DL205 Installation and I/O Manual, 2nd Edition
3–54
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-04THM 4-Channel Thermocouple Input Module
Notes:
1: Terminate shields at the respective signal source.
2: Connect unused channels to a common terminal (0V, CH4+, CH4).
3: When using 0-156 mV and 5V ranges, connect (-) or (0) volts terminal to 0V to
ensure common mode range acceptance.
4. This module is not compatible with the ZIPLink wiring system.
Number of Channels
4, differential
Common Mode Range
±5 VDC
Common Mode Rejection
90 dB min. @ DC, 150 dB min. @ 50/60 Hz.
Input Impedance
1 M
Absolute Maximum Ratings
Fault-protected inputs to ±50 VDC
Accuracy vs. Temperature
±5 ppm/ºC maximum full scale calibration
(including maximum offset change)
PLC Update Rate
4 channels per scan max.
D2-240/250(-1)/D2-260 CPU, H2-EBC(-F);
1 chan. per scan max. D2-230 CPU
Digital Input Points Required
32 (X) input points (16 binary data bits,
2 channel ID bits, 4 diagnostic bits)
External Power Supply
60 mA maximum, 18 to 26.4 VDC
Base Power Required 5VDC
110 mA
Operating Temperature
32º to 140ºF (0º to 60ºC)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Non-removable
CPU Firmware Required
CPU
Firmware Required
D2-230
V1.06
D2-240
V2.5
D2-250
V1.06
D2-250-1, D2-260
All firmware versions work