Azbil C15M Скачать руководство пользователя страница 6

Display

Item

Contents

Initial User 

value

level

C 64

CPL/MODBUS

0: CPL

0

0

1: MODBUS  ASCII format

2: MODBUS  RTU format

C 65

Station address

0 to 127

0

0

Communication is disabled when "0" is set.

C 66

Transmission 

0: 4800bps

2

0

speed

1: 9600bps

2: 19200bps

3: 38400bps

C 67

Data format (data   0: 7bits

1

0

length)

1: 8bits

C 68

Data format 

0: Even parity

0

0

(parity)

1: Odd parity

2: No parity

C 69

Data format (stop  0: 1bit

0

0

bits)

1: 2bits

C 70

Communication 

1 to 250ms

3

2

minimum response

time

C 7 1

Key operation 

0: Standard type

0

2

mode/type

1: Special type

C 72

MODE key 

0: Invalid

1

0

function

1: AUTO/MANUAL selection

2: RUN/READY selection

3: AT Stop/Start

4: LSP group selection

5: Release of all DO latches

6: Invalid

7: Communication DI1 selection

8: Invalid

C 73

MODE display 

Whether the mode bank setup display is enabled or 

255

1

setup

disabled is determined by the sum of the following 

weighting:

Bit 0: AUTO/MANUAL display

0: Disabled,  +1: Enabled

Bit 1: RUN/READY display

0: Disabled,  +2: Enabled

Bit 3: AT stop/start display

0: Disabled,  +8: Enabled

Bit 4: DO latch release

0: Disabled,  +16: Enabled

Bit 5: Communication DI1 ON/OFF display

0: Disabled,  +32: Enabled

Other invalid setup: 0, +4, +64, +128

C 74

PV/SP value 

Whether the basic display is enabled or disabled is 

15

1

display setup

determined by the sum of the following weighting:

Bit 0: PV display

0: Disabled,  +1: Enabled

Bit 1: SP display

0: Disabled,  +2: Enabled

Bit 2: LSP group No. display

0: Disabled,  +4: Enabled

Other invalid setup: 0, +8

C 75

MV display setup

Whether the basic display is enabled or disabled is 

15

1

determined by the sum of the following weighting:

Bit 0: MV display

0: Disabled,  +1: Enabled

Bit 1: Heat MV/cool MV display

0: Disabled,  +2: Enabled

Bit 3: AT progress display

0: Disabled,  +8: Enabled 

Other invalid setup: 0, +4

C 76

Event setting value  0: In the operation display mode, the internal event 

0

1

display setup

setting value is not displayed.

1: In the operation display mode, the internal event 1 

setting value is displayed.

2: In the operation display mode, the internal event 1 

to 2 setting value is displayed.

3: In the operation display mode, the internal event 1 

to 3 setting value is displayed.

C 77

Event remaining 

0: In the operation display mode, the ON/OFF delay 

0

1

time display setup

remaining time of the internal event is not 

displayed.

1: In the operation display mode, the ON/OFF delay 

remaining time of the internal event 1 is displayed.

2: In the operation display mode, the ON/OFF delay 

remaining time of the internal event 1 to 2 is 

displayed.

3: In the operation display mode, the ON/OFF delay 

remaining time of the internal event 1 to 3 is 

displayed.

C 78

CT input current 

0: In the operation display mode, the CT current 

0

1

value display 

value is not displayed.

setup

1: In the operation display mode, the CT1 current 

value is displayed.

2: In the operation display mode, the CT1 to 2 

current value is displayed.

C 79

User level

0: Basic configuration

0

0

1: Standard configuration

2: High function configuration

C 80

LED monitor

0: Disabled

0

2

1: Flashing at RS-485 communication signal 

transmission

2: Flashing at RS-485 communication signal 

receiving

3: OR (logical sum) of all DI status

4: Flashing at READY

C 90

Number of CT1

0: 800 turns

8

2

turns

1 to 40: CT turns divided by 100.

C 9 1

Number of CT1  0: 1 time

1

2

power wire loops 1 to 6: Number of times

C 92

Number of CT2

0: 800 turns

8

2

turns

1 to 40: CT turns divided by 100.

C 93

Number of CT2

0: 1 time

1

2

power wire loops 1 to 6: Number of times

Display

Item

Contents

Initial User 

value

level

C 0 1

PV input range 

Thermocouple (T): 1 to 6, 9 to 11, 13 to 21, 24, 25

1

0

type

RTD (R): 41 to 46, 51 to 54, 63, 64, 67, 68

41

DC current/voltage (L): 84, 86 to 90

88

C 02

Temperature unit

0: Centigrade (°C)

0

0

1: Fahrenheit (°F)

C 03

Cold junction 

0: Cold junction compensation is performed. (Internal)

0

2

compensation 

1: Cold junction compensation is not performed. 

(T/C)

(External)

C 04

Decimal point 

0: No decimal point

0

0

position

1: One digit below decimal point

2: Two digits below decimal point

3: Three digits below decimal point

(Select ‘0’ or ‘1’ for the RTD range with decimal 

point)

C 05

PV range low limit When the PV input range type is thermocouple (T) or 

-

0

RTD (R), the setting is disabled although range low 

limit is displayed.
–1999 to +9999U when the PV input range type is DC 

0

voltage/current (L).

C 06

PV range high

When the PV input range type is thermocouple (T) or 

-

0

RTD(R), the setting is disabled although range high 

limit is displayed.
–1999 to +9999U when the PV input range type is DC  1000

voltage/current (L).

C 07

SP low limit

PV input range low limit to PV input range high limit

0

1

C 08

SP high limit

1000

1

C 09

Squarer root 

0.0 to 100.0%

0.0

2

extraction dropout (0.0: No square root extraction)

C 14

Control action

0: Heat control (reverse action))

0

0

(direct/reverse)

1: Cool control (direct  action)

C 15

Selection of MV 

0: Control operation is continued.

0

2

at PV alarm 

1: MV at PV alarm occurrence is outputted.

occurrence

C 16

MV at PV alarm 

–10.0 to +110.0%

0.0

2

occurrence

C 17

MV at READY (at  –10.0 to +110.0%

0.0

1

heat-side for 

heat/cool control)

C 18

MV at READY (at  –10.0 to +110.0%

0.0

1

cool-side)

C 19

Operation at 

0: Bump-less

0

1

MANUAL change

1: Preset

C 20

Preset MANUAL 

–10.0 to +110.0%

0.0 or 

1

value

(Used even at MANUAL mode when power is ON.)

50.0

C 2 1

PID operation 

0: Automatic

0

2

initialization 

1: Not initialized

function selection

2: Initialized (when SP value different from current 

value is  inputted.)

C 22

PID operation 

–10.0 to +110.0%

0.0 or

2

initial MV

50.0

C 26

Heat/cool control

0: Disabled.

0

0

1: Enabled.

C 27

Heal/cool selection 0: Normal

0

1

1: Energy saving

C 28

Dead zone

–100.0 to +100.0%

0.0

0

C 29

Heal/cool control 

–10.0 to +110.0%

50.0

2

selection point

C 30

LSP setting 

1 to 4

1

0

system

C 32

SP ramp unit

0: 0.1U/s

1

2

1: 0.1U/min

2: 0.1U/h

C 36

CT1 operation 

0: Heater burnout detection

0

0

type

1: Current value measurement

C 37

CT1 output

0: Control output 1

0

0

1: Control output 2

2: Event output 1

3: Event output 2

4: Event output 3

C 38

CT1 measurement  30 to 300ms

30

0

wait time 

C 39

CT2 operation type Same as CT1.

0

0

C 40

CT2 output

0

0

C 4 1

CT2 measurement 

30

0

wait time 

C 42

Control output 1 

1: 4 to 2mA

1

0

range

2: 0 to 20mA

C 43

Control output 1 

0: MV

0

0

type

1: Heat MV

2: Cool MV

3: PV

4: PV before ratio bias filter

5: SP

6: Deviation (PV-SP)

7: CT1 current value

8: CT2 current value

9: Invalid

10: SP+MV

11: PV+MV

C 44

Control output 1 

–1999 to +9999

0.0

0

scaling low limit

(The decimal point position and unit may vary  

C 45

Control output 1 

depending on the control output 1 type.)

100.0

0

scaling high limit

C 46

Control output 1 0 to 9999

200

0

MV scaling

The decimal point position and unit are same as

for PV.

C 47

Control output 2 

Same as control output 1.

1

0

range

C 48

Control output 2 

3

0

type

C 49

Control output 2 

–1999 to +9999

0

0

scaling low limit

(The decimal point position and unit may vary  

C 50

Control output  2 

depending on the control output 2 type.)

1000

0

scaling high limit

C 5 1

Control output 2 0 to 9999

200

0

MV scaling

The decimal point position and unit are same as

for PV.

E3

Display

Item

Contents

Initial User 

value

level

A--M

AUTO/MANUAL 

AUTO

: AUTO mode

AUTO

0

mode selection

MAN

: MANUAL mode

r--r

RUN/READY 

RUN

: RUN mode

RUN

0

mode selection

RDY

: READY mode

At

AT Stop/Start 

At. OF

: AT Stop

AT Stop

0

selection

At. ON

: AT Start

do Lt

Release all DO 

Lt. ON

: Latch continue

Latch

0

latches

Lt. OF

: Latch release

continue

C. dI 1

Communication 

dI. OF

: OFF

OFF

0

DI 1

dI. On

: ON

[List of Parameter Setting Displays]

Mode bank 
Bank selection: 

MOdE

Display

Item

Contents

Initial User 

value

level

At. ty

AT type

0: Normal (Standard control characteristics)

1

0

1: Immediate response (Control 

characteristics immediately responding 

to the external disturbance.)

2: Stable (Control characteristics with less 

up/down function of PV)

JF. bd

Just-FiTTER setting band

0.00 to 10.00

0.30

2

SP. LG

SP lag constant

0.0 to 999.9

0.0

2

At-P

Proportional band tuning

0.00 to 99.99

1.00

2

factor at AT

At-I

Integration time tuning factor

0.00 to 99.99

1.00

2

at AT

At-d

Derivative time tuning factor 

0.00 to 99.99

1.00

2

at AT

Ctr. A

Control algorithm 

0: PID (conventional PID)

0

1

1: Ra-PID (high performance type)

JF. Ov

Just-FiTTER overshoot  

0 to 100

0

1

suppression factor

St.SA

ST step execution resolution 0.00 to 99.99 %

10.00

2

width

St.Sb

ST step settling bound

0.00 to 10.00 %

0.50

2

St.Hb

ST hunting settling bound

0.00 to 10.00 %

1.00

2

St.ud

ST step ramp change

0: ST is executed when the PV ramp up or 

0

1

down.

1: ST is executed only when the PV ramp 

up.

Display

Item

Contents

Initial User 

value

level

CtrL

Control method

0: ON/OFF control

0 or 1

0

1: PID fixed

2: ST (Self turning)

At. OL

MV low limit at AT 

–10.0 to +110.0%

0.0

0

At. OH

MV high limit at AT

–10.0 to +110.0%

100.0

0

dIFF

ON/OFF control differential

0 to 9999U

5

0

OFFS

ON/OFF control operating 

–1999 to 9999U

0

2

point differential

FL

PV filter

0.0 to 120.0s

0.0

0

rA

PV ratio

0.001 to 9.999

1.000

1

bI

PV bias

–1999 to +9999U

0

0

CyU

Time proportional cycle unit 1 0: 1s unit

0

2

1: 0.5s fixed (Cycle time is disabled.)

