45
Chapter 7. Specifications
General
specifications
Structure
Structure of the replacement base unit or sub-base and main unit
Mounted orientation Vertical or horizontal
However, for horizontal attachment, 7 segment display can only be mounted so that it faces directly
overhead
(DIN rail mounting or direct mounting through base screw holes)
Dimensions
• When used in combination with the replacement base unit (Q890A100) : W126 × H136 × D155 mm
• When used in combination with the sub-base (BC-R05A100) : W95 × H105 × D110 mm
Weight
Approximately 1200 g (When used in combination with the replacement base unit), Approximately
600 g (incl. sub-base)
Wiring types and max. wiring length • Low voltage temp. controller
600 V PVC-insulated copper wire cable (“IV wire, ” JIS C3307), 1.25 mm
2
, recommended length 20
m or less, max. wiring length 100 m
• Contact reset
600 V PVC-insulated copper wire cable (“IV wire, ” JIS C3307), 1.25 mm
2
, max. wiring length 10 m
• AUD100 Series (F, G)
Copper IV wire with 600V vinyl insulation, 1.25 mm
2
, maximum wiring length: 200m
• Flame rod (F, G)
RG-11U (JAN standard: US DoD compliant specification)
Or equivalent 5C2V, 7C2V (JIS standard)
Recommended condition: 20 m or less, maximum wiring length: 30 m
• Flame voltage output signal circuit
IV wire 0.75 mm
2
or larger, max. wiring length 10 m
*1 Selected by model number.
*2 If no alarm has occurred, input from the RESET switch and the contact reset terminal is not accepted.