DL205 Installation and I/O Manual, 2nd Edition
3–58
Chapter 3: I/O Wiring and Specifications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
F2-02DA-1L 2-Channel 4-20mA Analog Output Module
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).
This module requires a 12 VDC user power supply for operation. See the F2-02DA-1 on the
previous page if you want to use a 24 VDC supply. All other specifications are the same.
Number of Channels
2
Output Ranges
4 to 20 mA
Resolution
12 bit (1 in 4096)
Output Type
Single ended, 1 common
Digital Output Points
Required
16(Y) output points
(12 binary data bits, 2 channel ID bits)
Maximum Loop Supply
30 VDC
Peak Output Voltage
40 VDC
(clamped by transient voltage suppressor)
Load Impedance
0
minimum
Maximum Load/Power
Supply
620
/18V, 910
/24V, 1200
/30V
PLC Update Rate
1 channel per scan maximum (D2-230 CPU)
2 channels per scan maximum (D2-240,
D2-250(-1) and D2-260 CPUs)
Linearity Error (end to end)
±1 count (0.025% of full scale) maximum
Conversion Settling Time
100 µs maximum (full scale change)
Full Scale Calibration Error
(offset error included)
±5 counts max., 20 mA @ 77ºF (25ºC)
Offset Calibration Error
±3 counts max., 4mA @ 77ºF (25ºC)
Accuracy vs. Temperature
±50 ppm/ºC full scale calibration change
(including maximum offset change of 2 counts)
Maximum Inaccuracy
+0.1% @ 77ºF (25ºC)
±0.3% @ 32 to 140°F (0 to 60°C)
Base Power Required 5VDC
40 mA
External Power Supply
10 to 15 VDC, 70 mA
(add 20 mA for each current loop used)
Operating Temperature
32º to 140ºF (0º to 60ºC)
Storage Temperature
-4º to 158ºF (-20º to 70ºC)
Relative Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Shock & Vibration
MIL STD 810C 514.2
Noise Immunity
NEMA ICS3-304
Terminal Type (included)
Removable; D2-8IOCON