2: 0.2s fixed (Cycle time is disabled.)

3: 0.1s fixed (Cycle time is disabled.)

Cy

Time proportional cycle1 

5 to 120s (The output includes the relay 

10 or 2

0

output.)

1 to 120s (The output does not include the 

relay output.)

CyU2

Time proportional cycle unit 2 0: 1s unit

0

2

1: 0.5s fixed (Cycle time is disabled.)

2: 0.2s fixed (Cycle time is disabled.)

3: 0.1s fixed (Cycle time is disabled.)

Cy2

Time proportional cycle 2

5 to 120s (The output includes the relay 

10 or 2

0

output.)

1 to 120s (The output does not include the 

relay output.)

tP. ty

Time proportional operation 

0: Controllability aiming type

0 or 1

2

type

1: Actuator life aiming type 

(Only one ON/OFF operation within time 

proportional cycle time)

SPU

SP ramp-up

0.0 to 999.9U (0.0: No ramp)

0.0

2

SPd

SP ramp-down

0.0

2

Display

Item

Contents

Initial User 

value

level

SP- 1

to

SP of LSP1 group to SP low limit (C07) to SP high limit (C08)

0

0

SP-4

LSP4 group

Display

Item

Contents

Initial User 

value

level

Upper display: PV SP (Target value)

SP low limit (C07) to SP high limit (C08)

0

0

Lower display: SP

LSP 1

LSP No. (1st digit:  1 to LSP system group (C30 Max. 4)

1

0

Lower display: 

Value at the 

LSP

right end digit)

Out

MV (Manipulated 

–10.0 to +110.0%

-

0

Variable)

Setting is disabled in AUTO mode.

(Numeric value does not flash.) 

Setting is enabled in MANUAL mode.

(Numeric value flashes.)

HEAt

Heat MV

Setting is disabled 

-

0

(Manipulated 

–10.0 to +110.0%

Variable)

COOL

Cool MV 

-

0

(Manipulated 

Variable)

Upper display: PV AT progress 

Setting is disabled.

-

0

At 1

(display 

display (1st digit 

Except for 0: During execution of AT

example)

= Numeric value 

(Value is decreased.)

at right end digit)

0: Completion of AT

Ct 1

CT (Current 

Setting is disabled.

-

0

transformer) 

current value 1

Ct2

CT (Current 

Setting is disabled.

-

0

transformer) 

current value 2

E 1

Internal event 1 

Setting range is different depending on the internal 

0

0

main setting

event operation type.

E 1. Sb

Internal event 1 

–1999 to +9999U: Except below.

0

0

sub-setting

0 to 9999U: When the setting value is an absolute value.

–199.9 to +999.9%: For MV.

t 1. --

Timer remaining 

Setting is disabled.

-

0

time 1

Upper display: The distinction by ON delay or OFF 

delay is displayed at the side location of [t1.].

Lower display: Displayed by the unit (either one of 

0.1s,  s, or min) based on the internal event 1 delay 

time unit (E1. the 3rd digit of C3).

E2

Internal event 2 

Setting range is different depending on the internal 

0

0

main setting

event operation type.

E2. Sb

Internal event 2 

–1999 to +9999U: Except below.

0

0

sub-setting

0 to 9999U: When the setting value is an absolute 

value.

–199.9 to +999.9%: For MV.

t2. --

Timer remaining 

Setting is disabled.

-

0

time 2

Upper display: The distinction by ON delay or OFF 

delay is displayed at the side location of [t2.].

Lower display: Displayed by the unit (either one of 

0.1s,  s, or min) based on the internal event 2 delay 

time unit (E2. the 3rd digit of C3).

E3

Internal event 3

Setting range is different depending on the internal 

0

0

main setting

event operation type.

E3. Sb

Internal event 3 

–1999 to +9999U: Except below.

0

0

sub-setting

0 to 9999U: When the setting value is an absolute value.

–199.9 to +999.9%: For MV.

t3. --

Timer remaining 

Setting is disabled.

-

0

time 3

Upper display: The distinction by ON delay or OFF 

delay is displayed at the side location of [t3.].

Lower display: Displayed by the unit (either one of 

0.1s,  s, or min) based on the internal event 3 delay 

time unit(E3. the 3rd digit of C3).

Display

Item

Contents

Initial User 

value

level

P- 1

Proportional band 0.1 to 999.9%

5.0

0

I- 1

Integration time

0 to 9999s 

120

0

(0: No integral control action)

d- 1

Derivative time

0 to 9999s

30

0

(0: No derivative control action) 

rE- 1

Manual reset 

–10.0 to +110.0%

50.0

0

OL- 1

MV low limit 

–10.0 to +110.0%

0.0

1

OH- 1

MV high limit 

–10.0 to +110.0%

100.0

1

P- 1 C

Cool-side 

0.1 to 999.9%

5.0

0

proportional band 

I- 1 C

Cool-side 

0 to 9999s

120

0

integration time

(0: No integral control action)

d- 1 C

Cool-side 

0 to 9999s

30

0

derivative time

(0: No derivative control action)

OL. 1 C

Cool-side MV low  –10.0 to +110.0%

0.0

1

limit

OH. 1 C

Cool-side MV high  –10.0 to +110.0%

100.0

1

limit 

C15M List of Parameters

[List of Operation Displays]

Operation Displays 

SP bank 
Bank selection: 

SP

User level details

0: Display in basic / standard / high function,

1: Display in standard / high function,

2: Display in high function.

Initial value may vary depending on model No.

Event bank 
Bank selection: 

Ev

PID bank 
Bank selection: 

PId

Parameter bank
Bank selection: 

PArA

Extension tuning bank 
Bank selection: 

Et

[List of Setup Setting Displays]

Setup bank 

Bank selection: 

StUP

CP-UM-5410EC

(continued on back page)

Display

Item

Contents

Initial User 

value

level

E 1

to   

E5

Internal event 1 to –1999 to +9999

0

0

5, main setting

The decimal point position varies by meeting the 

E 1. Sb

to

Internal event 1 to  internal event operation type.

0

0

E5. Sb

5, sub-setting

0 to 9999 for some operation type.

E 1. Hy

to

Internal event 1 to  0 to 9999

5

0

E5. Hy

5, hysteresis

The decimal point position varies by meeting the 

internal event operation type.

E 1. On

to

Internal event 1 to  0.0 to 999.9 

0

2

E5. On

5, ON delay

(For the delay time unit 0.1s)

E 1. OF

to

Internal event 1 to  0 to 9999 

0

2

E5. OF

5, OFF delay

(Except for the delay time unit 0.1s)

E6

Содержание C15M

Страница 1: ...lure to do so might cause electric shock fire or faulty operation Do not allow lead clippings chips or water to enter the controller case Doing so might cause fire or faulty operation Firmly tighten t...

Страница 2: ...circuit is cut off If you connect two or more current input type controllers in series change the current input to voltage input by connecting a resistor No 81401325 sold separately Prepare a heater c...

Страница 3: ...64 JPt100 0 0 to 200 0 0 to 400 67 Pt100 0 to 500 0 to 900 68 JPt100 0 to 500 0 to 900 rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp 2 3 6 5 1 4 SDC15 7 SDC15 Alarm code Error Cause Countermeasure AL01...

Страница 4: ...3 C 1 FS at 0 to 1mA Event relay outputs ev1 to 3 Contact rating 250Vac 30Vdc 2A resistive load Life Min 100 000 operations Min switching specification 5V 10mA Reference value RS 485 communication Tr...

Страница 5: ...ress Setting is disabled 0 At 1 display display 1st digit Except for 0 During execution of AT example Numeric value Value is decreased at right end digit 0 Completion of AT Ct 1 CT Current Setting is...

