DC inverter ARV Individual Series technical manual
86
Over current protection:
“I” is the operation current of DC inverter compressor, I=24A.
Temp. sensor protection
If some malfunctions happen to discharge temp. senor , indoor coil temp. sensor, outdoor coil temp.
sensor, suction temp. sensor, ambient temp. sensor, the system will stop and display the error code.
In heating mode, if the defrosting temp. sensor is broken, and when it is time to defrost, it will directly
come to defrosting ,and last for 5 minutes. It will display the error coed when operate in cooling mode.
High pressure protection
When the switch is OFF for 2 seconds, the system stop, and 3 minutes later can start up. 3-time
protection in 60 minutes, should reset the outdoor.
Low pressure protection
When the switch is OFF for 2 seconds, the system stop, and 3 minutes later can start up. 3-time
protection in 60 minutes, should reset the outdoor.
During the first 10 minutes , defrosting progress, oil return progress, the low pressure switch will not
active.
Sequence protection
PCB detects whether the power supply is phase reversed or phase lost. IPM detects the power of DC
inverter compressor.
Communication protection
When signal missing for 4 minutes between outdoor unit and indoor unit,the system will display the
communication error code.
D
C
C
O
M
.curr
e
nt
(
A
)
I+4
I+3
I+2
I+1
I
10s late protection happen.3 minutes later can
start up;
Reduced by 2HZ/S
Reduced 1HZ/S
constant
increased by1HZ/10S
normal control
Содержание ANB66FVAMT
Страница 1: ...AUX DC inverter ARV individual series 1 Technical Manual DC Inverter ARV Individual Series ...
Страница 3: ...AUX DC inverter ARV individual series 3 ...
Страница 19: ...AUX DC inverter ARV outdoor unit individual series technical manual 16 ...
Страница 21: ...AUX DC inverter ARV outdoor unit individual series technical manual 18 ...
Страница 24: ...DC inverter ARV Individual Series technical manual 21 3 3 Wire Diagrams ARV H615 5R1B ARV H670 5R1B ...
Страница 25: ...DC inverter ARV Individual Series technical manual 22 ARV H730 5R1B ARV H780 5R1B ARV H850 5R1B ARV H900 5R1B ...
Страница 27: ...DC inverter ARV Individual Series technical manual 24 3 4Operation limits Cooling mode Heating mode ...
Страница 96: ...AUX DC inverter ARV outdoor unit individual series technical manual 93 ...
Страница 113: ...AUX DC inverter ARV outdoor unit individual series technical manual 110 ...
Страница 127: ...AUX DC inverter ARV outdoor unit individual series technical manual 124 ...