DL205 RTD and Thermocouple Modules
DL205 Installation and I/O Manual, 2nd Edition
3–52
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-04RTD 4-Channel RTD Input Module
Number of Channels
4
Input Ranges
Type Pt100: -200.0/850.0ºC,
-328/1562ºF
Type Pt1000: -200.0/595.0ºC,
-328/1103ºF
Type jPt100: -38.0/450.0ºC,
-36/842ºF
Type CU-10/25ž: -200.0/260.0ºC,
-328/500ºF
Resolution
16 bit (1 in 65535)
Display Resolution
±0.1ºC, ±0.1ºF (±3276.7)
RTD Excitation Current
200 µA
Input Type
Differential
Notch Filter
>100 db notches at 50/60 Hz
-3db=13.1Hz
Maximum Setting Time
100ms (full-scale step input)
Common Mode Range
0-5 VDC
Absolute Maximum
Ratings
Fault protected inputs to ±50 VDC
Sampling Rate
160 ms per channel
Converter Type
Charge Balancing
Linearity Error
±.05ºC maximum, ±.01ºC typical
Maximum Inaccuracy
±1ºC
PLC Update Rate
4 channel/scan max., 240/250(-1)/D2-260CPUs
1 channel per scan max., 230 CPU
Digital Input Points Required
32 input points (16 binary data bits,
2 channel ID bits, 4 fault bits)
Base Power Required 5VDC
90 mA
Operating Temperature
32° to 140°F (0° to 60°C)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Temperature Drift
None (self-calibrating)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON