(1) Upper display:

Displays PV values (current temperature, etc.)
or setup items. 

(2) Lower display:

Displays SP values (set temperature, etc.) and
other values of setup items.

(3) Mode indicator rdy:

Lights when READY (control stop)

man:

Lights when MANUAL (manual mode)

ev1 to ev3: Lights when event relays are ON.
ot1 to ot2: Lights when the control output is ON.

(4) Mode key:

The operation which was set beforehand can
be done by pressing the key for 1s or more. 
Factory setting is RUN / READY selection.

(5) Para key:

Switches the display.

(6) 

<

,  ,  keys:

Used for incrementing numeric values and
performing arithmetic shift operations.

(7) Loader connector: 

Connects to a personal computer with the 
special cable provided in the smart loader 
package. 

The following shows the flow of the key operation.  Various displays and
settings can be called up to the console:

PV Input range setup

In the setup setting display mode

[C01]

, press the [<] 

[ ] 

[ ] key

to set the lower display to select a desired PV range type.

>> When no keys are pressed for 2 sec. or longer, the flashing of the

numeric value is stopped to set the currently displayed value.

SP setup

While the PV/SP is displayed in the operation display mode, press the
[<] 

[ ] 

[ ] key to change the SP in the lower display.

>> When no keys are pressed for 2 sec. or longer, the flashing of the

numeric value is stopped to set the currently displayed value.
SP can be set in the parameter setting display mode.

Handling Precautions

· The accuracy of the B thermocouple is ±5%FS for a range of

260°C or less, and ±1%FS for 260 to 800°C.

· The accuracy of the PLII thermocouple(CO1 No.19) in the

range of 0 to 32˚F does not meet the indication accuracy

specified in the Specifications.

· For ranges with a decimal point, tenths are displayed on the

line underneath point.

· Make sure to set the correct number in setup display C01,

according to the type and range of the sensor used. If the

setting is wrong, problems such as large temperature errors in

the output may occur.

Cleaning:

When wiping out the C15M, use the soft and dried cloth.

Parts replacement: Do not replace the parts. 
Fuse replacement: When replacing the fuse for the power supply wires, make

sure that the replacement fuse complies with all applicable
safety standards.
Standard   IEC127, Cutoff Speed   Delayed operation type (T),
Rated Voltage   250V, Rated Current   0.2A

PV input
Thermocouple:

K,J,E,T,R,S,B,N (JIS C1602-1995)
PL II (Engelhard Industries Data (ITS90))
WRe5-26 (ASTM E988-96(Reapproved 2002))
DIN U,DIN L (DIN 43710-1985)

Resistance temperature detector (RTD):

Pt100 (JIS C1604-1997)
JPt100 (JIS C1604-1989)

DC voltage:

0 to 1V, 1 to 5V, 0 to 5V, 0 to 10V

DC current:

0 to 20mA, 4 to 20mA

Sampling cycle:

500ms

Accuracy :

±0.5%FS±1digit, 
±1%FS±1digit for a negative area of the
thermocouple (at ambient temperature 23±3°C)

Allowable input:

• -0.5 V to +12 V (thermocouple, RTD, DC,

voltage)

• 30 mA max or 4 V max (DC current)

More than the allowable input voltage or
current may damage this device.

Digital input

Input type :

Dry contact or open collector

Allowable ON contact resistance :

Max.250

Allowable OFF contact resistance : Min.100k

Allowable ON voltage :

Max.1.0V

Terminal current (ON ) :

Approx.7.5mA in case of short circuit

Approx.5.0mA in case of contact resistance

250

Minimum hold time :

1s or more

Current transformer input

Number of input points:

2 points

Input object:

Current transformer with 100 to 4,000 turns

(availability is by 100-turn units)

Optional unit Model No.: QN206A

(800 turns, hole diameter: 5.8 mm)

Optional unit Model No.: QN212A

(800 turns, hole diameter: 12mm)

Current measurement

lower limit:

0.4Aac (800 turns, 1 time)

Formula; Number of turns ÷ (2000 x number

of power wire loops)

Current measurement

upper limit:

50.0Aac (800 turns, 1 time)

Formula; Number of turns ÷ (16 x number of

power wire loops)

Allowable measured current:

70.0Aac (800 turns, 1 time)

Formula; Number of turns ÷ (16 x number of

power wire loops) x 1.4

Display range lower limit:

0.0Aac

Display range upper limit:

70.0Aac (800 turns, 1 time)

Formula; Number of turns ÷ (16 x number of

power wire loops) x 1.4

Display accuracy:

±5%FS

Display resolution:

0.1Aac

Control output

Relay output

Contact rating :

NO side  250Vac/30Vdc, 3A (resistive load)
NC side  250Vac/30Vdc, 1A (resistive load)

Life :

NO side  Min. 50,000 operations
NC side  Min. 100,000 operations

Min. switching specifications : 5V, 100mA
Min. ON time / OFF time :

250ms

Voltage pulse output (for SSR drive)

Open circuit voltage :

19Vdc±15%

Internal resistance :

82

±0.5%

Allowable current :

Max. 24mAdc (a higher current might cause

output circuit failure)

Min. OFF time / ON time :

1ms (Time proportional cycle time < 10s)
250ms (Time proportional cycle time 

10s)

Current output

Output type :

0 to 20mAdc or 4 to 20mAdc current output

Allowable load resistance :

Max.600

Output accuracy :

±0.5%FS (at ambient temperature 23±3°C)

±1%FS at 0 to 1mA

Event relay outputs (ev1 to 3)
Contact rating :

250Vac/30Vdc 2A (resistive load)

Life :

Min. 100,000 operations 

Min. switching specification :

5V, 10mA (Reference value)

RS-485 communication

Transmission line :

3-wire system

Transmission speed :

4800, 9600, 19200, 38400bps

Communication protocol :

CPL and MODBUS conforming

Terminating resistor :

Do not connect a terminating resistor.

Environmental condition

Operating conditions

Ambient temperature :

0 to 50°C (Gang-mounting: 0 to 40°C)

Ambient humidity :

10 to 90%RH (Without condensation)

Power supply voltage :

AC Model
85 to 264Vac, 50/60Hz±2Hz
(Rated power voltage 100 to 240Vac 50/60Hz)

Transport conditions

Ambient temperature :

–20 to +70°C

Ambient humidity :

10 to 95%RH (Without condensation)

Other specifications
Degrees of protection :

Case front side IP66 /NEMA 4 equivalent
(Only for stand-alone mounting on a panel
when an attached gasket is used. )

Power consumption :

AC Model

Max. 12VA (100Vac:8VA, 264Vac:12VA)

(6VA for 100Vac and 9VA for 264Vac to
our company SDC10 equivalent function)

Non-detected power failure time :

Max. 20ms (AC model)

Altitude :

Max. 2000m

Mass :

Approx.150g (with mounting bracket) at

panel mount type

Terminal screw tightening torque : 0.4 to 0.6N·m 
Applicable standards :

EN61010-1, 
EN61326-1 (For use in industrial locations)
During EMC testing, the reading or output
may fluctuate by ±10 % FS.

Over-voltage category :

Category II (IEC60364-4-443, IEC60664-1)

Allowable pollution degree :

Pollution degree 2

Recommended cables:

For thermocouples:

Connect thermocouple wires to the
terminals directly. When a thermocouple is
connected to terminal block, or wiring
distance is long, connect the wire via a
shielded compensating lead wire.

For input/output other than thermocouples:

Use a JCS 4364 instrument cable or
equivalent. If electromagnetic induction
noise is comparatively low, a shielded
multiconductor microphone cord (MVVS)
may be used.

<

<

<

<

<

<

C01 No. Sensor type

Range[°C]

Range[°F]

1

K

-200 to +1200 -300 to +2200

2

K

0 to 1200

0 to 2200

3

K

0.0 to 800.0

0 to 1500

4

K

0.0 to 600.0

0 to 1100

5

K

0.0 to 400.0

0 to 700

6

K

-200.0 to +400.0 -300 to +700

9

J

0.0 to 800.0

0 to 1500

10

J

0.0 to 600.0

0 to 1100

11

J

-200.0 to +400.0 -300 to +700

13

E

0.0 to 600.0

0 to 1100

14

T

-200.0 to +400.0 -300 to +700

15

R

0 to 1600

0 to 3000

16

S

0 to 1600

0 to 3000

17

B

0 to 1800

0 to 3300

18

N

0 to 1300

0 to 2300

19

PL

II

0 to 1300

0 to 2300

20

WRe5-26

0 to 1400

0 to 2400

21

WRe5-26

0 to 2300

0 to 4200

24

DIN  U

-200.0 to +400.0 -300 to +700

25

DIN  L

-100.0 to +800.0 -150 to +1500

C01 No. Sensor type Range[°C]

Range[°F]

41

Pt100

-200 to +500 -300 to +900

42

JPt100

-200 to +500 -300 to +900

43

Pt100

-200 to +200 -300 to +400

44

JPt100

-200 to +200 -300 to +400

45

Pt100

-100 to +300 -150 to +500

46

JPt100

-100 to +300 -150 to +500

51

Pt100

-50.0 to +200.0 -50 to +400

52

JPt100 -50.0 to +200.0 -50 to +400

53

Pt100

-50.0 to +100.0 -50 to +200

54

JPt100 -50.0 to +100.0 -50 to +200

63

Pt100

0.0 to 200.0

0 to 400

64

JPt100

0.0 to 200.0

0 to 400

67

Pt100

0 to 500

0 to 900

68

JPt100

0 to 500

0 to 900

rdy

man

ev1

ev2

ev3

ot1

ot2

para

mode

pv

sp

(2)

(3)

(6)

(5)

(1)

(4)

SDC15

Name

Model No.

Mounting bracket (for C15MT) 81409651-001 (Accessory)
Gasket (for C15MT)

81409657-001 (Accessory)

Current transformer

QN206A (5.8mm hole dia.)
QN212A (12mm hole dia.)

Hard cover

81446442-001

Soft cover

81446443-001

Terminal cover

81446898-001

(7)

SDC15

Alarm code

Error

Cause

Countermeasure

AL01

PV input error

Sensor line break, incorrect

Checking wiring or

(over range)

wiring, incorrect range code

reset range code.

setting

AL02

PV input error 

Sensor line break, incorrect

(under range)

wiring, incorrect range code
setting

AL03

CJ failure

Terminal temperature 

Checking the allowable

compensation unit failure 

ambient temperature.

(thermocouple)

PV input error 

Sensor line break, incorrect

Checking wiring.

wiring (RTD)

AL11

CT input failure

A current exceeding the upper

• Use a CT with the 

(over-range)

limit of the display range was

correct number of

(CT input 1 or 2,or both) measured. The number of CT

turns for the

turns or the number of CT power

display range.

wire loops is incorrectly set, or

• Reset the number of

wiring is incorrect.

CT turns.

• 

Reset the number of 

CT power wire loops.

• Check the wiring.

AL70

A/D conversion error

Defective A/D converter

Replace unit.

AL95

Parameter error

•Power turned OFF during fixing

Reset data or replace

of data

unit.

Data corrupted due to noise, etc.

AL96

Adjustment data error

•Power turned OFF during fixing

of data

Data corrupted due to noise, etc.

AL97

Parameter error

Data corrupted due to noise, etc.

(RAM area)

AL98

Adjustment data error

Data corrupted due to noise, etc.

(RAM area)

AL99

ROM error

Data corrupted due to noise, etc.

Replace unit.

PV range table

Part names and functions

Key Operation and Setting

Alarm code table

Maintenance

Specifications

Accessories and optional parts

Model selection table

Display when the power

is turned ON.

Keep the [para]

key pressed for

2 sec. or longer.

PV/SP display

Press the [para] key.

MV display

Other display and setup

(Operate the [para] key 

repeatedly.)

Press the [para] key.

Press the [para] key.

AUTO/MANUAL

selection
Press the [para] key.

RUN/READY 

selection

Other setup

(Operate the [para] key

repeatedly.)

Press the [para] key.

Press the [para] key.

Operation display

Press the [mode]

key.

Keep the [para] 

key pressed for 

2 sec. or longer.

Off.

The mode indicator 

is lit sequentially 

from the left.

Off.

No key operation for 

3 minutes or more.

No key operation for 

3 minutes or more.

Keep the [para] key pressed 

for 2 sec. or longer.

Press the [mode] key.

mode

pv

sp

mode

pv

sp

mode

pv

sp

mode

pv

sp

mode

pv

sp

mode

pv

sp

rdy

man

ev1

ev2

ev3

ot1

ot2

para

mode

pv

sp

The mode indicators are lit 

sequentially from the left during a 

period of 6 sec. after the power has 

been turned ON while both the upper 

display and lower display are off.  

When all mode indicators have been 

lit, the display is changed to the 

operation display.

Parameter setup

display

PV range type 

setup
Press the [para] key.

Temperature unit 

setup

Other setup

(Operate the [para] key

repeatedly.)

Press the [para] key.

Press the [para] key.

Setup setting display

The display and setup status shown above are examples for 

explanation.  Therefore, some displays or settings are not 

shown actually according to the model and/or setup contents.

C01 No.

Input type

Range

84

0 to 1V

86

1 to 5V

87

0 to 5V

88

0 to 10V

89

0 to 20mA

90

4 to 20mA

The scaling and
decimal point position
can be changed
variably in a range of
–1999 to +9999

Basic Mounting

Control

PV  Power Optional Additional

Specifications

model No.

output

input

supply

functions processing

C15M

T

Panel mount type

Control output 1

Control output 2

R0

Relay output (NO) Relay output (NC)

V0

Voltage pulse output

None

(for SSR drive)

C0

Current output

None

T

Thermocouple input
(K, J, E, T, R, S, B, N, PL

II, 

WRe5-26,

DINU, DINL)

R

RTD input (Pt100/JPt 100)

L

DC voltage /DC current input (0 to 1Vdc,
1 to 5Vdc, 0 to 5Vdc, 0 to 10Vdc, 0 to
20mAdc, 4 to 20mAdc)

A

AC Model (100 to 240Vac)

01

Event relay output: 3 points

02

Event relay output: 3 points
Current transformer input: 2 points
Digital input: 2 points

03

Event relay output: 3 points
Current transformer input: 2 points
RS-485 communication

00

Chinese (Simplified)

01

Chinese (Traditional)

E3

E2

Содержание C15M

Страница 1: ...lure to do so might cause electric shock fire or faulty operation Do not allow lead clippings chips or water to enter the controller case Doing so might cause fire or faulty operation Firmly tighten t...

Страница 2: ...circuit is cut off If you connect two or more current input type controllers in series change the current input to voltage input by connecting a resistor No 81401325 sold separately Prepare a heater c...

Страница 3: ...64 JPt100 0 0 to 200 0 0 to 400 67 Pt100 0 to 500 0 to 900 68 JPt100 0 to 500 0 to 900 rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp 2 3 6 5 1 4 SDC15 7 SDC15 Alarm code Error Cause Countermeasure AL01...

Страница 4: ...3 C 1 FS at 0 to 1mA Event relay outputs ev1 to 3 Contact rating 250Vac 30Vdc 2A resistive load Life Min 100 000 operations Min switching specification 5V 10mA Reference value RS 485 communication Tr...

Страница 5: ...ress Setting is disabled 0 At 1 display display 1st digit Except for 0 During execution of AT example Numeric value Value is decreased at right end digit 0 Completion of AT Ct 1 CT Current Setting is...

