background image

AV6A

5

CANOpen Protocol “C”

The CANOpen protocol provides a set of data bits inside a CANOpen 

message that represent the encoder position (in turns and within 1 

turn).

CANOpen may be wired in several different configurations, but the 

most common is a “Trunk and Drop Line” configuration.  The trunk 

message cable must be terminated at each end with 120 ohm 

resistors.  Note that CANOpen also offers the option to carry device 

power to each encoder through an additional cable pair of wires. 

Avtron CANOpen encoders with connection caps offer the ability 

to act as a “T” coupling in the bus system.  This means that the 

encoders can effectively be installed in a daisy-chain configuration, 

with each encoder wired to the next.  The first encoder is typically 

wired to the master/scanner device located at one end of the bus, 

but the master/scanner device can be located anywhere on the bus 

system. 

Preferred cable:  Twisted pair with individual pair and overall shields. 

Communication pair:  24 AWG, copper conductor, capacitance of 

50 pF/meter (15 pF/foot) terminated in a 120 Ohm resistive load.  

Power pair:  22AWG copper conductor, 17ohms/1000 ft [55 ohms/

km].  Note that resistive losses in long cables may decrease actual 

voltage (+Vs) available at the encoder; larger conductors can be 

used or the encoder can be powered locally and signal GND brought 

through the cable.  Maximum transmission speed is limited by cable 

length and number of devices as shown in the figures below.

For more details on CANOpen, consult the CiA, CANOpen in 

Automation:
www.can-cia.org 

Setting Node Number, Baud Rate & Termination Resistor

NOTE:  Units with hardware connection caps cannot accept 

software-commanded address, baud rate or termination resistor 

changes.  These must be made using the switches in the connection 

cap.  Before commencing any changes, check for a connection cap.  

It is secured to the rear of the encoder with 2 or 3 screws and due 

to snug fit will require a strong pull to remove it after removing the 

screws. 

NOTE:  Any changes to baud rate, node number, or resistor will not 

take effect until the encoder is reset (typically power cycled).

Power-Up Sequence

The encoder will power-up in the pre-operational mode.

The message it will issue is:

ID:  0x07nn   0x00

nn=node number, typically: 

0x01 for units with connection cap including hardware node and 

baud rate selection.  (software commands will not change node) 

0x20 is the factory default for units with software-selectable 

addressing. (software commands can change node number)

Setting Node Number:

To set the node number on units with a connection cap:  Set the 

address using the two rotating switches.  The node number can 

be between 0-89.  The node address = X10 switch * 10 + X1 + 1 

switch value.  (The encoder internally adds 1 to the switch value 

total).  Special addresses are shown below:

Address

Function

97

Recovery C2-C5

98

Protocol DS301-V3

99

Protocol DS301-V4

To set the node number on units without a connection cap: write 

SDO object 0x3000 using command 0x22.  The encoder internally 

adds 1 to the written value.  

Example, encoder at node 20, change node address to 02:

ID:  0x620   0x22  0x00  0x30  0x00  0x01 0x00  0x00  0x00  

Setting Baud Rate:

To set the baud rate on units with a connection cap:  Set the baud 

rate using the rotating switch marked Bd per the table below. 

To set the baud rate on units without a connection cap: write the 

baud code per the table below to SDO object 0x3001.

Example, encoder at node 20, change baud rate to 125K = 0x03

ID:  0x620  0x22  0x01  0x30  0x00  0x03  0x00  0x00

Network 

Baud 

Rate

LSS

1M

500K

250K

125K

50K

20K

Baud 

Code or 

Switch 

Setting

09h

07h

05h

04h

03h

01h

00h

Enabling Termination Resistor:

To enable the termination resistor in units with a connection cap:  

Turn switch Rt to “On”.

To enable the termination resistor in units without a connection 

cap:  write 01 to SDO object 3002h.  Ensure any devices on the bus 

power up at least 700mS after the encoder with the termination 

resistor activated.

Network 

Baud 

Rate

1M

500K

250K

125K

50K

20K

Units

Max. 

Length

65

[20]

325

[100]

800

[250]

1600

[500]

3250

[1000]

8200

[2500]

ft 

[m]

Max.  

Single 

Tap 

Length

1

[0.3]

15

[5]

15

[5]

15

[5]

200

[60]

500

[150]

ft

[m]

Max. 

Total Tap 

Length

5

[1.5]

100

[30]

200

[60]

400

[120]

1000 

[300]

2500

[750]

ft 

[m]

Min. Tap 

to Tap 

Length 

-

[-]

20

[6]

20

[6]

20

[6]

240

[72]

600

[180]

ft 

[m]

Number 

of 

Nodes

2

16

32

64

Units

Max. 

Overall 

Cable 

Length

750

[229]

690

[210]

640

[190]

560

[170]

ft 

[m]

Содержание AV6A Series

Страница 1: ...tion Supplied AV6A Encoder Optional none Not Supplied Open Wrenches Hex Wrenches Dial Indicator Gauge Caliper Gauge Coupling Foot Mount and Mounting Screws AV6A PART NUMBERS AND AVAILABLE OPTIONS Mode...

Страница 2: ...cceptable loosen the mounting screws to the flange and apply thin metal shims to the face of the encoder and retest the angular alignment until acceptable 5a Remove the AV6A Transfer punch or layout t...

Страница 3: ...e encoder replies Transmission rates vary but these messages can be extremely short and typically require scope triggering to spot them For CANOpen ensure termination resistors are in place or switche...

Страница 4: ...84 12 or 14 bits F Line Driver Specs See table G Connectors See connector options on page 1 H Accuracy 0 04 deg 2 6 arc min 12 bit units 0 02 deg 1 3 arc min 16 bit units MECHANICAL A Shaft Inertia 0...

Страница 5: ...encoder is reset typically power cycled Power Up Sequence The encoder will power up in the pre operational mode The message it will issue is ID 0x07nn 0x00 nn node number typically 0x01 for units wit...

Страница 6: ...SDO object 0x2300 Example encoder at node 20 store changes ID 0x620 0x22 0x00 0x23 0x00 0x55 0xAA 0xAA 0x55 No reset is triggered Cycle power after saving changes to parameters Other Parameters Contac...

Страница 7: ...cycled before the values are stored the encoder will default to the values previously stored in EEPROM Setting Node Number To set the node number on units with a connection cap Set the address using t...

Страница 8: ...cabling system and that no termination resistors are in placed or activated in the middle of the system Remove the connections to the master controller and all devices or power down all devices Measur...

Страница 9: ...an lowest bit right most bit Single turn data data within 1 turn is provided in the least significant bits Multiturn data is provided directly above the single turn data bitwise Example 12 turns x 13...

Страница 10: ...rs encoder operational LS DA 1 Status Flashing Green Active inbound communication LS DA 2 Status Green Output connected to next encoder LS DA 2 Flashing Green Active communication to next encoder Erro...

Страница 11: ...turns position data Zero Position for Multiturn Encoders Single turn Encoders NOTE Do not attempt to use zero preset function while the encoder is rotating Doing so will produce unpredictable results...

Страница 12: ...tion Speed and Acceleration To read position into your device acceleration and speed measurement is not supported For multiturn single turn encoders position data provided as 4 bytes 32 bits Format is...

Страница 13: ...ed to each cable Use hubs or switches to connect multiple Modbus TCP encoders to the master device A software snoop or sniffer program can also be used to packet analyze the communication If the posit...

Страница 14: ...ow operate at the assigned IP address which can be validated using the ping command from the PC The assigned name can be used throughout STEP7 software to address the encoder Note that if more than on...

Страница 15: ...coder use the parameters supplied in the GSDML file to set the appropriate mode Store the resulting configuration into the scanner module Storing Saving Encoder Parameters to EEPROM To store the curre...

