Thank you for purchasing the C15M.
Before operating this product described in this User's Manual,
please take note of the following points regarding safety. 
Be sure to keep this manual nearby for handy reference.

Please read the "Terms and Conditions" from the following URL
before ordering or use:
http://www.azbil.com/products/bi/order.html

This manual explains handling precautions, mounting, wiring procedures,

PV range types, parameter list and main specifications only.

Check the following items when removing the C15MT from its package:

Name

Part No.

Q'ty

Remarks

Mounting Bracket

81409651-001

1

Gasket

81409657-001

1

User's Manual 

CP-UM-5410EC

1

This Manual

Location

Install the controller in the following locations:
· Common mode voltages for I/O excluding the power supply and relay

contact output:  The voltage to ground is 30Vr.m.s max., 42.4V peak

max., and 60Vdc max.

· Not high or low temperature / humidity.
· Free from silicone gas and other corrosive gases such as sulfide gas.
· Less dust or soot.
· Appropriately processed locations to prevent direct sunlight, wind or rain.
· Less mechanical vibration and shock.
· Not close to the high voltage line, welding machine or electrical noise

generating source.

· The minimum 15 meters away from the high voltage ignition device for a

boiler.

· Less effect by the magnetic.
· No flammable liquid or gas.
· Indoors.

Mounting Procedure

· The mounting must be horizontal within 10 degrees tilted in back side

lowering or within 10 degrees tilted in back side rising.

· In the case of panel mount type (C15MT), the mounting panel should be

used with a thickness of less than 9 mm of firm board.

External Dimensions

C15MT (Panel Mount Type)

(unit: mm)

Handling Precautions

• To fasten this controller onto the panel, tighten a mounting

bracket screws, and turn one more half turn when there is no

play between the bracket and panel. Excessively tightening

the screws may deform the controller case.

Panel Cutout Dimensions

Stand-alone mounting

Gang-mounting

Handling Precautions

• When three or more units are gang-mounted horizontally, the

maximum allowable ambient temperature is 40°C.

• If dustproof or waterproof protection is required, mount the device

using the stand-alone mounting method.  If gang-mounted,

dustproof and waterproof protection may not be maintained.

• Provide a space of at least 50mm or more above and below

the controller.

Be sure to provide a switch within operator reach for shutting OFF the main
power supply to the controller in the main supply wiring.
Also, in case of AC power supply models, the main supply wiring also requires
a time-lagged type (T) fuse (rated current: 0.2A, rated voltage: 250 V).
(IEC127) 
The following table shows the meaning of the symbols in the terminal wiring
label on the controller side:

Handling Precautions

• Before wiring the C15M, verify the controller's model No. and

terminal Nos. written on the label on the side of the body.

Inspect all wiring once wiring work for the C15M has been

completed. 

• Provide a distance of at least 50cm between I/O lead wires or

communications lead wires and power lead wires of 100V min.

Also, do not pass these lead wires through the same piping or

wiring duct.

• Be careful not to allow any crimp terminals lugs to touch

adjacent terminals.

• To connect 2 (max.) crimp terminals to the same

terminal screw, bend the crimp terminals

beforehand.

• Connect wires to terminals 1 - 6 and 13 - 18 from the left

(when viewing the terminal block).

• Use crimp terminals compatible with M3

terminal screws, as shown in the diagram.

A: 5.8mm max. B: 5.5 to 7.6mm

• When the power to this controller is turned off, the current

input circuit is cut off. If you connect two or more current-input

type controllers in series, change the current input to voltage

input by connecting a resistor (No. 81401325, sold separately).

• Prepare a heater current conductor to send a heater current

through the current transformer.

Do not use a heater current that exceeds the specified

permissible current as this may damage the controller. 

• The controller requires about 6 seconds to start up once the

power is turned ON.  The controller can be used once it has

started up. However, it is recommended to allow a warm-up

time of at least 30 minutes to attain the specified accuracy.

• The current transformer input cannot be used for phase

control.

• There is no isolation provided between control output 1 and

control output 2. Install an isolator as required.

• Do not connect a terminating resistor to either end of the RS-

485 communications line.

Doing so may interfere with communication.

• Make sure that devices and equipment connected to this

device have reinforced insulation suitable for the maximum

operating voltage of this device's power supply and

input/output ports.

Connection of C15MT

I/O isolation

Items surrounded by solid lines are insulated from other signals.
Availability of input or output is based on a model number.

E1

CP-UM-5410EC

(Not for use in Japan)

C15M

Single Loop Controller

User's Manual 

"Installation"

Use the C15M within the operating ranges recommended in the

specifications (temperature, humidity, voltage, vibration, shock,

mounting direction, atmosphere, etc.). 

Failure to do so might cause fire or faulty operation.
Do not block ventilation holes. 

Doing so might cause fire or faulty operation.
Wire the C15M properly according to predetermined standards.

Also wire the C15M using specified power leads according to

recognized installation methods.

Failure to do so might cause electric shock, fire or faulty operation.
Do not allow lead clippings, chips or water to enter the controller case.

Doing so might cause fire or faulty operation.
Firmly tighten the terminal screws at the torque listed in the

specifications.  Insufficient tightening of terminal screws might

cause electric shock or fire.
Do not use unused terminals on the C15M as relay terminals.

Doing so might cause electric shock, fire or faulty operation.
We recommend attaching the terminal cover (sold separately)

after wiring the C15M.

Failure to do so might cause electric shock, fire or faulty operation.
Use the relays within the recommended service life.

Continuous use might cause fire or faulty operation.
If there is a risk of a power surge caused by lightning, use a surge

absorber (surge protector) to prevent fire or device failure.
Do not operate the keys with a propelling pencil or sharp-tipped

object.  Doing so might cause faulty operation.

CAUTION

59

60

2

44.8

48

48

rdy

man

ev1

ev2

ev3

ot1

ot2

para

mode

SDC15

pv

sp

Mounting bracket

(Accessory)

M3

Terminal screw

 0

+0.5

45

50 min.

 0

+0.5

45

30 min.

 0

+0.5

(48xN -3)

 0

+0.5

45

(N: number of mounted units)

1
2
3

1
2

1
2
3

4
5
6

13
14
15

16
17
18

7
8
9

10
11
12

4
5
6

4
5
6

7
8
9

10

+

+

11

12

1

2

3

C

B
A

Control outputs

Event outputs

Power supply

Relay

Voltage pulse

PV inputs

Thermo-

couple

RTD

Relay

AC power supply
100 to 240Vac

16
17
18

16
17
18

DA
DB
SG

1

2

DI/COM

Digital
inputs

RS-485
Communication

13
14
15

CT1

CT2

Current transformer inputs

1
2

+

Current

WARNING

Warnings are indicated when mishandling
this product might result in death or serious
injury to the user.

CAUTION

Cautions are indicated when mishandling
this product might result in minor injury to
the user, or only physical damage to this
product.

Power supply
PV input
Current Transformer input 1
Current Transformer input 2
Loader communication
Digital input 1
Digital input 2
RS-485 Communication

Internal
Circuit

Control output 1
Control output 2

Event output 1
Event output 2 
Event output 3

Mounting

Wiring

SAFETY PRECAUTIONS

(unit: mm)

Symbols

Meaning

AC power supply
Caution, fear of electric shock
Caution

Be sure that the user receives this manual before the product is
used.

Copying or duplicating this user’s manual in part or in whole is
forbidden. The information and specifications in this manual are
subject to change without notice.

Considerable effort has been made to ensure that this manual is
free from inaccuracies and omissions. If you should find an error
or omission, please contact Azbil Corporation.

In no event is Azbil Corporation liable to anyone for any indirect,
special or consequential damages as a result of using this prod-
uct.

2006-2015 Azbil Corporation All Rights Reserved.

NOTICE

Note that incorrect wiring of the C15M can damage the C15M and

lead to other hazards.  Check that the C15M has been correctly

wired before turning the power ON.
Before wiring, or removing/mounting the C15M, be sure to turn

the power OFF.  Failure to do so might cause electric shock.
Do not touch electrically charged parts such as the power

terminals.  Doing so might cause electric shock.
Do not disassemble the C15M. 

Doing so might cause electric shock or faulty operation.

WARNING

A

B

Unpacking

E1

Содержание C15M

Страница 1: ...lure to do so might cause electric shock fire or faulty operation Do not allow lead clippings chips or water to enter the controller case Doing so might cause fire or faulty operation Firmly tighten t...

Страница 2: ...circuit is cut off If you connect two or more current input type controllers in series change the current input to voltage input by connecting a resistor No 81401325 sold separately Prepare a heater c...

Страница 3: ...64 JPt100 0 0 to 200 0 0 to 400 67 Pt100 0 to 500 0 to 900 68 JPt100 0 to 500 0 to 900 rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp 2 3 6 5 1 4 SDC15 7 SDC15 Alarm code Error Cause Countermeasure AL01...

