Display
Item
Contents
Initial User
value
level
C 64
CPL/MODBUS
0: CPL
0
0
1: MODBUS ASCII format
2: MODBUS RTU format
C 65
Station address
0 to 127
0
0
Communication is disabled when "0" is set.
C 66
Transmission
0: 4800bps
2
0
speed
1: 9600bps
2: 19200bps
3: 38400bps
C 67
Data format (data 0: 7bits
1
0
length)
1: 8bits
C 68
Data format
0: Even parity
0
0
(parity)
1: Odd parity
2: No parity
C 69
Data format (stop 0: 1bit
0
0
bits)
1: 2bits
C 70
Communication
1 to 250ms
3
2
minimum response
time
C 7 1
Key operation
0: Standard type
0
2
mode/type
1: Special type
C 72
MODE key
0: Invalid
1
0
function
1: AUTO/MANUAL selection
2: RUN/READY selection
3: AT Stop/Start
4: LSP group selection
5: Release of all DO latches
6: Invalid
7: Communication DI1 selection
8: Invalid
C 73
MODE display
Whether the mode bank setup display is enabled or
255
1
setup
disabled is determined by the sum of the following
weighting:
Bit 0: AUTO/MANUAL display
0: Disabled, +1: Enabled
Bit 1: RUN/READY display
0: Disabled, +2: Enabled
Bit 3: AT stop/start display
0: Disabled, +8: Enabled
Bit 4: DO latch release
0: Disabled, +16: Enabled
Bit 5: Communication DI1 ON/OFF display
0: Disabled, +32: Enabled
Other invalid setup: 0, +4, +64, +128
C 74
PV/SP value
Whether the basic display is enabled or disabled is
15
1
display setup
determined by the sum of the following weighting:
Bit 0: PV display
0: Disabled, +1: Enabled
Bit 1: SP display
0: Disabled, +2: Enabled
Bit 2: LSP group No. display
0: Disabled, +4: Enabled
Other invalid setup: 0, +8
C 75
MV display setup
Whether the basic display is enabled or disabled is
15
1
determined by the sum of the following weighting:
Bit 0: MV display
0: Disabled, +1: Enabled
Bit 1: Heat MV/cool MV display
0: Disabled, +2: Enabled
Bit 3: AT progress display
0: Disabled, +8: Enabled
Other invalid setup: 0, +4
C 76
Event setting value 0: In the operation display mode, the internal event
0
1
display setup
setting value is not displayed.
1: In the operation display mode, the internal event 1
setting value is displayed.
2: In the operation display mode, the internal event 1
to 2 setting value is displayed.
3: In the operation display mode, the internal event 1
to 3 setting value is displayed.
C 77
Event remaining
0: In the operation display mode, the ON/OFF delay
0
1
time display setup
remaining time of the internal event is not
displayed.
1: In the operation display mode, the ON/OFF delay
remaining time of the internal event 1 is displayed.
2: In the operation display mode, the ON/OFF delay
remaining time of the internal event 1 to 2 is
displayed.
3: In the operation display mode, the ON/OFF delay
remaining time of the internal event 1 to 3 is
displayed.
C 78
CT input current
0: In the operation display mode, the CT current
0
1
value display
value is not displayed.
setup
1: In the operation display mode, the CT1 current
value is displayed.
2: In the operation display mode, the CT1 to 2
current value is displayed.
C 79
User level
0: Basic configuration
0
0
1: Standard configuration
2: High function configuration
C 80
LED monitor
0: Disabled
0
2
1: Flashing at RS-485 communication signal
transmission
2: Flashing at RS-485 communication signal
receiving
3: OR (logical sum) of all DI status
4: Flashing at READY
C 90
Number of CT1
0: 800 turns
8
2
turns
1 to 40: CT turns divided by 100.
C 9 1
Number of CT1 0: 1 time
1
2
power wire loops 1 to 6: Number of times
C 92
Number of CT2
0: 800 turns
8
2
turns
1 to 40: CT turns divided by 100.
C 93
Number of CT2
0: 1 time
1
2
power wire loops 1 to 6: Number of times
Display
Item
Contents
Initial User
value
level
C 0 1
PV input range
Thermocouple (T): 1 to 6, 9 to 11, 13 to 21, 24, 25
1
0
type
RTD (R): 41 to 46, 51 to 54, 63, 64, 67, 68
41
DC current/voltage (L): 84, 86 to 90
88
C 02
Temperature unit
0: Centigrade (°C)
0
0
1: Fahrenheit (°F)
C 03
Cold junction
0: Cold junction compensation is performed. (Internal)
0
2
compensation
1: Cold junction compensation is not performed.
(T/C)
(External)
C 04
Decimal point
0: No decimal point
0
0
position
1: One digit below decimal point
2: Two digits below decimal point
3: Three digits below decimal point
(Select ‘0’ or ‘1’ for the RTD range with decimal
point)
C 05
PV range low limit When the PV input range type is thermocouple (T) or
-
0
RTD (R), the setting is disabled although range low
limit is displayed.
–1999 to +9999U when the PV input range type is DC
0
voltage/current (L).
C 06
PV range high
When the PV input range type is thermocouple (T) or
-
0
RTD(R), the setting is disabled although range high
limit is displayed.
–1999 to +9999U when the PV input range type is DC 1000
voltage/current (L).
C 07
SP low limit
PV input range low limit to PV input range high limit
0
1
C 08
SP high limit
1000
1
C 09
Squarer root
0.0 to 100.0%
0.0
2
extraction dropout (0.0: No square root extraction)
C 14
Control action
0: Heat control (reverse action))
0
0
(direct/reverse)
1: Cool control (direct action)
C 15
Selection of MV
0: Control operation is continued.
0
2
at PV alarm
1: MV at PV alarm occurrence is outputted.
occurrence
C 16
MV at PV alarm
–10.0 to +110.0%
0.0
2
occurrence
C 17
MV at READY (at –10.0 to +110.0%
0.0
1
heat-side for
heat/cool control)
C 18
MV at READY (at –10.0 to +110.0%
0.0
1
cool-side)
C 19
Operation at
0: Bump-less
0
1
MANUAL change
1: Preset
C 20
Preset MANUAL
–10.0 to +110.0%
0.0 or
1
value
(Used even at MANUAL mode when power is ON.)
50.0
C 2 1
PID operation
0: Automatic
0
2
initialization
1: Not initialized
function selection
2: Initialized (when SP value different from current
value is inputted.)
C 22
PID operation
–10.0 to +110.0%
0.0 or
2
initial MV
50.0
C 26
Heat/cool control
0: Disabled.
0
0
1: Enabled.
C 27
Heal/cool selection 0: Normal
0
1
1: Energy saving
C 28
Dead zone
–100.0 to +100.0%
0.0
0
C 29
Heal/cool control
–10.0 to +110.0%
50.0
2
selection point
C 30
LSP setting
1 to 4
1
0
system
C 32
SP ramp unit
0: 0.1U/s
1
2
1: 0.1U/min
2: 0.1U/h
C 36
CT1 operation
0: Heater burnout detection
0
0
type
1: Current value measurement
C 37
CT1 output
0: Control output 1
0
0
1: Control output 2
2: Event output 1
3: Event output 2
4: Event output 3
C 38
CT1 measurement 30 to 300ms
30
0
wait time
C 39
CT2 operation type Same as CT1.
0
0
C 40
CT2 output
0
0
C 4 1
CT2 measurement
30
0
wait time
C 42
Control output 1
1: 4 to 2mA
1
0
range
2: 0 to 20mA
C 43
Control output 1
0: MV
0
0
type
1: Heat MV
2: Cool MV
3: PV
4: PV before ratio bias filter
5: SP
6: Deviation (PV-SP)
7: CT1 current value
8: CT2 current value
9: Invalid
10: SP+MV
11: PV+MV
C 44
Control output 1
–1999 to +9999
0.0
0
scaling low limit
(The decimal point position and unit may vary
C 45
Control output 1
depending on the control output 1 type.)
100.0
0
scaling high limit
C 46
Control output 1 0 to 9999
200
0
MV scaling
The decimal point position and unit are same as
for PV.
C 47
Control output 2
Same as control output 1.
1
0
range
C 48
Control output 2
3
0
type
C 49
Control output 2
–1999 to +9999
0
0
scaling low limit
(The decimal point position and unit may vary
C 50
Control output 2
depending on the control output 2 type.)
1000
0
scaling high limit
C 5 1
Control output 2 0 to 9999
200
0
MV scaling
The decimal point position and unit are same as
for PV.
E3
Display
Item
Contents
Initial User
value
level
A--M
AUTO/MANUAL
AUTO
: AUTO mode
AUTO
0
mode selection
MAN
: MANUAL mode
r--r
RUN/READY
RUN
: RUN mode
RUN
0
mode selection
RDY
: READY mode
At
AT Stop/Start
At. OF
: AT Stop
AT Stop
0
selection
At. ON
: AT Start
do Lt
Release all DO
Lt. ON
: Latch continue
Latch
0
latches
Lt. OF
: Latch release
continue
C. dI 1
Communication
dI. OF
: OFF
OFF
0
DI 1
dI. On
: ON
[List of Parameter Setting Displays]
■
Mode bank
Bank selection:
MOdE
Display
Item
Contents
Initial User
value
level
At. ty
AT type
0: Normal (Standard control characteristics)
1
0
1: Immediate response (Control
characteristics immediately responding
to the external disturbance.)
2: Stable (Control characteristics with less
up/down function of PV)
JF. bd
Just-FiTTER setting band
0.00 to 10.00
0.30
2
SP. LG
SP lag constant
0.0 to 999.9
0.0
2
At-P
Proportional band tuning
0.00 to 99.99
1.00
2
factor at AT
At-I
Integration time tuning factor
0.00 to 99.99
1.00
2
at AT
At-d
Derivative time tuning factor
0.00 to 99.99
1.00
2
at AT
Ctr. A
Control algorithm
0: PID (conventional PID)
0
1
1: Ra-PID (high performance type)
JF. Ov
Just-FiTTER overshoot
0 to 100
0
1
suppression factor
St.SA
ST step execution resolution 0.00 to 99.99 %
10.00
2
width
St.Sb
ST step settling bound
0.00 to 10.00 %
0.50
2
St.Hb
ST hunting settling bound
0.00 to 10.00 %
1.00
2
St.ud
ST step ramp change
0: ST is executed when the PV ramp up or
0
1
down.
1: ST is executed only when the PV ramp
up.
Display
Item
Contents
Initial User
value
level
CtrL
Control method
0: ON/OFF control
0 or 1
0
1: PID fixed
2: ST (Self turning)
At. OL
MV low limit at AT
–10.0 to +110.0%
0.0
0
At. OH
MV high limit at AT
–10.0 to +110.0%
100.0
0
dIFF
ON/OFF control differential
0 to 9999U
5
0
OFFS
ON/OFF control operating
–1999 to 9999U
0
2
point differential
FL
PV filter
0.0 to 120.0s
0.0
0
rA
PV ratio
0.001 to 9.999
1.000
1
bI
PV bias
–1999 to +9999U
0
0
CyU
Time proportional cycle unit 1 0: 1s unit
0
2
1: 0.5s fixed (Cycle time is disabled.)
2: 0.2s fixed (Cycle time is disabled.)
3: 0.1s fixed (Cycle time is disabled.)
Cy
Time proportional cycle1
5 to 120s (The output includes the relay
10 or 2
0
output.)
1 to 120s (The output does not include the
relay output.)
CyU2
Time proportional cycle unit 2 0: 1s unit
0
2
1: 0.5s fixed (Cycle time is disabled.)
2: 0.2s fixed (Cycle time is disabled.)
3: 0.1s fixed (Cycle time is disabled.)
Cy2
Time proportional cycle 2
5 to 120s (The output includes the relay
10 or 2
0
output.)
1 to 120s (The output does not include the
relay output.)
tP. ty
Time proportional operation
0: Controllability aiming type
0 or 1
2
type
1: Actuator life aiming type
(Only one ON/OFF operation within time
proportional cycle time)
SPU
SP ramp-up
0.0 to 999.9U (0.0: No ramp)
0.0
2
SPd
SP ramp-down
0.0
2
Display
Item
Contents
Initial User
value
level
SP- 1
to
SP of LSP1 group to SP low limit (C07) to SP high limit (C08)
0
0
SP-4
LSP4 group
Display
Item
Contents
Initial User
value
level
Upper display: PV SP (Target value)
SP low limit (C07) to SP high limit (C08)
0
0
Lower display: SP
LSP 1
LSP No. (1st digit: 1 to LSP system group (C30 Max. 4)
1
0
Lower display:
Value at the
LSP
right end digit)
Out
MV (Manipulated
–10.0 to +110.0%
-
0
Variable)
Setting is disabled in AUTO mode.
(Numeric value does not flash.)
Setting is enabled in MANUAL mode.
(Numeric value flashes.)
HEAt
Heat MV
Setting is disabled
-
0
(Manipulated
–10.0 to +110.0%
Variable)
COOL
Cool MV
-
0
(Manipulated
Variable)
Upper display: PV AT progress
Setting is disabled.
-
0
At 1
(display
display (1st digit
Except for 0: During execution of AT
example)
= Numeric value
(Value is decreased.)
at right end digit)
0: Completion of AT
Ct 1
CT (Current
Setting is disabled.
-
0
transformer)
current value 1
Ct2
CT (Current
Setting is disabled.
-
0
transformer)
current value 2
E 1
Internal event 1
Setting range is different depending on the internal
0
0
main setting
event operation type.
E 1. Sb
Internal event 1
–1999 to +9999U: Except below.
0
0
sub-setting
0 to 9999U: When the setting value is an absolute value.
–199.9 to +999.9%: For MV.
t 1. --
Timer remaining
Setting is disabled.
-
0
time 1
Upper display: The distinction by ON delay or OFF
delay is displayed at the side location of [t1.].
Lower display: Displayed by the unit (either one of
0.1s, s, or min) based on the internal event 1 delay
time unit (E1. the 3rd digit of C3).
E2
Internal event 2
Setting range is different depending on the internal
0
0
main setting
event operation type.
E2. Sb
Internal event 2
–1999 to +9999U: Except below.
0
0
sub-setting
0 to 9999U: When the setting value is an absolute
value.
–199.9 to +999.9%: For MV.
t2. --
Timer remaining
Setting is disabled.
-
0
time 2
Upper display: The distinction by ON delay or OFF
delay is displayed at the side location of [t2.].
Lower display: Displayed by the unit (either one of
0.1s, s, or min) based on the internal event 2 delay
time unit (E2. the 3rd digit of C3).
E3
Internal event 3
Setting range is different depending on the internal
0
0
main setting
event operation type.
E3. Sb
Internal event 3
–1999 to +9999U: Except below.
0
0
sub-setting
0 to 9999U: When the setting value is an absolute value.
–199.9 to +999.9%: For MV.
t3. --
Timer remaining
Setting is disabled.
-
0
time 3
Upper display: The distinction by ON delay or OFF
delay is displayed at the side location of [t3.].
Lower display: Displayed by the unit (either one of
0.1s, s, or min) based on the internal event 3 delay
time unit(E3. the 3rd digit of C3).
Display
Item
Contents
Initial User
value
level
P- 1
Proportional band 0.1 to 999.9%
5.0
0
I- 1
Integration time
0 to 9999s
120
0
(0: No integral control action)
d- 1
Derivative time
0 to 9999s
30
0
(0: No derivative control action)
rE- 1
Manual reset
–10.0 to +110.0%
50.0
0
OL- 1
MV low limit
–10.0 to +110.0%
0.0
1
OH- 1
MV high limit
–10.0 to +110.0%
100.0
1
P- 1 C
Cool-side
0.1 to 999.9%
5.0
0
proportional band
I- 1 C
Cool-side
0 to 9999s
120
0
integration time
(0: No integral control action)
d- 1 C
Cool-side
0 to 9999s
30
0
derivative time
(0: No derivative control action)
OL. 1 C
Cool-side MV low –10.0 to +110.0%
0.0
1
limit
OH. 1 C
Cool-side MV high –10.0 to +110.0%
100.0
1
limit
C15M List of Parameters
[List of Operation Displays]
■
Operation Displays
■
SP bank
Bank selection:
SP
User level details
0: Display in basic / standard / high function,
1: Display in standard / high function,
2: Display in high function.
Initial value may vary depending on model No.
■
Event bank
Bank selection:
Ev
■
PID bank
Bank selection:
PId
■
Parameter bank
Bank selection:
PArA
■
Extension tuning bank
Bank selection:
Et
[List of Setup Setting Displays]
■
Setup bank
Bank selection:
StUP
CP-UM-5410EC
(continued on back page)
Display
Item
Contents
Initial User
value
level
E 1
to
E5
Internal event 1 to –1999 to +9999
0
0
5, main setting
The decimal point position varies by meeting the
E 1. Sb
to
Internal event 1 to internal event operation type.
0
0
E5. Sb
5, sub-setting
0 to 9999 for some operation type.
E 1. Hy
to
Internal event 1 to 0 to 9999
5
0
E5. Hy
5, hysteresis
The decimal point position varies by meeting the
internal event operation type.
E 1. On
to
Internal event 1 to 0.0 to 999.9
0
2
E5. On
5, ON delay
(For the delay time unit 0.1s)
E 1. OF
to
Internal event 1 to 0 to 9999
0
2
E5. OF
5, OFF delay
(Except for the delay time unit 0.1s)
E5
E4