Operating manual Folding corner fireplace inserts
EN
9 | Installation instructions
37
9.2
Convection claddings
Model 38x38x57 K and 55x55x have no convection cladding.
KV cladding 63x40x42 K right
KV cladding 63x40x42 K left
9.3
Convection chamber
5
4
16
Fig. 8:
Convection space
• If the convection cladding (appliance part) is not used, a
convection space of at least 6 cm depth between fire-
place insert (4) and insulation layer (16) to the rear and
on both sides must be allowed for.
• The convection space (5) must be heat-insulated to all
areas that are not heat-emitting claddings.
• The walls, the floor and the ceiling of the heating cham-
ber must be clean and resistant to abrasion (see tech-
nical rules of the stove- and air heating constructors as-
sociation). Therefore the insulation layer, if it is not cal-
cium silicate slabs, must be protected with an abrasion-
resistant material (heat shield/heating chamber plate or
similar).
4 Convection space between fireplace insert and insulation
layer
5 Convection space
16 Insulation layer