Страница 16: ...laced in registers identified in the configuration package Profibus DP Diagnostic LEDs LED Status Meaning STATUS ERROR Green Off Power Ok Status OK STATUS ERROR Green Red No Configuration Data Receive...

Страница 17: ...s required Measuring Position Speed and Acceleration To read position and speed into your device acceleration measurement is not supported Following the instructions for your master scanner module for...

Страница 18: ...unication A software snoop or sniffer program can also be used to packet analyze the communication If the position is changing as the encoder moves but is reported incorrectly the Preset parameter may...

Страница 19: ...Upon the Set Zero signal returning to logic zero falling edge the encoder count value will be set to zero Set Direction input 10K resistance For input logic zero or no connection the encoder will cou...

Страница 20: ...st L GND 0V BROWN 3 NC PINK NC BLUE NC GRAY CAN_H Rightmost H CAN_L Rightmost L CAN_GND Rightmost G Double up Double up REF SIGNAL CAN_GND V CAN_H CAN_L GND 0V Optional Daisy Chain CAN_H CAN_L CAN_GND...

Страница 21: ...ftmost H CAN_L BLUE 3 Leftmost L NC NC NC CAN_H Rightmost H CAN_L Rightmost L Double up Double up REF SIGNAL V V GND CAN_H CAN_L Optional Daisy Chain CAN_H CAN_L GND V DeviceNet Bus D AV6A WIRING DIAG...

Страница 22: ...ey pairing as shown optional overall shield may be used for high noise environments NOTE For encoder switch connections use the crossover pinout shown for encoder PC or encoder PLC direct wiring use a...

Страница 23: ...W BROWN 16 BIT 15 WHITE YELLOW 15 BIT 14 BROWN GREEN 14 BIT 13 WHITE GREEN 13 BIT 12 BLUE RED 12 BIT 11 GREY PINK 11 BIT 10 VIOLET 10 BIT 9 BLACK 9 BIT 8 RED 8 BIT 7 BLUE 7 BIT 6 PINK 6 BIT 5 GREY 5 B...

Страница 24: ...OWN GREEN NC NC 14 BIT 13 WHITE GREEN NC 13 13 BIT 12 BLUE RED 12 12 12 BIT 11 GREY PINK 11 11 11 BIT 10 VIOLET 10 10 10 BIT 9 BLACK 9 9 9 BIT 8 RED 8 8 8 BIT 7 BLUE 7 7 7 BIT 6 PINK 6 6 6 BIT 5 GREY...

Страница 25: ...own optional overall shield may be used for high noise environments Communication Bus M Modbus TCP Pinout AV6A WIRING DIAGRAMS Master Scanner or Switch Power Supply NOTE For encoder switch connections...

Страница 26: ...B Bus A out 5 pin female 2 Rightmost A Bus B out 4 Rightmost B REF SIGNAL GND OV Vs Bus A out Bus B out Bus A in Bus B in NOTE Profibus cabling required Obey pairing as shown If termination resistor R...

Страница 27: ...NK 4 6 SET ZERO BLUE 9 7 SET DIRECTION RED 8 8 NC 5 NC 6 NC 7 NC 10 REF SIGNAL GND Vs CLK CLK DAT DAT SET ZERO SET DIRECTION NC NC NC NC NOTE Twisted pair cable required with overall shield individual...

Страница 28: ...or M12 K Radial exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed t...

Страница 29: ...12 E Axial exit E Multiturn IP65 Seals and Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed to...

Страница 30: ...M27 G End Axial exit E Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed...

Страница 31: ...R Connector M12x3 Side Exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superi...

Страница 32: ...M12 8 E Side exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed to c...

Страница 33: ...5 1 25 pilot Devicenet D Connector 2xM12 5 B Radial exit A Multiturn IP65 Seals Aluminum Steel Enclosure A DIMENSIONS IN INCHES MILLIMETERS ALL DIMENSIONS ARE APPROXIMATE Features and specifications...

Отзывы: