DC inverter ARV Individual Series technical manual
80
Heating Capacity Correction Coefficient “K4” under Frosting of Outdoor Heat Exchanger
Outdoor Ambient Temperature [
℃
]
Capacity Correction
In cooling mode: actual cooling capacity = nominal cooling capacity×K3
In heating mode: actual Heating capacity = nominal cooling capacity×K3×K4
Units selection example
(Selection procedure for cooling and heating are the same)
(1) Given condition
a. temperature condition
Cooling: Indoor 21°C (WB), Outdoor 35°C (DB)
b. Cooling load
Room A
Room B
Room C
Room D
Load (kW)
2.5
9.5
5.3
6.0
c. Piping equivalent length: 30m
d. Height difference: 10m (Outdoor unit is lower than indoor units)
(2)Indoor unit selection
Содержание ANB66FVAMT
Страница 1: ...AUX DC inverter ARV individual series 1 Technical Manual DC Inverter ARV Individual Series ...
Страница 3: ...AUX DC inverter ARV individual series 3 ...
Страница 19: ...AUX DC inverter ARV outdoor unit individual series technical manual 16 ...
Страница 21: ...AUX DC inverter ARV outdoor unit individual series technical manual 18 ...
Страница 24: ...DC inverter ARV Individual Series technical manual 21 3 3 Wire Diagrams ARV H615 5R1B ARV H670 5R1B ...
Страница 25: ...DC inverter ARV Individual Series technical manual 22 ARV H730 5R1B ARV H780 5R1B ARV H850 5R1B ARV H900 5R1B ...
Страница 27: ...DC inverter ARV Individual Series technical manual 24 3 4Operation limits Cooling mode Heating mode ...
Страница 96: ...AUX DC inverter ARV outdoor unit individual series technical manual 93 ...
Страница 113: ...AUX DC inverter ARV outdoor unit individual series technical manual 110 ...
Страница 127: ...AUX DC inverter ARV outdoor unit individual series technical manual 124 ...