Страница 6: ...play Item Contents Initial User value level C 0 1 PV input range Thermocouple T 1 to 6 9 to 11 13 to 21 24 25 1 0 type RTD R 41 to 46 51 to 54 63 64 67 68 41 DC current voltage L 84 86 to 90 88 C 02 T...

Страница 7: ...ty of input assignment D dI 1 8 to Internal contact 0 Direct 0 2 dI3 8 1 to 3 Polarity 1 Reverse dI 1 9 to Internal contact 0 Every internal event 0 2 dI3 9 1 to 3 1 to 5 Internal event numbers Intern...

Страница 8: ...al No 2 Lock bank Bank selection LOC Instrument information bank Bank selection Id Display Item Contents Initial User value level LOC Key lock 0 All settings are enabled 0 0 1 Mode event operation dis...

Страница 9: ...C1 CP UM 5410EC C15M http www azbil com cn products order html 2006 2015 Azbil Corporation All Rights Reserved PV C15MT 81409651 001 1 81409657 001 1 CP UM 5410EC 1 C1...

Страница 10: ...1 2 RS 485 C15MT 59 60 2 44 8 48 48 rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp M3 SDC15 0 0 5 45 50 0 0 5 45 30 0 0 5 48xN 3 0 0 5 45 N 1 2 3 1 2 1 2 3 4 5 6 13 14 15 16 17 18 7 8 9 10 11 12 4 5 6 4...

Страница 11: ...Pt100 200 200 44 JPt100 200 200 45 Pt100 100 300 46 JPt100 100 300 51 Pt100 50 0 200 0 52 JPt100 50 0 200 0 53 Pt100 50 0 100 0 54 JPt100 50 0 100 0 63 Pt100 0 0 200 0 64 JPt100 0 0 200 0 67 Pt100 0 5...

Страница 12: ...24mAdc OFF ON 10s 1ms 10s 250ms 0 20mAdc 4 20mA 600 0 5 FS 23 3 0 1mA 1 FS ev1 250Vac 30Vdc 2A 10 5V 10mA RS 485 3 4800 9600 19200 38400bps CPL MODBUS 0 50 0 40 10 90 RH AC 85 264Vac 50 60Hz 2Hz 100...

Страница 13: ...0 1s 0 2 E1 oF E5 oF 1 5 OFF 0 2 0 1 2 PID PID P 1 0 1 999 9 5 0 0 I 1 0 9999s 0 120 0 d 1 0 9999s 0 30 0 rE 1 10 0 110 0 50 0 0 oL 1 10 0 110 0 0 0 1 oH 1 10 0 110 0 100 0 1 P 1C 0 1 999 9 5 0 0 I 1C...

Страница 14: ...1 0 MV 1 MV 2 MV 3 PV 4 PV 5 SP 6 PV SP 7 CT1 8 CT2 9 MFB C15M 10 SP MV 11 PV MV 0 0 C44 1 1999 9999 1 0 0 0 C45 1 100 0 0 C46 1 MV 0 9999 PV 200 0 C47 2 1 13 0 C48 2 0 C49 2 1999 9999 2 0 0 C50 2 10...

Страница 15: ...3 A 0 OFF 0 1 ON 1 2 DI1 3 DI2 4 9 10 1 11 2 12 3 13 4 14 5 15 17 18 DI1 19 DI2 20 DI3 21 DI4 22 MANUAL 23 READY 24 25 AT 26 SP 27 28 29 PV 30 31 mode 32 1 33 1 2 4 2 dI1 4 dI3 4 1 3 B 0 2 dI1 5 dI3...

Страница 16: ...mode 3 UF MV mode 0 0 C LoC 0 RS 485 read write 1 RS 485 read write 0 2 L LoC 0 read write 1 read write 0 2 PASS 0 15 5 1A 2B 0 0 PS1A 1A 0000 FFFF 16 0000 0 PS2A 2A 0000 FFFF 16 0000 0 PS1b 1B 0000 F...

Отзывы: