Specifications
Table 1. 48 Vdc Extended Battery Cabinet Technical Specifications
Battery Type
Valve-regulated lead acid (VRLA); Hawker 12HR-300 or C & D Dynasty UPS12-270
Expected Life
8 years @ 20-hr rate, 25
°
C (77
°
F)
Nominal Battery String Voltage
48 Vdc
Nominal Float Voltage
2.3V/cell
Recharge Current
5A per string, 10A total
Charger AC Input
120/240 Vac, 7/4A, 50/60 Hz (625 VA nominal); automatically selected
IEC 320-C13 input connector
Circuit Protection
Circuit breaker protection
Alarm Contact
1A/30 Vac or 1A/60 Vdc
Dimensions
(WxDxH)
17.2
”
x 24.6
”
x 28.3
”
(43.7 x 62.5 x 71.9 cm)
Weight
Shipping weight: 750 lb (341 kg)
Installed weight: 665 lb (302 kg)
Operating Environment
Temperature: 10
°
C to 40
°
C (50
°
F to 104
°
F)
Recommended use: 25
°
C (77
°
F); For each 8
°
C (15
°
F) rise in temperature,
the battery loses approximately 50% of its rated life.
Humidity: 10 to 95% (noncondensing)
Altitude: -300 to +10,000 ft
Safety Conformance
UL 1778, CAN/CSA C22.2, No. 107.1-M91, EN 50091-1-1 and IEC 60950
Agency Markings
UL, cUL
EMC (Class A)
FCC Part 15, EN 50091-2, ICES-003
Table 2. Part Number
XBU48 Model
Avaya Comcode
48 Vdc
700404486