Страница 6: ...play Item Contents Initial User value level C 0 1 PV input range Thermocouple T 1 to 6 9 to 11 13 to 21 24 25 1 0 type RTD R 41 to 46 51 to 54 63 64 67 68 41 DC current voltage L 84 86 to 90 88 C 02 T...

Страница 7: ...ty of input assignment D dI 1 8 to Internal contact 0 Direct 0 2 dI3 8 1 to 3 Polarity 1 Reverse dI 1 9 to Internal contact 0 Every internal event 0 2 dI3 9 1 to 3 1 to 5 Internal event numbers Intern...

Страница 8: ...al No 2 Lock bank Bank selection LOC Instrument information bank Bank selection Id Display Item Contents Initial User value level LOC Key lock 0 All settings are enabled 0 0 1 Mode event operation dis...

Страница 9: ...C1 CP UM 5410EC C15M http www azbil com cn products order html 2006 2015 Azbil Corporation All Rights Reserved PV C15MT 81409651 001 1 81409657 001 1 CP UM 5410EC 1 C1...

Страница 10: ...1 2 RS 485 C15MT 59 60 2 44 8 48 48 rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp M3 SDC15 0 0 5 45 50 0 0 5 45 30 0 0 5 48xN 3 0 0 5 45 N 1 2 3 1 2 1 2 3 4 5 6 13 14 15 16 17 18 7 8 9 10 11 12 4 5 6 4...

Страница 11: ...Pt100 200 200 44 JPt100 200 200 45 Pt100 100 300 46 JPt100 100 300 51 Pt100 50 0 200 0 52 JPt100 50 0 200 0 53 Pt100 50 0 100 0 54 JPt100 50 0 100 0 63 Pt100 0 0 200 0 64 JPt100 0 0 200 0 67 Pt100 0 5...

Страница 12: ...24mAdc OFF ON 10s 1ms 10s 250ms 0 20mAdc 4 20mA 600 0 5 FS 23 3 0 1mA 1 FS ev1 250Vac 30Vdc 2A 10 5V 10mA RS 485 3 4800 9600 19200 38400bps CPL MODBUS 0 50 0 40 10 90 RH AC 85 264Vac 50 60Hz 2Hz 100...

Страница 13: ...0 1s 0 2 E1 oF E5 oF 1 5 OFF 0 2 0 1 2 PID PID P 1 0 1 999 9 5 0 0 I 1 0 9999s 0 120 0 d 1 0 9999s 0 30 0 rE 1 10 0 110 0 50 0 0 oL 1 10 0 110 0 0 0 1 oH 1 10 0 110 0 100 0 1 P 1C 0 1 999 9 5 0 0 I 1C...

Страница 14: ...1 0 MV 1 MV 2 MV 3 PV 4 PV 5 SP 6 PV SP 7 CT1 8 CT2 9 MFB C15M 10 SP MV 11 PV MV 0 0 C44 1 1999 9999 1 0 0 0 C45 1 100 0 0 C46 1 MV 0 9999 PV 200 0 C47 2 1 13 0 C48 2 0 C49 2 1999 9999 2 0 0 C50 2 10...

Страница 15: ...3 A 0 OFF 0 1 ON 1 2 DI1 3 DI2 4 9 10 1 11 2 12 3 13 4 14 5 15 17 18 DI1 19 DI2 20 DI3 21 DI4 22 MANUAL 23 READY 24 25 AT 26 SP 27 28 29 PV 30 31 mode 32 1 33 1 2 4 2 dI1 4 dI3 4 1 3 B 0 2 dI1 5 dI3...

Страница 16: ...mode 3 UF MV mode 0 0 C LoC 0 RS 485 read write 1 RS 485 read write 0 2 L LoC 0 read write 1 read write 0 2 PASS 0 15 5 1A 2B 0 0 PS1A 1A 0000 FFFF 16 0000 0 PS2A 2A 0000 FFFF 16 0000 0 PS1b 1B 0000 F...