Azbil ACTIVAL Скачать руководство пользователя страница 16

AB-7356-U 

16 

 Inspection and Maintenance 

 WARNING 

 

  Detach the cover only when wiring, setting the product or maintenance and reattach the cover after  wiring, setting 

the product or maintenance. Failure to do so might cause electric shock. 

 

  Before wiring or maintenance, be sure to turn off the power to the product (including the optional devices). Failure 

to do so might cause electric shock or device failure. 

 

 CAUTION 

 

  Do not carelessly touch the product when being used to control hot water. The product temperature is hot, and you 

might get burned 

 

  Do not touch the moving parts of the product. Doing so might cause injury. 

 

 

Inspect the ACTIVAL according to Table 1. 

 

Manually open/close the ACTIVAL at least once a month if it is left in inactive state for a long period. 

 

Visually inspect the fluid leakage of the valve and the actuator operations every six months. If any of the problems described 
in Table 2 are found, take corresponding actions shown in the table. 
If your problem is not solved by the corresponding action, please contact Azbil Corporation near you. 

 

Table 1.  Inspection items and details 

Inspection item 

Inspection interval 

Inspection detail 

Visual inspection 

Semiannual 

  Fluid leakage from the gland and the flange face 

 Loosened 

bolts 

  Valve and actuator damages 

Operating status 

Semiannual 

  Unstable open/close operation 

  Abnormal noise and vibration 

Routine inspection 

Any time 

  Fluid leakage to the outside 

  Abnormal noise and vibration 

  Unstable open/close operation 

 Valve 

hunting 

 

Table 2.  Troubleshooting 

Problem 

Part to check 

Action 

Fluid leaks from the flange face. 

Loosened flange bolts 
Gasket on the flange face 
Misaligned piping 

Tighten the flange bolts. 
Replace the gasket. 
Redo piping. 

Fluid leaks from the gland part. 

 

Consult with our sales/service personnel. 

Fluid leaks from the bonnet. 

Loosened bolts 

Tighten the bolts. 

Valve does not operate smoothly / 
valve stops halfway / 
valve does not operate at all. 

Conditions of the power applied and of the input 
signal applied 
Loosened terminals 
Wiring condition / disconnected wires 

Check the power supply and the controller 
connected to. 
Tighten the terminals. 
Check the wiring. 

Fluid leaks to the outside of the valve 
when the ACTIVAL is in fully closed 
position. 

Actuator pointer not pointing to fully closed 
position 

Fully close the ACTIVAL. 

The valve vibrates or produces an 
abnormal noise. 

Primary pressure condition 
Differential pressure condition 

Adjust the mounting position and change the 
installation location. 

The auxiliary switch does not operate. 

Auxiliary switch (cam switch) condition 
Loosened terminals 
Wiring condition / disconnected wires 

Redo the cam switch setting. 
Tighten the terminals. 
Check the wiring. 

Valve hunting occurs. 

Secondary pressure condition 
Differential pressure condition 
Control stability 

Adjust the mounting position and change the 
installation location. 
Correct the control parameter setting of 
controller. 

Voltage/current input signal disagrees 
with the feedback output signal. 

To completely shut off the valve, valve open and close (0-100% position) operation is controlled by 
10-90 % range of actuator voltage/current input signal. Voltage/current input signal therefore 
disagrees with the feedback signal, and this is not an error. 

 

 

Содержание ACTIVAL

Страница 1: ...cutes proportional control in combination with a single loop controller e g Model SDC15 Features Compact and lightweight Valve and actuator integrated in a single unit NEMA 4X and IP54 enclosure ratin...

Страница 2: ...ve the product with a vehicle or enough manpower in an appropriate manner Careless lift or accidental drop of the product might cause injury or product damage Detach the cover only when wiring setting...

Страница 3: ...t circuit leading to fire or device failure Firmly tighten the terminal screws Insufficient tightening of the terminal screws might cause fire or overheating Do not touch the moving parts of the produ...

Страница 4: ...cation Environmental conditions Rated operating conditions Transport storage conditions packaged 2 Ambient temperature 1 4 F to 122 F 20 C to 50 C fluid no freezing 4 F to 158 F 20 C to 70 C Ambient h...

Страница 5: ...Hz 53 5 sec 60 Hz Control signal 4 mA DC to 20 mA DC input input impedance 100 Analog output Range 2 V DC 0 to 10 V DC 100 Allowable load resistance 10 k or higher Max 1 mA Materials Case Die cast alu...

Страница 6: ...ication Figure 3 Example of mixing valve application Installation examples For diverting valve installation For mixing valve installation Figure 4 Example of diverting valve installation Figure 5 Exam...

Страница 7: ...in 10 79 5 33 5 12 9 06 4 53 0 87 5 51 6 89 0 75 4 41 9 lb DN65 mm 274 135 5 130 230 115 22 140 175 19 19 kg VY5430F0081S 019 3 in 10 96 5 51 5 91 9 45 4 72 0 87 6 00 7 28 0 75 4 48 7 lb DN80 mm 278...

Страница 8: ...de of each valve In case that the strainers cannot be installed on the inflow side of each valve install it on the pipe diverting sections sections diverting from main piping system to sub piping syst...

Страница 9: ...ve seat may get damaged causing fluid leakage due to an object jammed inside the valve When piping do not apply too much sealing material such as solidifying liquid and tape to the pipe connection sec...

Страница 10: ...0 mark To manually open close the ACTIVAL slowly turn the joint If shock is sent to the actuator the actuator might get damaged Disconnect the power from the ACTIVAL before manually operating the ACTI...

Страница 11: ...mount onto the valve Step 3 in Fig 13 4 A thermal insulation sheet is inserted between the yoke and the valve When changing the mounting positions reinsert the sheet and then fit the yoke into the new...

Страница 12: ...al screws Insufficient tightening of the terminal screws might cause fire or overheating IMPORTANT The ACTIVAL is designed for 24 V AC power supply voltage Do not apply any other power voltage e g 120...

Страница 13: ...ightly knocking the hole using a screwdriver Figure 14 Knockout hole for wiring port 2 Unscrew the 3 setscrews M4 10 of the terminal cover and remove the terminal cover as shown in Fig 15 Figure 15 Te...

Страница 14: ...mer individually Figure 17 Connection example for Model SDC35 SDC36 TC0 Further connection example 4 to 20 mA DC input Model VY5430 A power supply commonly used Note When a power transformer is common...

Страница 15: ...r transformers are used see Fig 19 or a power transformer is commonly used see Fig 20 If a power transformer is commonly used install an isolator into 4 to 20 mA DC input of the second ACTIVAL If an i...

Страница 16: ...ooting Problem Part to check Action Fluid leaks from the flange face Loosened flange bolts Gasket on the flange face Misaligned piping Tighten the flange bolts Replace the gasket Redo piping Fluid lea...

Страница 17: ...AB 7356 U 17 This blank page is added for page layout purposes...

Страница 18: ...AB 7356 U 18 This blank page is added for page layout purposes...

Страница 19: ...AB 7356 U 19 This blank page is added for page layout purposes...

Страница 20: ...AB 7356 U ACTIVAL is a trademark of Azbil Corporation in Japan or in other countries Rev 4 0 Jun 2016 AB 7356 U 20...

Отзывы: