background image

AV6A 15

1 turn is provided in the least-significant bits.  Multiturn data is 

provided directly “above” the single turn data, bitwise.  Example:  12 

bit turns x 12 bits/turn encoder, lowest 12 bits = position within one 

turn, next 12 bits (up to bit 24) represent turns position data, most 

significant 8 bits unused.

Profile 4.0:  data is left-justified within Position 1 register:  Multi-turn 

data is provided in the most-significant bits.  Singleturn/data within 

one turn is provided directly “below” the multiturn data, bitwise.  

Example:  12 bit turns x 12 bits/turn encoder, lowest 8 bits unused, 

next 12 bits (up to bit 20) = position within one turn, next 12 bits (up 

to bit 32) represent turns position data.   

Profile 4.1:  data is right-justified:  Single-turn data/data within 

1 turn is provided in the least-significant bits.  Multiturn data is 

provided directly “above” the single turn data, bitwise and fills 

entire remaining number of bits.  Example:  12 bit turns x 12 bits/

turn encoder, lowest 12 bits = position within one turn, next 20 bits 

represent turns position data.

Setting (Zero) Position for Multiturn Encoders and Single turn 

Encoders:

This can be done manually via the master/scanner software, or via 

programmed code in the master device:  

Use manufacturer-specific telegram 860: (all data little-Endian)  

Data from encoder:  32 bits UDINT, Position, 32 bits UDINT Velocity

Data to encoder:  32 bits:  bit 32 = 1, set preset/zero position, bits 

1-31 = preset value.

Alternatively, set bit 11 of Control Word (ID=9) = 1. 

Setting Direction of Rotation for Count Up/Down:

Parameter Code Sequence (from the GSDML file) contains a 

Direction Counting Toggle for the count direction.  Use the Online 

Parameters tab to change the value.  Note that this is REVERSED 

from standard Avtron nomenclature--the encoder is viewed from the 

front.  

Setting Polling, Cyclic, Sync, and Implicit Messaging Mode

Polling, cycling, sync, and implicit messaging modes are supported 

by the encoder; use the parameters supplied in the GSDML file to 

set the appropriate mode.  Store the resulting configuration into the 

scanner module.

Storing/Saving Encoder Parameters to EEPROM

To store the current encoder operating parameters into non-volatile 

memory:  

Other Parameters

Contact Nidec Avtron for additional parameters, diagnostic registers, 

cam and programmable limit switch functionality and other 

advanced features.

PROFINET IO/ PROFIDRIVE TROUBLESHOOTING

Viewing on oscilliscope:  for Profinet IO/Profibus IRT the transmit and 

receive signal pairs should change state rapidly as the controller 

transmits messages to the encoder and the encoder replies.  

Transmission rates vary, but these messages can be extremely short 

and typically require scope triggering to spot them.  

A simple one-to-one connection can be made to an ordinary PC.    

Connect the PC to the encoder using standard (not cross-patch) 

cable.  Power the encoder using the power connector.  The encoder 

Link 1 should illuminate green.  Use the Ping command, Run “ping 

xxx.xxx.xxx.xxx” where xxx represents the IP address that has 

been assigned to the encoder.  The encoder should reply, and the 

communication “ping” time will be reported by the PC.  The Active 1 

LED should flash briefly during the communication.

A software “snoop” or “sniffer” program can also be used to packet-

analyze the communication.  

If the position is changing as the encoder moves, but is reported 

incorrectly, the Preset parameter may have been loaded into the 

encoder at the wrong physical position of the machine.  Drive the 

machine to the home/preset position, and cycle power to see if the 

position is correctly reloaded.

Profinet IO Diagnostic LEDs
LED

Status

Meaning

Stat 1

Stat 2

Link 1

Green

Off 

Green

Input connected to Ethernet, power 

OK, node address ok, no Ethernet 

errors, encoder operational, Profinet IO 

connection established

Link 2

Green

Output connected to next encoder

 

Stat 2

Flashing 

Red

IP address established, but no Profinet IO 

connection established

Active 1 Flashing 

Yellow

Active inbound communication

Active 2 Flashing 

Yellow

Active communication to next encoder

Содержание AV6A Series

Страница 1: ...tion Supplied AV6A Encoder Optional none Not Supplied Open Wrenches Hex Wrenches Dial Indicator Gauge Caliper Gauge Coupling Foot Mount and Mounting Screws AV6A PART NUMBERS AND AVAILABLE OPTIONS Mode...

Страница 2: ...cceptable loosen the mounting screws to the flange and apply thin metal shims to the face of the encoder and retest the angular alignment until acceptable 5a Remove the AV6A Transfer punch or layout t...

Страница 3: ...e encoder replies Transmission rates vary but these messages can be extremely short and typically require scope triggering to spot them For CANOpen ensure termination resistors are in place or switche...

Страница 4: ...84 12 or 14 bits F Line Driver Specs See table G Connectors See connector options on page 1 H Accuracy 0 04 deg 2 6 arc min 12 bit units 0 02 deg 1 3 arc min 16 bit units MECHANICAL A Shaft Inertia 0...

Страница 5: ...encoder is reset typically power cycled Power Up Sequence The encoder will power up in the pre operational mode The message it will issue is ID 0x07nn 0x00 nn node number typically 0x01 for units wit...

Страница 6: ...SDO object 0x2300 Example encoder at node 20 store changes ID 0x620 0x22 0x00 0x23 0x00 0x55 0xAA 0xAA 0x55 No reset is triggered Cycle power after saving changes to parameters Other Parameters Contac...

Страница 7: ...cycled before the values are stored the encoder will default to the values previously stored in EEPROM Setting Node Number To set the node number on units with a connection cap Set the address using t...

Страница 8: ...cabling system and that no termination resistors are in placed or activated in the middle of the system Remove the connections to the master controller and all devices or power down all devices Measur...

Страница 9: ...an lowest bit right most bit Single turn data data within 1 turn is provided in the least significant bits Multiturn data is provided directly above the single turn data bitwise Example 12 turns x 13...

Страница 10: ...rs encoder operational LS DA 1 Status Flashing Green Active inbound communication LS DA 2 Status Green Output connected to next encoder LS DA 2 Flashing Green Active communication to next encoder Erro...

Страница 11: ...turns position data Zero Position for Multiturn Encoders Single turn Encoders NOTE Do not attempt to use zero preset function while the encoder is rotating Doing so will produce unpredictable results...

Страница 12: ...tion Speed and Acceleration To read position into your device acceleration and speed measurement is not supported For multiturn single turn encoders position data provided as 4 bytes 32 bits Format is...

Страница 13: ...ed to each cable Use hubs or switches to connect multiple Modbus TCP encoders to the master device A software snoop or sniffer program can also be used to packet analyze the communication If the posit...

Страница 14: ...ow operate at the assigned IP address which can be validated using the ping command from the PC The assigned name can be used throughout STEP7 software to address the encoder Note that if more than on...

Страница 15: ...coder use the parameters supplied in the GSDML file to set the appropriate mode Store the resulting configuration into the scanner module Storing Saving Encoder Parameters to EEPROM To store the curre...

Страница 16: ...laced in registers identified in the configuration package Profibus DP Diagnostic LEDs LED Status Meaning STATUS ERROR Green Off Power Ok Status OK STATUS ERROR Green Red No Configuration Data Receive...

Страница 17: ...s required Measuring Position Speed and Acceleration To read position and speed into your device acceleration measurement is not supported Following the instructions for your master scanner module for...

Страница 18: ...unication A software snoop or sniffer program can also be used to packet analyze the communication If the position is changing as the encoder moves but is reported incorrectly the Preset parameter may...

Страница 19: ...Upon the Set Zero signal returning to logic zero falling edge the encoder count value will be set to zero Set Direction input 10K resistance For input logic zero or no connection the encoder will cou...

Страница 20: ...st L GND 0V BROWN 3 NC PINK NC BLUE NC GRAY CAN_H Rightmost H CAN_L Rightmost L CAN_GND Rightmost G Double up Double up REF SIGNAL CAN_GND V CAN_H CAN_L GND 0V Optional Daisy Chain CAN_H CAN_L CAN_GND...

Страница 21: ...ftmost H CAN_L BLUE 3 Leftmost L NC NC NC CAN_H Rightmost H CAN_L Rightmost L Double up Double up REF SIGNAL V V GND CAN_H CAN_L Optional Daisy Chain CAN_H CAN_L GND V DeviceNet Bus D AV6A WIRING DIAG...

Страница 22: ...ey pairing as shown optional overall shield may be used for high noise environments NOTE For encoder switch connections use the crossover pinout shown for encoder PC or encoder PLC direct wiring use a...

Страница 23: ...W BROWN 16 BIT 15 WHITE YELLOW 15 BIT 14 BROWN GREEN 14 BIT 13 WHITE GREEN 13 BIT 12 BLUE RED 12 BIT 11 GREY PINK 11 BIT 10 VIOLET 10 BIT 9 BLACK 9 BIT 8 RED 8 BIT 7 BLUE 7 BIT 6 PINK 6 BIT 5 GREY 5 B...

Страница 24: ...OWN GREEN NC NC 14 BIT 13 WHITE GREEN NC 13 13 BIT 12 BLUE RED 12 12 12 BIT 11 GREY PINK 11 11 11 BIT 10 VIOLET 10 10 10 BIT 9 BLACK 9 9 9 BIT 8 RED 8 8 8 BIT 7 BLUE 7 7 7 BIT 6 PINK 6 6 6 BIT 5 GREY...

Страница 25: ...own optional overall shield may be used for high noise environments Communication Bus M Modbus TCP Pinout AV6A WIRING DIAGRAMS Master Scanner or Switch Power Supply NOTE For encoder switch connections...

Страница 26: ...B Bus A out 5 pin female 2 Rightmost A Bus B out 4 Rightmost B REF SIGNAL GND OV Vs Bus A out Bus B out Bus A in Bus B in NOTE Profibus cabling required Obey pairing as shown If termination resistor R...

Страница 27: ...NK 4 6 SET ZERO BLUE 9 7 SET DIRECTION RED 8 8 NC 5 NC 6 NC 7 NC 10 REF SIGNAL GND Vs CLK CLK DAT DAT SET ZERO SET DIRECTION NC NC NC NC NOTE Twisted pair cable required with overall shield individual...

Страница 28: ...or M12 K Radial exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed t...

Страница 29: ...12 E Axial exit E Multiturn IP65 Seals and Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed to...

Страница 30: ...M27 G End Axial exit E Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed...

Страница 31: ...R Connector M12x3 Side Exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superi...

Страница 32: ...M12 8 E Side exit A Multiturn IP65 Seals Aluminum Steel Enclosure A Shaft front flange dimensions are independent of body connector bus systems The drawings on all these pages can be superimposed to c...

Страница 33: ...5 1 25 pilot Devicenet D Connector 2xM12 5 B Radial exit A Multiturn IP65 Seals Aluminum Steel Enclosure A DIMENSIONS IN INCHES MILLIMETERS ALL DIMENSIONS ARE APPROXIMATE Features and specifications...

Отзывы: