E2
(1) Upper display:
Displays PV values (current temperature, etc.)
or setup items.
(2) Lower display:
Displays SP values (set temperature, etc.) and
other values of setup items.
(3) Mode indicator rdy:
Lights when READY (control stop)
man:
Lights when MANUAL (manual mode)
ev1 to ev3: Lights when event relays are ON.
ot1 to ot2: Lights when the control output is ON.
(4) Mode key:
The operation which was set beforehand can
be done by pressing the key for 1s or more.
Factory setting is RUN / READY selection.
(5) Para key:
Switches the display.
(6)
<
, , keys:
Used for incrementing numeric values and
performing arithmetic shift operations.
(7) Loader connector:
Connects to a personal computer with the
special cable provided in the smart loader
package.
The following shows the flow of the key operation. Various displays and
settings can be called up to the console:
●
PV Input range setup
In the setup setting display mode
[C01]
, press the [<]
•
[ ]
•
[ ] key
to set the lower display to select a desired PV range type.
>> When no keys are pressed for 2 sec. or longer, the flashing of the
numeric value is stopped to set the currently displayed value.
●
SP setup
While the PV/SP is displayed in the operation display mode, press the
[<]
•
[ ]
•
[ ] key to change the SP in the lower display.
>> When no keys are pressed for 2 sec. or longer, the flashing of the
numeric value is stopped to set the currently displayed value.
SP can be set in the parameter setting display mode.
Handling Precautions
· The accuracy of the B thermocouple is ±5%FS for a range of
260°C or less, and ±1%FS for 260 to 800°C.
· The accuracy of the PLII thermocouple(CO1 No.19) in the
range of 0 to 32˚F does not meet the indication accuracy
specified in the Specifications.
· For ranges with a decimal point, tenths are displayed on the
line underneath point.
· Make sure to set the correct number in setup display C01,
according to the type and range of the sensor used. If the
setting is wrong, problems such as large temperature errors in
the output may occur.
Cleaning:
When wiping out the C15M, use the soft and dried cloth.
Parts replacement: Do not replace the parts.
Fuse replacement: When replacing the fuse for the power supply wires, make
sure that the replacement fuse complies with all applicable
safety standards.
Standard IEC127, Cutoff Speed Delayed operation type (T),
Rated Voltage 250V, Rated Current 0.2A
●
PV input
Thermocouple:
K,J,E,T,R,S,B,N (JIS C1602-1995)
PL II (Engelhard Industries Data (ITS90))
WRe5-26 (ASTM E988-96(Reapproved 2002))
DIN U,DIN L (DIN 43710-1985)
Resistance temperature detector (RTD):
Pt100 (JIS C1604-1997)
JPt100 (JIS C1604-1989)
DC voltage:
0 to 1V, 1 to 5V, 0 to 5V, 0 to 10V
DC current:
0 to 20mA, 4 to 20mA
Sampling cycle:
500ms
Accuracy :
±0.5%FS±1digit,
±1%FS±1digit for a negative area of the
thermocouple (at ambient temperature 23±3°C)
Allowable input:
• -0.5 V to +12 V (thermocouple, RTD, DC,
voltage)
• 30 mA max or 4 V max (DC current)
More than the allowable input voltage or
current may damage this device.
●
Digital input
Input type :
Dry contact or open collector
Allowable ON contact resistance :
Max.250
Ω
Allowable OFF contact resistance : Min.100k
Ω
Allowable ON voltage :
Max.1.0V
Terminal current (ON ) :
Approx.7.5mA in case of short circuit
Approx.5.0mA in case of contact resistance
250
Ω
Minimum hold time :
1s or more
●
Current transformer input
Number of input points:
2 points
Input object:
Current transformer with 100 to 4,000 turns
(availability is by 100-turn units)
Optional unit Model No.: QN206A
(800 turns, hole diameter: 5.8 mm)
Optional unit Model No.: QN212A
(800 turns, hole diameter: 12mm)
Current measurement
lower limit:
0.4Aac (800 turns, 1 time)
Formula; Number of turns ÷ (2000 x number
of power wire loops)
Current measurement
upper limit:
50.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of
power wire loops)
Allowable measured current:
70.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of
power wire loops) x 1.4
Display range lower limit:
0.0Aac
Display range upper limit:
70.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of
power wire loops) x 1.4
Display accuracy:
±5%FS
Display resolution:
0.1Aac
●
Control output
•
Relay output
Contact rating :
NO side 250Vac/30Vdc, 3A (resistive load)
NC side 250Vac/30Vdc, 1A (resistive load)
Life :
NO side Min. 50,000 operations
NC side Min. 100,000 operations
Min. switching specifications : 5V, 100mA
Min. ON time / OFF time :
250ms
•
Voltage pulse output (for SSR drive)
Open circuit voltage :
19Vdc±15%
Internal resistance :
82
Ω
±0.5%
Allowable current :
Max. 24mAdc (a higher current might cause
output circuit failure)
Min. OFF time / ON time :
1ms (Time proportional cycle time < 10s)
250ms (Time proportional cycle time
≥
10s)
•
Current output
Output type :
0 to 20mAdc or 4 to 20mAdc current output
Allowable load resistance :
Max.600
Ω
Output accuracy :
±0.5%FS (at ambient temperature 23±3°C)
±1%FS at 0 to 1mA
●
Event relay outputs (ev1 to 3)
Contact rating :
250Vac/30Vdc 2A (resistive load)
Life :
Min. 100,000 operations
Min. switching specification :
5V, 10mA (Reference value)
●
RS-485 communication
Transmission line :
3-wire system
Transmission speed :
4800, 9600, 19200, 38400bps
Communication protocol :
CPL and MODBUS conforming
Terminating resistor :
Do not connect a terminating resistor.
●
Environmental condition
•
Operating conditions
Ambient temperature :
0 to 50°C (Gang-mounting: 0 to 40°C)
Ambient humidity :
10 to 90%RH (Without condensation)
Power supply voltage :
AC Model
85 to 264Vac, 50/60Hz±2Hz
(Rated power voltage 100 to 240Vac 50/60Hz)
•
Transport conditions
Ambient temperature :
–20 to +70°C
Ambient humidity :
10 to 95%RH (Without condensation)
●
Other specifications
Degrees of protection :
Case front side IP66 /NEMA 4 equivalent
(Only for stand-alone mounting on a panel
when an attached gasket is used. )
Power consumption :
AC Model
Max. 12VA (100Vac:8VA, 264Vac:12VA)
(6VA for 100Vac and 9VA for 264Vac to
our company SDC10 equivalent function)
Non-detected power failure time :
Max. 20ms (AC model)
Altitude :
Max. 2000m
Mass :
Approx.150g (with mounting bracket) at
panel mount type
Terminal screw tightening torque : 0.4 to 0.6N·m
Applicable standards :
EN61010-1,
EN61326-1 (For use in industrial locations)
During EMC testing, the reading or output
may fluctuate by ±10 % FS.
Over-voltage category :
Category II (IEC60364-4-443, IEC60664-1)
Allowable pollution degree :
Pollution degree 2
Recommended cables:
For thermocouples:
Connect thermocouple wires to the
terminals directly. When a thermocouple is
connected to terminal block, or wiring
distance is long, connect the wire via a
shielded compensating lead wire.
For input/output other than thermocouples:
Use a JCS 4364 instrument cable or
equivalent. If electromagnetic induction
noise is comparatively low, a shielded
multiconductor microphone cord (MVVS)
may be used.
<
<
<
<
<
<
C01 No. Sensor type
Range[°C]
Range[°F]
1
K
-200 to +1200 -300 to +2200
2
K
0 to 1200
0 to 2200
3
K
0.0 to 800.0
0 to 1500
4
K
0.0 to 600.0
0 to 1100
5
K
0.0 to 400.0
0 to 700
6
K
-200.0 to +400.0 -300 to +700
9
J
0.0 to 800.0
0 to 1500
10
J
0.0 to 600.0
0 to 1100
11
J
-200.0 to +400.0 -300 to +700
13
E
0.0 to 600.0
0 to 1100
14
T
-200.0 to +400.0 -300 to +700
15
R
0 to 1600
0 to 3000
16
S
0 to 1600
0 to 3000
17
B
0 to 1800
0 to 3300
18
N
0 to 1300
0 to 2300
19
PL
II
0 to 1300
0 to 2300
20
WRe5-26
0 to 1400
0 to 2400
21
WRe5-26
0 to 2300
0 to 4200
24
DIN U
-200.0 to +400.0 -300 to +700
25
DIN L
-100.0 to +800.0 -150 to +1500
C01 No. Sensor type Range[°C]
Range[°F]
41
Pt100
-200 to +500 -300 to +900
42
JPt100
-200 to +500 -300 to +900
43
Pt100
-200 to +200 -300 to +400
44
JPt100
-200 to +200 -300 to +400
45
Pt100
-100 to +300 -150 to +500
46
JPt100
-100 to +300 -150 to +500
51
Pt100
-50.0 to +200.0 -50 to +400
52
JPt100 -50.0 to +200.0 -50 to +400
53
Pt100
-50.0 to +100.0 -50 to +200
54
JPt100 -50.0 to +100.0 -50 to +200
63
Pt100
0.0 to 200.0
0 to 400
64
JPt100
0.0 to 200.0
0 to 400
67
Pt100
0 to 500
0 to 900
68
JPt100
0 to 500
0 to 900
rdy
man
ev1
ev2
ev3
ot1
ot2
para
mode
pv
sp
(2)
(3)
(6)
(5)
(1)
(4)
SDC15
Name
Model No.