Страница 4: ...3 C 1 FS at 0 to 1mA Event relay outputs ev1 to 3 Contact rating 250Vac 30Vdc 2A resistive load Life Min 100 000 operations Min switching specification 5V 10mA Reference value RS 485 communication Tr...

Страница 5: ...ress Setting is disabled 0 At 1 display display 1st digit Except for 0 During execution of AT example Numeric value Value is decreased at right end digit 0 Completion of AT Ct 1 CT Current Setting is...

Страница 6: ...play Item Contents Initial User value level C 0 1 PV input range Thermocouple T 1 to 6 9 to 11 13 to 21 24 25 1 0 type RTD R 41 to 46 51 to 54 63 64 67 68 41 DC current voltage L 84 86 to 90 88 C 02 T...

Страница 7: ...ty of input assignment D dI 1 8 to Internal contact 0 Direct 0 2 dI3 8 1 to 3 Polarity 1 Reverse dI 1 9 to Internal contact 0 Every internal event 0 2 dI3 9 1 to 3 1 to 5 Internal event numbers Intern...

Страница 8: ...al No 2 Lock bank Bank selection LOC Instrument information bank Bank selection Id Display Item Contents Initial User value level LOC Key lock 0 All settings are enabled 0 0 1 Mode event operation dis...

Страница 9: ...C1 CP UM 5410EC C15M http www azbil com cn products order html 2006 2015 Azbil Corporation All Rights Reserved PV C15MT 81409651 001 1 81409657 001 1 CP UM 5410EC 1 C1...

Страница 10: ...1 2 RS 485 C15MT 59 60 2 44 8 48 48 rdy man ev1 ev2 ev3 ot1 ot2 para mode pv sp M3 SDC15 0 0 5 45 50 0 0 5 45 30 0 0 5 48xN 3 0 0 5 45 N 1 2 3 1 2 1 2 3 4 5 6 13 14 15 16 17 18 7 8 9 10 11 12 4 5 6 4...

Страница 11: ...Pt100 200 200 44 JPt100 200 200 45 Pt100 100 300 46 JPt100 100 300 51 Pt100 50 0 200 0 52 JPt100 50 0 200 0 53 Pt100 50 0 100 0 54 JPt100 50 0 100 0 63 Pt100 0 0 200 0 64 JPt100 0 0 200 0 67 Pt100 0 5...

Страница 12: ...24mAdc OFF ON 10s 1ms 10s 250ms 0 20mAdc 4 20mA 600 0 5 FS 23 3 0 1mA 1 FS ev1 250Vac 30Vdc 2A 10 5V 10mA RS 485 3 4800 9600 19200 38400bps CPL MODBUS 0 50 0 40 10 90 RH AC 85 264Vac 50 60Hz 2Hz 100...

Страница 13: ...0 1s 0 2 E1 oF E5 oF 1 5 OFF 0 2 0 1 2 PID PID P 1 0 1 999 9 5 0 0 I 1 0 9999s 0 120 0 d 1 0 9999s 0 30 0 rE 1 10 0 110 0 50 0 0 oL 1 10 0 110 0 0 0 1 oH 1 10 0 110 0 100 0 1 P 1C 0 1 999 9 5 0 0 I 1C...

Страница 14: ...1 0 MV 1 MV 2 MV 3 PV 4 PV 5 SP 6 PV SP 7 CT1 8 CT2 9 MFB C15M 10 SP MV 11 PV MV 0 0 C44 1 1999 9999 1 0 0 0 C45 1 100 0 0 C46 1 MV 0 9999 PV 200 0 C47 2 1 13 0 C48 2 0 C49 2 1999 9999 2 0 0 C50 2 10...

Страница 15: ...3 A 0 OFF 0 1 ON 1 2 DI1 3 DI2 4 9 10 1 11 2 12 3 13 4 14 5 15 17 18 DI1 19 DI2 20 DI3 21 DI4 22 MANUAL 23 READY 24 25 AT 26 SP 27 28 29 PV 30 31 mode 32 1 33 1 2 4 2 dI1 4 dI3 4 1 3 B 0 2 dI1 5 dI3...

Страница 16: ...mode 3 UF MV mode 0 0 C LoC 0 RS 485 read write 1 RS 485 read write 0 2 L LoC 0 read write 1 read write 0 2 PASS 0 15 5 1A 2B 0 0 PS1A 1A 0000 FFFF 16 0000 0 PS2A 2A 0000 FFFF 16 0000 0 PS1b 1B 0000 F...

Отзывы: