The informat ion conta ined in th is docu ment is the property of Automat ic Syst ems and is conf ident ial. The rec ip ient is forb idd en to use it for any purpose ot her
than for the use of the products or the exe cut ion of the project to wh ich th ey refer or to communicate it to th ird parties w ithout the pr ior wr itten conse nt of
Automat ic Systems. Document sub ject to change w ithout advance not if icat ion .
SL93x + TBV327-MT-EN
p. 12/40
3.4. Electrical connections
WARNING
: The operations must be undertaken in accordance with the safety warnings, ch.1.
In particular, the mains must be shut down before any of the work described below is begun.
Connections must be executed
in accordance with the wiring diagrams
provided inside the equipment,
which
remain the reference
.
Type of
cable
Connections
3G2.5²
Electrical power supply of
each equipment (230 V
single phase +
differential breaker 30 mA
min for each equipment).
WARNING
: High leakage
current.
=> Connection to the
ground imperative with a
1-mm² cable before
connecting the mains.
=> Do not connect
several equipments to the
same differential breaker.
2.5²
If the gates are powered
through long cables,
ensure the equipotential
bonding between the
gates forming a bank by
connecting them with a
1-mm² ground wire.
Δ 30
m A
Δ 30
m A
230 VAC - 50 Hz