Room Alert 32S (RA32S-DAP-RAS)
4. The
High
and
Low
fields are disabled by default.
•
To enable a High or Low threshold, select the check box in that field.
• You may then leave the default value or enter values that fall within the
Scale
range
from the previous step. In our example, we entered a conversion scale of 0 to 10
(amps) in the previous step for the Current Loop, and we’ve chosen to generate
alarms at the high and low thresholds of 6 and 2 (amps).
Tip
• The
Adjust
field is not available if custom scale is enabled. When custom scale is
disabled, you may enter a value to adjust the reading if it differs from a known
value.
Tip
5. In
Use Alarm Profile
, which controls light towers and relays on your Room Alert, you
may leave the default,
Profile 1
, or choose another Alarm Profile from the drop-down
menu.
Note
6. Select
Save Settings
at the top or bottom of the page. Your Room Alert will
automatically reboot and commit your changes.
Switch Sensor Settings
You may configure the alert state for the external switch sensors in the
Switch Sensor
Settings
fields. Shown below are the default settings.
With the custom scale enabled, you may enter positive and negative whole
numbers in High and Low that fall within the Scale range; with the custom scale
disabled, you may enter decimal numbers in the range of +/-5.0 (for 0-5 VDC).
With the custom scale disabled, you may enter decimal numbers in the range of
+/-5.0.
If you have an AVTECH Light Tower, Relay Switch or built-in relays on your
Room Alert, you may configure Alarm Profiles to toggle them on and off when
alarms are detected. Please refer to the
section in this manual for
further information.