16
The TOTAL screen displays the flow total of A or B in programmed engineering
units. Pressing the RESET button resets the value back to zero (0). The Total
can also be reset remotely by connecting a momentary voltage to the external
RESET input.
GRAND TOTAL A (B)
6000 GAL
The GRAND TOTAL screen can be accessed using the ENTER button from the
TOTAL screen. To reset this total pressing the RESET button will request the
user to enter a password at this point. Use the UP – DOWN – SELECT buttons
to enter the password code of “53126”. Then press the RESET button which will
reset the grand total value back to zero (0).
Note that both grand totals must be reset independent of one another.
The STATUS screen is a raw data display of the current major properties of
STATUS L1 OFF L2 OFF
RTA 100.14 TOA 15400
RTB 150.32 TOB 03561
ANLG 04.00 mA
STATUS Screen
the monitor. The rates are shown as Hz, total in pulses, limits as on or off and
current loop output (main loop only) in programmed mA DC.
NOTE: The Gate Time filter and linearizer, if active, do not affect the flow rate value in the STATUS
screen.
This is the raw incoming frequency. The mA shown is not a direct reading of the
loop current if there are other problems outside of the controller such as a broken
wire or defective loop power source.
NOTE: Because the mA value is an actual signal output, it is affected by the Gate Time and linearizer,
if activated.