Mounting bracket (for C15MT) 81409651-001 (Accessory)
Gasket (for C15MT)
81409657-001 (Accessory)
Current transformer
QN206A (5.8mm hole dia.)
QN212A (12mm hole dia.)
Hard cover
81446442-001
Soft cover
81446443-001
Terminal cover
81446898-001
(7)
SDC15
Alarm code
Error
Cause
Countermeasure
AL01
PV input error
Sensor line break, incorrect
Checking wiring or
(over range)
wiring, incorrect range code
reset range code.
setting
AL02
PV input error
Sensor line break, incorrect
(under range)
wiring, incorrect range code
setting
AL03
CJ failure
Terminal temperature
Checking the allowable
compensation unit failure
ambient temperature.
(thermocouple)
PV input error
Sensor line break, incorrect
Checking wiring.
wiring (RTD)
AL11
CT input failure
A current exceeding the upper
• Use a CT with the
(over-range)
limit of the display range was
correct number of
(CT input 1 or 2,or both) measured. The number of CT
turns for the
turns or the number of CT power
display range.
wire loops is incorrectly set, or
• Reset the number of
wiring is incorrect.
CT turns.
•
Reset the number of
CT power wire loops.
• Check the wiring.
AL70
A/D conversion error
Defective A/D converter
Replace unit.
AL95
Parameter error
•Power turned OFF during fixing
Reset data or replace
of data
unit.
•
Data corrupted due to noise, etc.
AL96
Adjustment data error
•Power turned OFF during fixing
of data
•
Data corrupted due to noise, etc.
AL97
Parameter error
Data corrupted due to noise, etc.
(RAM area)
AL98
Adjustment data error
Data corrupted due to noise, etc.
(RAM area)
AL99
ROM error
Data corrupted due to noise, etc.
Replace unit.
PV range table
Part names and functions
Key Operation and Setting
Alarm code table
Maintenance
Specifications
Accessories and optional parts
Model selection table
Display when the power
is turned ON.
Keep the [para]
key pressed for
2 sec. or longer.
PV/SP display
Press the [para] key.
MV display
Other display and setup
(Operate the [para] key
repeatedly.)
Press the [para] key.
Press the [para] key.
AUTO/MANUAL
selection
Press the [para] key.
RUN/READY
selection
Other setup
(Operate the [para] key
repeatedly.)
Press the [para] key.
Press the [para] key.
Operation display
Press the [mode]
key.
Keep the [para]
key pressed for
2 sec. or longer.
Off.
The mode indicator
is lit sequentially
from the left.
Off.
No key operation for
3 minutes or more.
No key operation for
3 minutes or more.
Keep the [para] key pressed
for 2 sec. or longer.
Press the [mode] key.
mode
pv
sp
mode
pv
sp
mode
pv
sp
mode
pv
sp
mode
pv
sp
mode
pv
sp
rdy
man
ev1
ev2
ev3
ot1
ot2
para
mode
pv
sp
The mode indicators are lit
sequentially from the left during a
period of 6 sec. after the power has
been turned ON while both the upper
display and lower display are off.
When all mode indicators have been
lit, the display is changed to the
operation display.
Parameter setup
display
PV range type
setup
Press the [para] key.
Temperature unit
setup
Other setup
(Operate the [para] key
repeatedly.)
Press the [para] key.
Press the [para] key.
Setup setting display
The display and setup status shown above are examples for
explanation. Therefore, some displays or settings are not
shown actually according to the model and/or setup contents.
C01 No.
Input type
Range
84
0 to 1V
86
1 to 5V
87
0 to 5V
88
0 to 10V
89
0 to 20mA
90
4 to 20mA
The scaling and
decimal point position
can be changed
variably in a range of
–1999 to +9999
Basic Mounting
Control
PV Power Optional Additional
Specifications
model No.
output
input
supply
functions processing
C15M
T
Panel mount type
Control output 1
Control output 2
R0
Relay output (NO) Relay output (NC)
V0
Voltage pulse output
None
(for SSR drive)
C0
Current output
None
T
Thermocouple input
(K, J, E, T, R, S, B, N, PL
II,
WRe5-26,
DINU, DINL)
R
RTD input (Pt100/JPt 100)
L
DC voltage /DC current input (0 to 1Vdc,
1 to 5Vdc, 0 to 5Vdc, 0 to 10Vdc, 0 to
20mAdc, 4 to 20mAdc)
A
AC Model (100 to 240Vac)
01
Event relay output: 3 points
02
Event relay output: 3 points
Current transformer input: 2 points
Digital input: 2 points
03
Event relay output: 3 points
Current transformer input: 2 points
RS-485 communication
00
Chinese (Simplified)
01
Chinese (Traditional)
E3