AVTECH Software, Inc.
Page 22
AVTECH.com
Room Alert 32S (RA32S-DAP-RAS)
1. In
Relay 1 Label
, you may leave the default, “Internal Relay 1,” or enter something
more descriptive, such as “Server Rm AC.”
Tip
2.
Choose the Profile you wish to configure in the Profile drop-down list. Depending on
your model, you may have up to 5 available Profiles, plus a “Default” profile where you
can configure the built-in Relay’s default behavior.
Associate Alarm Profiles With Sensors
Each sensor is set at Profile 1 by default; connected light towers, built-in LTA relays, Relay
Switches and built-in relay outputs execute Profile 1 when that sensor goes into an alarm
state.
You may associate a profile with a sensor by following the steps below. In this example from
our Room Alert 32S, you can see we have 5 profiles to choose from:
1. Navigate to
Settings
→
Sensors
.
2.
Find your sensor’s interface and choose the profile you’ve configured from the drop-
down list in
Use Alarm Profile
. Note that the default for all sensors is
Profile 1
. You
may also choose
No Alarm
if you do not want to associate your sensor with a profile.
3. Select
Save Settings
at the top or bottom of the page. Your Room Alert will
automatically reboot and commit your changes.
Tip
Room Alert 32S relay labels may be up to 30 characters and can include the
following: letters, numbers, spaces, and special characters.
The Room Alert 32S offers a “Default” profile plus 5 additional profiles.
Alarm Profiles affect only light towers and relays; they do not affect email
alerts.