AB-7356-U
12
Wiring
WARNING
Before wiring or maintenance, be sure to turn off the power to the product (including the optional devices). Failure
to do so might cause electric shock or device failure.
Detach the cover only when wiring, setting the product or maintenance and reattach the cover after wiring, setting
the product or maintenance. Failure to do so might cause electric shock.
CAUTION
Installation and wiring must be performed by qualified personnel in accordance with all applicable safety
standards.
All wiring must comply with applicable codes and ordinances.
Provide circuit breaker/fuse protection when powering this product.
Provide a circuit protector (e.g., a fuse, circuit breaker) for the control panel to ensure your safety.
Use crimp terminals with insulation for connections to the product terminals. Failure to do so might cause short
circuit leading to fire or device failure.
Firmly tighten the terminal screws. Insufficient tightening of the terminal screws might cause fire or overheating.
IMPORTANT:
The ACTIVAL is designed for 24 V AC power supply voltage.
Do not apply any other power voltage (e.g., 120 V AC, 240 V AC) to the ACTIVAL.
For 4 to 20 mA input type, make sure the polarity of the power supply and 2 to 10 V DC feedback output
referring to the wiring diagrams. Incorrect wiring might result in PCB (print circuit board) burnout.
To prevent damage, cover the terminals except when connecting/disconnecting wires.
Do not connect 24 V AC power to the terminals 4 to 7. (Max. applicable voltage: 5 V DC)
To keep NEMA 4X and IP54 protection
Use a water-proof connector for the ACTIVAL in a high-humidity environment or outdoor location.
Be sure to completely close the terminal cover and the top cover.
Waterproof the wiring port.
- For cable connection, use a water-proof connector. (Seal connector Part No. 83104346-003 is recommended.)
- For conduit connection, use a water-proof plica tube or the like.
Control signal
The control signal type is shown on the actuator label and the wiring label as follows:
4 to 20 mA input
4–20 mA