AUX-DC inverter ARV outdoor unit individual series technical manual
10
Fan Quantity
2
2
3
Outdoor Coil
a.Number Of Row
3
3
2
b.Tube Pitch(a)x Row
Pitch(b)
mm
22×19.05
22×19.05
22×19.05
c.Fin Pitch
mm
1.5
1.5
1.5
d.Fin Material
Hydrophilic
aluminum fin
Hydrophilic
aluminum fin
Hydrophilic
aluminum fin
e.Tube Outside
Dia.And Material
mm
φ7
,
Inner grooved
φ7
,
Inner grooved
φ7
,
Inner grooved
f.Coil Length x Height x
Width
mm
2600×1232×57.1
2600×1232×57.1
4128×1232×38.1
g.Heat Exchanging
Area
m
2
217.88
217.88
230.62
Air Flow Volume
CFM
12353
12353
16471
m
3
/h
21000
21000
28000
Noise Level
dB(A)
≤63
≤63
≤65
Dimension(W×D
×H)
Net
mm
1590×765×1600
1590×765×1600
2350×765×1600
Packing
mm
1650×815×1770
1650×815×1770
2410×815×1770
Weight
Net
kg
400
400
500
Gross
kg
420
420
515
Refrigerant
type/Quantity
Type
R410A
R410A
R410a
Charged Volume
kg
18
18
25
Design Pressure
MPa
4.2
4.2
4.2
Refrigerant
Piping
Liquid Side
mm
φ15.88
φ15.88
φ
19.05
Gas Side
mm
φ28.6
φ28.6
φ
34.9
Max. Length
m
1000
1000
1000
Max. Height
m
≤
90m
≤
90m
≤
90m
Ambient Temp (Cooling/Heating)
℃
-5~52/-20~27
-5~52/-20~27
-5~52/-20~27
Stuffing Quantity
20/40/40H
Unit
7/14/14
7/14/14
4/8/8
Notes:
1. Cooling Capacity: Indoor temperature 27
℃
DB / 19
℃
WB; Outdoor temperature:35
℃
DB / 24
℃
WB;
2. Heating Capacity: Indoor temperature 20
℃
DB; Outdoor temperature:7
℃
DB / 6
℃
WB;
3. Piping Length:Equivalent piping length:5m,level difference:0m;
4. Anechoic chamber conversion value,measured in test room.During actual operation.These values
are normally somewhat higher as a result of ambient conditions ;
5. The above designs and specifications are subject to change of product improvement without prior
notice.
Содержание ANB66FVAMT
Страница 1: ...AUX DC inverter ARV individual series 1 Technical Manual DC Inverter ARV Individual Series ...
Страница 3: ...AUX DC inverter ARV individual series 3 ...
Страница 19: ...AUX DC inverter ARV outdoor unit individual series technical manual 16 ...
Страница 21: ...AUX DC inverter ARV outdoor unit individual series technical manual 18 ...
Страница 24: ...DC inverter ARV Individual Series technical manual 21 3 3 Wire Diagrams ARV H615 5R1B ARV H670 5R1B ...
Страница 25: ...DC inverter ARV Individual Series technical manual 22 ARV H730 5R1B ARV H780 5R1B ARV H850 5R1B ARV H900 5R1B ...
Страница 27: ...DC inverter ARV Individual Series technical manual 24 3 4Operation limits Cooling mode Heating mode ...
Страница 96: ...AUX DC inverter ARV outdoor unit individual series technical manual 93 ...
Страница 113: ...AUX DC inverter ARV outdoor unit individual series technical manual 110 ...
Страница 127: ...AUX DC inverter ARV outdoor unit individual series technical manual 124 ...