42
Recommended breaker specification of battery for each inverter:
Model
1 unit*
5KW
80A/70VDC
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should
be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.
Recommended breaker specification of AC input with single phase:
Model
2 units
3 units
4 units
5 units
6 units
7 units
8 units
9 units
5KW
80A/
230VAC
120A/
230VAC
160A/
230VAC
200A/
230VAC
240A/
230VAC
280A/
230VAC
320A/
230VAC
360A/
230VAC
Note1: Also, you can use 50A breaker for only 1 unit and install one breaker at its AC input in each inverter.
Note2: Regarding three-phase system, you can use 4-pole breaker directly and the rating of the breaker
should be compatible with the phase current limitation from the phase with maximum units
Recommended battery capacity
Inverter parallel numbers
2
3
4
5
6
7
8
9
Battery Capacity
200AH 400AH 400AH 600AH
600AH
800AH
800AH
1000AH
WARNING! Be sure that all inverters will share the same battery bank. Otherwise, the inverters will transfer to
fault mode.