AUX-DC inverter ARV outdoor unit individual series technical manual
100
2. Other branch pipes and shouldnot larger than the 1
st
Branch pipe.
Diameter of pipe “3” depends on connected indoor unit capacity.
Cooling capacity of
indoor unit(kW)
Gas pipe(mm)
Liquid pipe(mm)
Remark
2.2
φ9.52
φ6.35
2.8
φ9.52
φ6.35
Cassette and Ceiling & Floor unit: 12.7/6.35
3.6
φ12.7
φ6.35
4.5
φ12.7
φ6.35
5.6
φ12.7
φ6.35
7.1
φ15.88
φ9.52
8.0
φ15.88
φ9.52
9.0
φ15.88
φ9.52
10.0
φ15.88
φ9.52
11.2
φ19.05
φ9.52
12.5
φ19.05
φ9.52
14.0
φ19.05
φ9.52
15.0
φ19.05
φ9.52
Minimum thickness of pipe should meet data of the following table.
Diameter of pipe (mm)
φ6.35
φ9.52
φ12.7
φ15.88
φ19.05
φ22.2
Minimum wall thickness (mm)
0.8
0.8
1.0
1.0
1.0
1.2
Diameter of pipe (mm)
Φ25.4
Φ28.6
Φ34.93
Φ41.3
Φ44.5
Φ47.6
Minimum wall thickness (mm)
1.2
1.3
1.5
1.5
2
2
Содержание ANB66FVAMT
Страница 1: ...AUX DC inverter ARV individual series 1 Technical Manual DC Inverter ARV Individual Series ...
Страница 3: ...AUX DC inverter ARV individual series 3 ...
Страница 19: ...AUX DC inverter ARV outdoor unit individual series technical manual 16 ...
Страница 21: ...AUX DC inverter ARV outdoor unit individual series technical manual 18 ...
Страница 24: ...DC inverter ARV Individual Series technical manual 21 3 3 Wire Diagrams ARV H615 5R1B ARV H670 5R1B ...
Страница 25: ...DC inverter ARV Individual Series technical manual 22 ARV H730 5R1B ARV H780 5R1B ARV H850 5R1B ARV H900 5R1B ...
Страница 27: ...DC inverter ARV Individual Series technical manual 24 3 4Operation limits Cooling mode Heating mode ...
Страница 96: ...AUX DC inverter ARV outdoor unit individual series technical manual 93 ...
Страница 113: ...AUX DC inverter ARV outdoor unit individual series technical manual 110 ...
Страница 127: ...AUX DC inverter ARV outdoor unit individual series technical manual 124 ...