background image

AV6A

7

DeviceNet Protocol “D”

The DeviceNet protocol provides a set of data bits inside a DeviceNet 

message that represent the encoder position (in turns and within 1 

turn).

DeviceNet may be wired in several different configurations, but the 

most common is a “Trunk and Drop Line” configuration.  The trunk 

message cable must be terminated at each end with 120 ohm 

resistors.  Note that DeviceNet also offers the option to carry device 

power to each encoder through an additional cable pair of wires.  

Preferred cable:  Nidec Avtron recommends structured DeviceNet 

wiring systems, available from a broad range of vendors.  Large 

diameter main, small diameter round cable, as well as flat cabling 

systems are all acceptable.

For more details on DeviceNet, consult the Open DeviceNet Vendor’s 

Association (ODVA):
www.odva.org 

Network 

Baud 

Rate

500K

250K

125K Units

Max. 

Length*

325

[100]

800

[250]

1600

[500]

ft 

[m]

Max.  

Single 

Tap 

Length

15

[5]

15

[5]

15

[5]

ft

[m]

Max. 

Total 

Tap 

Length

100

[30]

200

[60]

400

[120]

ft 

[m]

Min. Tap 

to Tap 

Length 

20

[6]

20

[6]

20

[6]

ft 

[m]

*Using thick cable 

Number 

of 

Nodes

2

16

32

64

Units

Max. 

Overall 

Cable 

Length*

750

[229]

690

[210]

640

[190]

560

[170]

ft 

[m]

*Using thick cable 

Setting Node (MAC-ID), Baud Rate & Termination Resistor

NOTE:  Units with hardware connection caps cannot accept 

software-commanded address, baud rate or termination resistor 

changes.  These must be made using the switches in the connection 

cap.  Before commencing any changes, check for a connection cap.  

It is secured to the rear of the encoder with 2 or 3 screws and due 

to snug fit will require a strong pull to remove it after removing the 

screws. 

NOTE:  Any changes to baud rate, node number, or resistor will not 

take effect until the encoder is reset (typically power cycled)--be 

sure to store parameters in EEPROM.

NOTE:  Baud rate, termination resistor and a values are not stored 

permanently until they are written to EEPROM.  If power is cycled 

before the values are stored, the encoder will default to the values 

previously stored in EEPROM.

Setting Node Number:

To set the node number on units with a connection cap:  Set the 

address using the two rotating switches.  The node number can be 

between 0-63.  The node address = X10 switch * 10 + X1 switch 

value. 

To set the node MAC-ID number on units without a connection cap: 

write attribute 6Fh (byte).  [(master MAC-ID) 0x10 0x23 0x01 0x6F 

(node)].  The encoder will reply [0x0A 0x90]. 

Setting Baud Rate:

To set the baud rate on units with a connection cap:  Set the baud 

rate using the rotating switch marked Bd per the table below. 

To set the baud rate: write the baud code to attribute 6Eh (byte). 

[(master MAC-ID) 0x10 0x23 0x01 0x6E (baud code)]. The encoder 

will reply [0x0A 0x90]. 

Network Baud 

Rate

500K

250K

125K

Baud Code/ 

Switch Setting

0x02

0x01

0x00

Enabling Termination Resistor:

To enable the termination resistor in units with a connection cap:  

Turn switch Rt to “On”.

To enable the termination resistor:  write 01 to attribute 67h.  Ensure 

any devices on the bus power up at least 700mS after the encoder 

with the termination resistor activated.

Note that only devices at each end of the bus should have 

termination resistors enabled--if the master/scanner is at one of the 

bus, then only one encoder (at the opposite bus end) will require a 

termination resistor.

Measuring Position, Speed, and Acceleration

Only position feedback is supported in DeviceNet; acceleration and 

speed are not directly supported at this time.

To read position feedback into your device:  Following the 

instructions for your master/scanner module for the DeviceNet 

network, load the encoder EDS file into your configuration.  Assign it 

to the correct MAC-ID node number.  Store the configuration to the 

scanner module.

All of the position data and other parameters will be read by 

the scanner module and placed in registers identified in the 

configuration package.

Setting Polling, Cyclic and Sync Mode

Polling, cycling and sync mode are supported by the encoder; use 

the parameters supplied in the EDS file to set the appropriate mode.  

Содержание AV6A Series

Страница 1: ...tion Supplied AV6A Encoder Optional none Not Supplied Open Wrenches Hex Wrenches Dial Indicator Gauge Caliper Gauge Coupling Foot Mount and Mounting Screws AV6A PART NUMBERS AND AVAILABLE OPTIONS Mode...

Страница 2: ...cceptable loosen the mounting screws to the flange and apply thin metal shims to the face of the encoder and retest the angular alignment until acceptable 5a Remove the AV6A Transfer punch or layout t...

Страница 3: ...e encoder replies Transmission rates vary but these messages can be extremely short and typically require scope triggering to spot them For CANOpen ensure termination resistors are in place or switche...

Страница 4: ...84 12 or 14 bits F Line Driver Specs See table G Connectors See connector options on page 1 H Accuracy 0 04 deg 2 6 arc min 12 bit units 0 02 deg 1 3 arc min 16 bit units MECHANICAL A Shaft Inertia 0...

Страница 5: ...encoder is reset typically power cycled Power Up Sequence The encoder will power up in the pre operational mode The message it will issue is ID 0x07nn 0x00 nn node number typically 0x01 for units wit...

Страница 6: ...SDO object 0x2300 Example encoder at node 20 store changes ID 0x620 0x22 0x00 0x23 0x00 0x55 0xAA 0xAA 0x55 No reset is triggered Cycle power after saving changes to parameters Other Parameters Contac...

Страница 7: ...cycled before the values are stored the encoder will default to the values previously stored in EEPROM Setting Node Number To set the node number on units with a connection cap Set the address using t...

Страница 8: ...cabling system and that no termination resistors are in placed or activated in the middle of the system Remove the connections to the master controller and all devices or power down all devices Measur...

Страница 9: ...an lowest bit right most bit Single turn data data within 1 turn is provided in the least significant bits Multiturn data is provided directly above the single turn data bitwise Example 12 turns x 13...

Страница 10: ...rs encoder operational LS DA 1 Status Flashing Green Active inbound communication LS DA 2 Status Green Output connected to next encoder LS DA 2 Flashing Green Active communication to next encoder Erro...

Страница 11: ...turns position data Zero Position for Multiturn Encoders Single turn Encoders NOTE Do not attempt to use zero preset function while the encoder is rotating Doing so will produce unpredictable results...

Страница 12: ...tion Speed and Acceleration To read position into your device acceleration and speed measurement is not supported For multiturn single turn encoders position data provided as 4 bytes 32 bits Format is...

Страница 13: ...ed to each cable Use hubs or switches to connect multiple Modbus TCP encoders to the master device A software snoop or sniffer program can also be used to packet analyze the communication If the posit...

Страница 14: ...ow operate at the assigned IP address which can be validated using the ping command from the PC The assigned name can be used throughout STEP7 software to address the encoder Note that if more than on...

Страница 15: ...coder use the parameters supplied in the GSDML file to set the appropriate mode Store the resulting configuration into the scanner module Storing Saving Encoder Parameters to EEPROM To store the curre...

Страница 16: ...laced in registers identified in the configuration package Profibus DP Diagnostic LEDs LED Status Meaning STATUS ERROR Green Off Power Ok Status OK STATUS ERROR Green Red No Configuration Data Receive...

Страница 17: ...s required Measuring Position Speed and Acceleration To read position and speed into your device acceleration measurement is not supported Following the instructions for your master scanner module for...

Страница 18: ...unication A software snoop or sniffer program can also be used to packet analyze the communication If the position is changing as the encoder moves but is reported incorrectly the Preset parameter may...

Страница 19: ...Upon the Set Zero signal returning to logic zero falling edge the encoder count value will be set to zero Set Direction input 10K resistance For input logic zero or no connection the encoder will cou...

Страница 20: ...st L GND 0V BROWN 3 NC PINK NC BLUE NC GRAY CAN_H Rightmost H CAN_L Rightmost L CAN_GND Rightmost G Double up Double up REF SIGNAL CAN_GND V CAN_H CAN_L GND 0V Optional Daisy Chain CAN_H CAN_L CAN_GND...

Страница 21: ...ftmost H CAN_L BLUE 3 Leftmost L NC NC NC CAN_H Rightmost H CAN_L Rightmost L Double up Double up REF SIGNAL V V GND CAN_H CAN_L Optional Daisy Chain CAN_H CAN_L GND V DeviceNet Bus D AV6A WIRING DIAG...

Страница 22: ...ey pairing as shown optional overall shield may be used for high noise environments NOTE For encoder switch connections use the crossover pinout shown for encoder PC or encoder PLC direct wiring use a...

Страница 23: ...W BROWN 16 BIT 15 WHITE YELLOW 15 BIT 14 BROWN GREEN 14 BIT 13 WHITE GREEN 13 BIT 12 BLUE RED 12 BIT 11 GREY PINK 11 BIT 10 VIOLET 10 BIT 9 BLACK 9 BIT 8 RED 8 BIT 7 BLUE 7 BIT 6 PINK 6 BIT 5 GREY 5 B...

Страница 24: ...OWN GREEN NC NC 14 BIT 13 WHITE GREEN NC 13 13 BIT 12 BLUE RED 12 12 12 BIT 11 GREY PINK 11 11 11 BIT 10 VIOLET 10 10 10 BIT 9 BLACK 9 9 9 BIT 8 RED 8 8 8 BIT 7 BLUE 7 7 7 BIT 6 PINK 6 6 6 BIT 5 GREY...

Страница 25: ...own optional overall shield may be used for high noise environments Communication Bus M Modbus TCP Pinout AV6A WIRING DIAGRAMS Master Scanner or Switch Power Supply NOTE For encoder switch connections...

Страница 26: ...B Bus A out 5 pin female 2 Rightmost A Bus B out 4 Rightmost B REF SIGNAL GND OV Vs Bus A out Bus B out Bus A in Bus B in NOTE Profibus cabling required Obey pairing as shown If termination resistor R...

Страница 27: ...NK 4 6 SET ZERO BLUE 9 7 SET DIRECTION RED 8 8 NC 5 NC 6 NC 7 NC 10 REF SIGNAL GND Vs CLK CLK DAT DAT SET ZERO SET DIRECTION NC NC NC NC NOTE Twisted pair cable required with overall shield individual...

Страница 28: ...or M12 K Radial exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed t...

Страница 29: ...12 E Axial exit E Multiturn IP65 Seals and Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed to...

Страница 30: ...M27 G End Axial exit E Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed...

Страница 31: ...R Connector M12x3 Side Exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superi...

Страница 32: ...M12 8 E Side exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed to c...

Страница 33: ...5 1 25 pilot Devicenet D Connector 2xM12 5 B Radial exit A Multiturn IP65 Seals Aluminum Steel Enclosure A DIMENSIONS IN INCHES MILLIMETERS ALL DIMENSIONS ARE APPROXIMATE Features and specifications...

Отзывы: