19
25
Record Fault code
Record enable
Record disable (Default)
26
Bulk charging voltage
(C.V voltage)
default setting: 56.4V
If self-defined is selected in
program 5, this program can be
set up. Setting range is from 48.0V
to 64.0V. Increment of each click is
0.1V.
27
Floating charging voltage
default setting: 54.0V
If self-defined is selected in
program 5, this program can be
set up. Setting range is from 48.0V
to 64.0V. Increment of each click
is 0.1V.
28
AC output mode
*This setting is able to set
up only when the inverter
is in standby mode, Be
sure that on/off Switch is
in ”OFF” status.
Single: This inverter is used
in single phase application.
Parallel: This inverter is operated
in parallel system.
L1 phase:
L2 phase:
L3 phase:
29
Low DC cut-off voltage
default setting: 42.0V
If self-defined is selected in
program 5, this program can be
set up. Setting range is from 40.0V
to 54.0V. Increment of each click
is 0.1V. Low DC cut-off voltage will
be fixed to setting value no matter
what percentage of load is
connected.