AB-7356-U 

 Model  Numbers 

Model VY5430F00XXS-019 
Model number is assigned for the valve combined with the actuator. Model number label is attached to the yoke. 

Base 

model 

No. 

Actuator / Valve 

Actuator 

Valve 

Fixed

Description 

Control 

signal 

Rating / 

Material 

Size/Cv

Fixed Size/Cv

VY54  

 

 

 

 

 

Motorized 

three-way valve with flanged connection 

 

 

 

 

 

 

4 mA DC to 20 mA DC input with 2 V DC to 10 V DC feedback output

 

 

 

 

 

 

145 psig /Gray cast iron* 

 

 

 

 

 

 

NEMA 4X and IEC IP54 protected and standard torque type actuator
with terminal block 
(Mountable valve sizes: 2" to 3") 

      00     

Fixed 

 

 

 

 

 

51 

 

2” / 45 Cv value 

         61  

2

1

/

2

” / 70 Cv value 

 

 

 

 

 

81 

 

3” / 100 Cv value 

          

S-019 Fixed 

* This product was designed and manufactured conforming to the JIS (Japanese Industrial Standards, JIS10K / FC200). 

 

 Specifications 

For weight of the ACTIVAL, refer to the table shown in the section 

Dimensions

 Valve and actuator (as a single unit) specifications 

Item Specification 

Environmental conditions 

Rated operating conditions 

Transport/storage conditions (packaged*

2

)

 Ambient 

temperature*

1

 -4 

F to 122 

F (-20 

C to 50 

C), fluid no 

freezing 

-4 

F to 158 

F (-20 

C to 70 

C) 

 

Ambient humidity 

5 % RH to 95 % RH 

 Vibration 

16.1 

fps

2

 (4.9 m/s

2

), 10 Hz to 150 Hz 

64.3 fps

2

 (19.6 m/s

2

), 10 Hz to 150 Hz 

 Notes: 

1  Do not allow the fluid to freeze. 

 

2  Actuator shall be packed during transport. 

Installation locations 

Indoor (salt air, corrosive gas, and organic solvent must be avoided.) 
Outdoor (the optional outdoor cover must be used. Direct sunlight, salt air, corrosive gas,
and organic solvent must be avoided.) 

Installation orientation 

Installable in any position ranging from upright to sideways (90

 tilted.)  

  *Always install in upright position outdoors. 

Position for shipment 

Port A 100 % (fully open) preset at factory. 

Weight 

VY5430F0051S-019: 30.9 lb (14 kg) 
VY5430F0061S-019: 40.8 lb (18.5 kg) 
VY5430F0081S-019: 44.1 lb (20.0 kg) 

Insulation resistance 

Between terminal and case: 

5 M

 or higher at 500 V DC 

Dielectric strength 

Between terminal and case: 

500 V AC/min with 5 mA or less leakage current 

Содержание ACTIVAL

Страница 1: ...cutes proportional control in combination with a single loop controller e g Model SDC15 Features Compact and lightweight Valve and actuator integrated in a single unit NEMA 4X and IP54 enclosure ratin...

Страница 2: ...ve the product with a vehicle or enough manpower in an appropriate manner Careless lift or accidental drop of the product might cause injury or product damage Detach the cover only when wiring setting...

Страница 3: ...t circuit leading to fire or device failure Firmly tighten the terminal screws Insufficient tightening of the terminal screws might cause fire or overheating Do not touch the moving parts of the produ...

Страница 4: ...cation Environmental conditions Rated operating conditions Transport storage conditions packaged 2 Ambient temperature 1 4 F to 122 F 20 C to 50 C fluid no freezing 4 F to 158 F 20 C to 70 C Ambient h...

Страница 5: ...Hz 53 5 sec 60 Hz Control signal 4 mA DC to 20 mA DC input input impedance 100 Analog output Range 2 V DC 0 to 10 V DC 100 Allowable load resistance 10 k or higher Max 1 mA Materials Case Die cast alu...

Страница 6: ...ication Figure 3 Example of mixing valve application Installation examples For diverting valve installation For mixing valve installation Figure 4 Example of diverting valve installation Figure 5 Exam...

Страница 7: ...in 10 79 5 33 5 12 9 06 4 53 0 87 5 51 6 89 0 75 4 41 9 lb DN65 mm 274 135 5 130 230 115 22 140 175 19 19 kg VY5430F0081S 019 3 in 10 96 5 51 5 91 9 45 4 72 0 87 6 00 7 28 0 75 4 48 7 lb DN80 mm 278...

Страница 8: ...de of each valve In case that the strainers cannot be installed on the inflow side of each valve install it on the pipe diverting sections sections diverting from main piping system to sub piping syst...

Страница 9: ...ve seat may get damaged causing fluid leakage due to an object jammed inside the valve When piping do not apply too much sealing material such as solidifying liquid and tape to the pipe connection sec...

Страница 10: ...0 mark To manually open close the ACTIVAL slowly turn the joint If shock is sent to the actuator the actuator might get damaged Disconnect the power from the ACTIVAL before manually operating the ACTI...

Страница 11: ...mount onto the valve Step 3 in Fig 13 4 A thermal insulation sheet is inserted between the yoke and the valve When changing the mounting positions reinsert the sheet and then fit the yoke into the new...

Страница 12: ...al screws Insufficient tightening of the terminal screws might cause fire or overheating IMPORTANT The ACTIVAL is designed for 24 V AC power supply voltage Do not apply any other power voltage e g 120...

Страница 13: ...ightly knocking the hole using a screwdriver Figure 14 Knockout hole for wiring port 2 Unscrew the 3 setscrews M4 10 of the terminal cover and remove the terminal cover as shown in Fig 15 Figure 15 Te...

Страница 14: ...mer individually Figure 17 Connection example for Model SDC35 SDC36 TC0 Further connection example 4 to 20 mA DC input Model VY5430 A power supply commonly used Note When a power transformer is common...

Страница 15: ...r transformers are used see Fig 19 or a power transformer is commonly used see Fig 20 If a power transformer is commonly used install an isolator into 4 to 20 mA DC input of the second ACTIVAL If an i...

Страница 16: ...ooting Problem Part to check Action Fluid leaks from the flange face Loosened flange bolts Gasket on the flange face Misaligned piping Tighten the flange bolts Replace the gasket Redo piping Fluid lea...

Страница 17: ...AB 7356 U 17 This blank page is added for page layout purposes...

Страница 18: ...AB 7356 U 18 This blank page is added for page layout purposes...

Страница 19: ...AB 7356 U 19 This blank page is added for page layout purposes...

Страница 20: ...AB 7356 U ACTIVAL is a trademark of Azbil Corporation in Japan or in other countries Rev 4 0 Jun 2016 AB 7356 U 20...

Отзывы: