29
Chapter 4. Explanation of Operation
z
Operation when a flame failure occurs (Non-recycling gas-fired combustion)
Input
AUR890 operation
Sequence
codes
Operation of external devices
Power ON
When approximately 8 seconds have passed after the power has
been turned on, the 7-segment LED display on the front panel of
the AUR890 shows the sequence code [- -].
- -
Burner operation
switch ON
- -
When the burner operation switch is turned
on, the blower starts to operate, and if the
limit and interlock conditions are normal, a
prepurge is done. After the prepurge, the
prepurge completion signal is turned ON.
Blower: operating
Controller ON
If the prepurge completion signal is ON and the controller turns
ON, the sequence that follows is start check, ignition standby,
lockout time, standby for normal combustion, and normal
combustion.
The FLAME LED (green) on the front panel of the AUR890 lights up.
P8
Pilot valve : open
Main valve : open
During main burner combustion, if a flame failure of the burner
occurs for some reason, after the flame failure response time has
passed, the AUR890 will be locked out so that relays K1, K2, K3,
and K4 turn OFF, the pilot and main valves close, relay K6 turns
ON, and the alarm output turns ON.
FLAME LED (green) on the front panel of the AUR890 turns off,
and ALARM LED (red) turns on.
P8
/
E7
Pilot valve : closed
Main valve : closed
Alarm output : ON
Burner operation
switch OFF
P8
/
E7
Blower : stop
Contact reset or
main unit reset
switch: ON
Relay K6 turns OFF to turn OFF the alarm output.
The ALARM LED (red) on the front panel of the AUR890 turns off.
- -
Alarm output : OFF
––
P1
––
––
Stop
Star
t check
P3
Ignition standb
y
P4
Lockout timing
P8
P8/E7
P8/E7
Main bur
ner c
ombustion standb
y
P5
RUN
Stop
Stop
Flame failur
e
Lockout
AUR890
Prepurge time
(external circuit)
Start check + Ignition standby time
Approximately 3 s
Approximately 8 s
Lockout timing time
Flame response
Main burner combustion standby time
Reset time
1 s or longer
[Input]
Power supply
[7-segment display]
Limit, Interlock
[Output]
Ignition transformer
Burner operation switch
Blower
Controller
Flame signal
RESET switch
[LED]
FLAME LED (Green)
Alarm output
Pilot valve
Main valve
ALARM LED (Red)
Содержание 81447514-001