![Autocall 4007ES Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/autocall/4007es/4007es_operators-manual_3021010007.webp)
Page 5
579-1165AC Rev C
4007ES Operator’s Manual
3 User Interface
The user interface is used to operate the FACP.
Power LED
Alarm Silenced LED
Trouble LED
Priority 2 LED
Supervisory LED
Fire LED
Slide-in Labels
Bi-Color User Defined LEDs
Piezo
Touchscreen
Fig 1: 4007ES User Interface
Power LED
Alarm Silenced LED
Trouble LED
Priority 2 LED
Supervisory LED
Fire LED
Bi-Color User Defined LEDs
Slide-in Labels
Piezo
Touchscreen
Keyswitch
Fig 2: Color Touchscreen LCD Annunciator User Interface
Table 1: Components of the FACP User Interface
Component
Description
Touchscreen
Used as the panel’s input/output interface.
Piezo
Emits tones during Alarm, Trouble, Pri2 and Supervisory conditions.
Bi-color User- Defined LEDs Associated with the three custom-configured user buttons. The top two LEDs can be either yellow or red. The bottom
LED can be either yellow or green.
Slide-in Labels
Used to describe the functions of the user buttons.
Fire LED
Indicates a fire alarm when flashing and an acknowledged alarm when steady on.
Priority 2 LED
Indicates a Priority 2 condition when flashing and an acknowledged condition when steady on.
Supervisory LED
Indicates a Supervisory condition when flashing and an acknowledged condition when steady on.
Trouble LED
Indicates a Trouble state when flashing and acknowledged Trouble when steady on.
Alarm Silence LED
Indicates an alarm has been silenced when steady on.
Power LED
Indicates AC power is applied to the panel when steady on.
Keyswitch
(Only on the Color Touchscreen LCD Annunciator) Allows interaction with the panel if the key is used.