![Azbil 81447514-001 Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/azbil/81447514-001/81447514-001_user-manual_3042584030.webp)
22
Chapter 3. Operation
z
When an error occurs
The 7-segment display shows a alarm code and the sequence code for which the
alarm was issued alternately.
Every time the DISP switch is pressed, the display is changed between a alarm code
and the sequence code for which the alarm was issued alternately as well as the
flame voltage.
•
Alarm codes
Alarm codes
Sub-code
Description
E
1
None
Interlock error
E6
Ignition failure
E7
Flame failure
E9
02
Switch input
E9
03
Internal relay feedback (K1)
E9
05
Abnormal voltage on terminal 7 (PV)
E9
06
Abnormal voltage on terminal 8 (MV)
E9
07
Abnormal voltage on terminal 6 (IG)
E9
08
Alarm at power ON
E9
50
or more
Device error
Examples of sequence codes and alarm codes
(Alarm code: When there is not a
sub-code)
Examples of sequence codes and alarm codes
(Alarm code: When there is a sub-
code)
Switches every 0.8 s
Switches every 0.8 s