5.5 Pulse
This option allows you to configure the pulse output. The output can be set to provide a pulse
for a defined amount of energy active or reactive.
This option sets the pulse output type, pulse rate, duration time.
From the Set-up menu, Use and to select the Pulse option.
5.5.1 Pulse output1
Pulse output 1 setting
Output type options: Total kwh, Import kwh, Export kwh, Total
kVarh, Import kVarh, Export kVarh.
Default: Total import kWh
Long press to enter the PT Pulse Output 1 routine.
Example shows:
Pulse Output 1: Total kWh
Options:
Total
kWh
, Total kVarh, Import kWh, Export kWh, Import kVarh,
Export kVarh.
Long press , the setting will flash.
and to choose Options.
Long press for confirmation.
5.5.2 Pulse rate
Pulse rate options: 0.001 , 0.01 , 0.1 , 1, 10, 100, 1000 kWh / kVarh per Pulse
Default : 0.01 kWh (100imp/kWh)
Use and to select Pulse Rate option.
Long press the setting will flash.
Use and to choose Options.
Long press for confirmation.
Example shows:
Pulse rate: 0.01
kWh
Total
P
PF Hz
MD
P
PF Hz
MD
P
PF Hz
MD
E
E
P
PF Hz
MD
E
E
E