
date code (month, Ex.: “12.01” means the 1st day of December
day)
Id08
Serial No.
-
2
Display
Item
Contents
Initial User
value
level
dI 1. 1
to
Internal contact 1 0: No function
0
0
dI3. 1
to 3
1: LSP group selection (0/+1)
Operation type
2: LSP group selection (0/+2)
3: LSP group selection (0/+4)
4: Invalid
5: Invalid
6: Invalid
7: RUN/READY selection
8: AUTO/MANUAL selection
9: Invalid
10: AT Stop/Start
11: ST Disabled/Enabled
12: Control action direct/reverse selection (As per
setting/opposite operation of setting)
13: SP ramp Enabled/Disabled
14: PV hold (No-hold/Hold)
15: PV maximum value hold (No-hold/Hold)
16: PV minimum value hold (No-hold/Hold)
17: Timer Stop/Start
18: Release of all DO latches (Continue/Release)
19: Invalid
20: Invalid
dI 1. 2
to
Internal contact 1 0: Disabled. (Input of default)
0
2
dI3. 2
to 3
1: Function 1 ((A and B) or (C and D))
Input bit operation 2: Function 2 ((A or B) and (C or D))
3: Function 3 (A or B or C or D)
4: Function 4 (A and B and C and D)
■
Event assignment bank
Bank selection:
EvCF
■
DI assignment bank
Bank selection:
dI
■
Lock bank
Bank selection:
LOC
■
Instrument information bank
Bank selection:
Id
Display
Item
Contents
Initial User
value
level
LOC
Key lock
0: All settings are enabled.
0
0
1: Mode, event, operation display, SP, UF, lock,
manual MV, and mode key can be set.
2: Operation display, SP, UF, lock, manual MV, and
mode key can be set.
3: UF, lock, manual MV, and mode key can be set.
C. LOC
Communication
0: RS-485 communication read/write is enabled.
0
2
lock
1: RS-485 communication read/write is disabled.
L. LOC
Loader lock
0: Loader communication read/write is enabled.
0
2
1: Loader communication read/write is disabled.
PASS
Password display
0 to 15
0
0
5: Password 1A to 2B display
PS 1A
Password 1A
0000 to FFFF (hexadecimal value)
0000
0
PS2A
Password 2A
0000 to FFFF (hexadecimal value)
0000
0
PS 1b
Password 1B
0000 to FFFF (hexadecimal value)
0000
0
PS2b
Password 2B
0000 to FFFF (hexadecimal value)
0000
0
■
DO assignment bank
Bank selection:
dO
■
User function bank
Bank selection:
UF
Display
Item
Contents
Initial User
value
level
E 1. C 1
to
Operation type of 0: No event
0
0
E5. C 1
internal event 1 to 1: PV high limit
5 configuration 1
2: PV low limit
3: PV high/low limit
4: Deviation high limit
5: Deviation low limit
6: Deviation high/low limit
7: Deviation high limit (Final SP reference)
8: Deviation low limit (Final SP reference)
9: Deviation high/low limit (Final SP reference)
10: SP high limit
11: SP low limit
12: SP high/low limit
13: MV high limit
14: MV low limit
15: MV high/low limit
16: CT1 heater burnout/over-current
17: CT1 heater short-circuit
18: CT2 heater burnout/over-current
19: CT2 heater short-circuit
20: Loop diagnosis 1
21: Loop diagnosis 2
22: Loop diagnosis 3
23: Alarm (status)
24: READY (status)
25: MANUAL (status)
26: Invalid
27: During AT execution (status)
28: During SP ramp (status)
29: Control direct action (status)
30: ST execution (status)
31: Invalid
32: Timer (status)
E 1. C2
to
Internal event 1 to Digits are called as 1st digit, 2nd digit, 3rd digit and
0000
0
E5. C2
5 Configuration 2
4th digit from the right end digit.
1st digit:
0: Direct
0
Direct/Reverse
1: Reverse
2nd digit: Stand-by 0: None
0
1: Standby
2: S Standby at SP change
3rd digit: EVENT
0: Continue
0
state at READY
1: Forced OFF
4th digit: Undefined 0
0
E 1. C3
to
Internal event 1 to Digits are called as 1st digit, 2nd digit, 3rd digit and
0000
2
E5. C3
5 Configuration 3
4th digit from the right end digit.
1st digit: Alarm OR 0: No event
0
1: Alarm OR operation
2: Alarm AND operation
3: Alarm r OR operation
4: Alarm r AND operation
2nd digit: Special 0: As normal execution
0
OFF
1: Event OFF at the event setting value (main)=0
3rd digit: Delay
0: 0.1s
0
time unit
1: 1s
2: 1min
4th digit:
0
0
Undefined
This is the display in upper display. The setup
exception is as follows:
----
: Yet to be registered.
P--
:
Proportional band of the PID group in use
I--
:
Integration time of the PID group in use
d--
:
Derivative time of the PID group in use
rE--
: Manual reset of the PID group in use
OL--
: MV low limit of the PID group in use
OH--
: MV high limit of the PID group in use
P--C
: Cool-side proportional band of the PID
group in use
I--C
: Cool-side integration time of the PID group
in use
d--C
: Cool-side derivative time of the PID group
in use
Ol.-C
: Cool-side MV low limit of the PID group in
use
Oh.-C
: Cool-side of MV high limit of the PID group
in use
1st edition: Mar. 2006
13th edition: Mar. 2015 (F)