AB-7356-U 

Safety Instructions 

Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual nearby for quick 
reference.  

Restrictions 

This product is targeted for general air conditioning. Do not use this product in a situation where human life might be affected. 
Also, do not install this product in an atmosphere containing explosive gas or flammable gas.  
If this product is used in a clean room or a place where particularly high reliability or control accuracy is required, please contact 
our sales representative. Azbil Corporation will not bear any responsibility for the results produced by the operators. 

 

Warnings and Cautions 

 WARNING

 

Alerts users that improper handling might cause death or serious injury. 

 CAUTION

 

Alerts users that improper handling might cause minor injury or material loss. 

 

Signs 

 

Alerts users possible hazardous conditions caused by erroneous operation or erroneous use. The symbol inside 

indicates the specific type of danger. (For example, the sign on the left warns of the risk of electric shock.) 

 

Notifies users that specific actions are prohibited to prevent possible danger. The symbol inside 

 graphically 

indicates the prohibited action. (For example, the sign on the left notifies that disassembly is prohibited.)  

 

Instructs users to carry out a specific obligatory action to prevent possible danger. The symbol inside 

 graphically 

indicates the actual action to be carried out. (For example, the sign on the left indicates general instructions.) 

 

  WARNING 

 

  Some of the product models weigh more than 40 lb (18.1 kg). Carefully move the product with a vehicle or enough 

manpower in an appropriate manner. Careless lift or accidental drop of the product might cause injury or product 
damage. 

 

  Detach the cover only when wiring, setting the product or maintenance and reattach the cover after  wiring, setting 

the product or maintenance. Failure to do so might cause electric shock. 

 

  Before wiring or maintenance, be sure to turn off the power to the product (including the optional devices) .Failure 

to do so might cause electric shock or device failure. 

 

  CAUTION                                                                     

(1/2)

 

  Install and use this product under the operating conditions (for temperature, humidity, power, vibration, shock, 

mounting direction, atmosphere, etc.) listed in the specifications. Failure to do so might cause fire or device failure.

 

  Use the product within its lifespan and avoid instrumentations that keep the product to operate excessively.

Continued use beyond the lifespan might cause fire or device failure. 

 

  Keep the products in package for storage. Failure to do so might damage or stain the products. 

 

  Do not allow any shock on the product. Doing so might damage the product. 

 

  Installation and wiring must be performed by qualified personnel in accordance with all applicable safety 

standards. 

 

  All wiring must comply with applicable codes and ordinances. 

 

  Provide circuit breaker/fuse protection when powering this product. 

 

  Provide a circuit protector (e.g., a fuse, circuit breaker) for the control panel to ensure your safety. 

 

  For installation, do not mount the valve in an improper position or overtighten the bolts on the flange. Doing so 

might damage the product. 

 

  After installation, make sure no fluid leaks from the valve-pipe connections. Incorrect installation might cause fluid 

leakage. 

 

  Use full face gaskets for flat face flanges to prevent the product damage or fluid leakage. 

 

Содержание ACTIVAL

Страница 1: ...cutes proportional control in combination with a single loop controller e g Model SDC15 Features Compact and lightweight Valve and actuator integrated in a single unit NEMA 4X and IP54 enclosure ratin...

Страница 2: ...ve the product with a vehicle or enough manpower in an appropriate manner Careless lift or accidental drop of the product might cause injury or product damage Detach the cover only when wiring setting...

Страница 3: ...t circuit leading to fire or device failure Firmly tighten the terminal screws Insufficient tightening of the terminal screws might cause fire or overheating Do not touch the moving parts of the produ...

Страница 4: ...cation Environmental conditions Rated operating conditions Transport storage conditions packaged 2 Ambient temperature 1 4 F to 122 F 20 C to 50 C fluid no freezing 4 F to 158 F 20 C to 70 C Ambient h...

Страница 5: ...Hz 53 5 sec 60 Hz Control signal 4 mA DC to 20 mA DC input input impedance 100 Analog output Range 2 V DC 0 to 10 V DC 100 Allowable load resistance 10 k or higher Max 1 mA Materials Case Die cast alu...

Страница 6: ...ication Figure 3 Example of mixing valve application Installation examples For diverting valve installation For mixing valve installation Figure 4 Example of diverting valve installation Figure 5 Exam...

Страница 7: ...in 10 79 5 33 5 12 9 06 4 53 0 87 5 51 6 89 0 75 4 41 9 lb DN65 mm 274 135 5 130 230 115 22 140 175 19 19 kg VY5430F0081S 019 3 in 10 96 5 51 5 91 9 45 4 72 0 87 6 00 7 28 0 75 4 48 7 lb DN80 mm 278...

Страница 8: ...de of each valve In case that the strainers cannot be installed on the inflow side of each valve install it on the pipe diverting sections sections diverting from main piping system to sub piping syst...

Страница 9: ...ve seat may get damaged causing fluid leakage due to an object jammed inside the valve When piping do not apply too much sealing material such as solidifying liquid and tape to the pipe connection sec...

Страница 10: ...0 mark To manually open close the ACTIVAL slowly turn the joint If shock is sent to the actuator the actuator might get damaged Disconnect the power from the ACTIVAL before manually operating the ACTI...

Страница 11: ...mount onto the valve Step 3 in Fig 13 4 A thermal insulation sheet is inserted between the yoke and the valve When changing the mounting positions reinsert the sheet and then fit the yoke into the new...

Страница 12: ...al screws Insufficient tightening of the terminal screws might cause fire or overheating IMPORTANT The ACTIVAL is designed for 24 V AC power supply voltage Do not apply any other power voltage e g 120...

Страница 13: ...ightly knocking the hole using a screwdriver Figure 14 Knockout hole for wiring port 2 Unscrew the 3 setscrews M4 10 of the terminal cover and remove the terminal cover as shown in Fig 15 Figure 15 Te...

Страница 14: ...mer individually Figure 17 Connection example for Model SDC35 SDC36 TC0 Further connection example 4 to 20 mA DC input Model VY5430 A power supply commonly used Note When a power transformer is common...

Страница 15: ...r transformers are used see Fig 19 or a power transformer is commonly used see Fig 20 If a power transformer is commonly used install an isolator into 4 to 20 mA DC input of the second ACTIVAL If an i...

Страница 16: ...ooting Problem Part to check Action Fluid leaks from the flange face Loosened flange bolts Gasket on the flange face Misaligned piping Tighten the flange bolts Replace the gasket Redo piping Fluid lea...

Страница 17: ...AB 7356 U 17 This blank page is added for page layout purposes...

Страница 18: ...AB 7356 U 18 This blank page is added for page layout purposes...

Страница 19: ...AB 7356 U 19 This blank page is added for page layout purposes...

Страница 20: ...AB 7356 U ACTIVAL is a trademark of Azbil Corporation in Japan or in other countries Rev 4 0 Jun 2016 AB 7356 U 20...

Отзывы: