10 Program Instructions
68
© Copyright Reserved Autonics Co., Ltd.
10.3
Program control Instruction
10.3.1
JMP (jump)
It jumps to the designated step (Step No.).
instruction
DATA
JMP
Instruction
Step no.
Step No. : Set the step number to jump. Setting range is 0 to 255.
When using JMP instruction, be sure to the position of END instruction.
At the loop between REP, RPE instruction, do not use JMP (jump).
10.3.2
REP (repeat start)
It operates repeatedly for the set times from the next step of this instruction to RPE (repeat end
instruction).
Instruction
DATA
REP
Instruction
Repeat count
Repeat Count
: Set the repeat times. Setting range is 1 to 255.
RPE (repeat end) instruction should be below (higher step number) of the REP (repeat
start) instruction. The lower nested loops are available up to 3.
Содержание AiC Series
Страница 1: ...AiC Series User Manual AiC Series Controller Integrated 2 Phase Closed Loop Stepper Motor System ...
Страница 2: ...ii Copyright Reserved Autonics Co Ltd ...
Страница 12: ...Table of Contents xii Copyright Reserved Autonics Co Ltd ...
Страница 22: ...2 Specifications 22 Copyright Reserved Autonics Co Ltd ...
Страница 26: ...3 Dimensions 26 Copyright Reserved Autonics Co Ltd ...
Страница 31: ...5 Connection Copyright Reserved Autonics Co Ltd 31 5 Connection ...
Страница 32: ...5 Connection 32 Copyright Reserved Autonics Co Ltd ...
Страница 34: ...6 Characteristics 34 Copyright Reserved Autonics Co Ltd ...
Страница 54: ...8 Control Input Output 54 Copyright Reserved Autonics Co Ltd ...
Страница 70: ...10 Program Instructions 70 Copyright Reserved Autonics Co Ltd ...
Страница 86: ...11 Driver Function 86 Copyright Reserved Autonics Co Ltd ...