AURATON S14 Скачать руководство пользователя страница 8

9

8

1.

Current temperature on the 

CH sensor (SR2)

2

. Indicator of the set CH 

temperature in the 
fireplace circuit,

3

. Indicator of the set 

temperature of the 
automatically reset 
actuator or the second CH 
pump,

4.

Indicator of manual activation 

of the CH pump,

5.

CH pump operation indicator,

6.

Indicator of operation of a tee valve or the second CH pump,

7.

Indicator of manual activation of a tee valve or the second CH pump.

3.2.7.  Manual mode - continuous operation 

In order to manually switch on the circulating pump (regardless of the 
current temperature at the 

SR1

 (CH) sensor), press the "

A

" button and 

hold it pressed for 3 seconds.
The display will show the hand symbol "

" (

3

). If you wish to switch off 

the pump's manual operation, press the "

A

" button again and hold it 

pressed for 3 seconds.

NOTE: When only the SR1 sensor is connected, the remaining functions 
of the controller are inactive, i.e. there is no indication of operation of 
CH pumps in the fire place circuit and of the control of the pump in the 
HDW circuit.

[h]

3.3. Diagram of connection of the controller with 

the pump at the CH boiler

0

I

A

B

C

D

SR1 SR2 SR3

OUT1

OUT2

OUT3

OUT4

OUT5

IN

CH 

boiler

Pump

230V 

mains power supply

Temperature sensor 
(fix with a band)

4

Description of a controller working with 
a CH pump and an automatically reset 
actuator, or with a second CH pump - 
a fireplace boiler stove circuit 

(part B of the display)

4

6

7

1

5

B

2

3

AURATON S14 

in a circuit with a boiler stove fireplace uses two control 

outputs:

one for the water pump in the fireplace circuit;

ź

one for an actuated valve or the second pump, which is required for 

ź

proper cooperation between the boiler stove fireplace with the CH 
circuit. 

After the power supply is switched on, temperature in the water jacket of 
the  boiler  stove  fireplace  is  measured  (with  the  digital  sensor);  the 
temperature signal can be divided into two independent channels.  

Depending  on  the  temperature  of  water  in  the  fireplace  circuit,  the 
controller automatically starts or stops the CH pump of the fireplace and 
starts the valve or the second pump. 

The 

AURATON  S14

 

controller  also  has  the 

GUARD 

functions  which 

prevents the stalling process in the rotor of the pump when it is not in use. 
After the heating season, 

AURATON S14

 automatically starts the pump 

for 30 seconds every 14 days. 

In order for the system to work after the heating season, the controller 
must be switched on at all times.  

Содержание S14

Страница 1: ...User manual www auraton pl S14 dla oprogramowania w ver F03 oraz F0A ...

Страница 2: ...1 ThedisplayoftheAURATONS14controllerisdividedintofourparts Eachpartcorrespondstoaseparatedevicesupportedbythecontroller PartA Controlofthecentralheating CH pump PartB Control of the central heating CH pump the automatically reset actuator or the second central heating pump in the fireplacecircuit PartC Controlofthehotdomesticwater HDW circulatingpump PartD Controlofthefan blower ON OFF S MIN STOP...

Страница 3: ...ors 2 User ssetting 3 Counted operation time of the fan and the duration of the interval betweentheblow throughs 4 Indicatorofextinguishedfireinthefurnace 5 Indicatorofemergencyshutdownofthefan 6 Indicatorofmanualactivationofthedevice 7 Indicatorofignition 8 Indicatoroffanpowerpercentagevalue 9 Indicatorofforcedoperation oftheCHpump 10 Indicatorofsustainedfireinthefurnace ...

Страница 4: ... provided with an approx 2 5 m long cable If an expanded functionality of the controller is required additional temperature sensors must be bought option If the length of the cable is inadequate a sensor with an approx 15 m long cable can be purchased 4 1 2 3 4 5 6 7 8 0 I A B C D SR1 SR2 SR3 OUT1 OUT2 OUT3 OUT4 OUT5 IN Description of buttons and cable terminals 2 NOTE Inordertoaccessthecabletermi...

Страница 5: ...to circulate in a CH system with a coal fired boiler or a gas boiler without a system controlling the operation of the pump The controller s sensor measures the temperatureofthewateronthesupplysideoftheCHsystem In a CH system with a coal fired boiler the controller switches off the circulation pump after the flame in the boiler is extinguished Pumping of water is not recommended when the flame is ...

Страница 6: ...ing them off In the controller connect the temperature sensor to the SR1 terminals Then install the sensor on an uncovered outlet pipe connected totheCHboiler asclosetotheboileraspossible NOTE If a coal fired boiler and a gas fired boiler work in the same CH system the sensor should be installed in a location where the two outletsmergeandmustbeinsulated 3 1 4 Connection check Checkifthewireisconne...

Страница 7: ...topat38 C 3 2 5 Changing the forced pump operation mode Press the A button under the temperature setting The digits begin to blink and indicate the value of the current setting Display the hysteresis setting HI by pressing the A button again After you press the A button one more time the value of 85 C will be displayed in the temperature section and on the right side of the display the symbol of f...

Страница 8: ...n again and hold it pressedfor3seconds NOTE When only the SR1 sensor is connected the remaining functions of the controller are inactive i e there is no indication of operation of CH pumps in the fire place circuit and of the control of the pump in the HDWcircuit h 3 3 Diagram of connection of the controller with the pump at the CH boiler 0 I A B C D SR1 SR2 SR3 OUT1 OUT2 OUT3 OUT4 OUT5 IN CH boil...

Страница 9: ... stove fireplace uses two control outputs oneforthewaterpumpinthefireplacecircuit ź one for an actuated valve or the second pump which is required for ź proper cooperation between the boiler stove fireplace with the CH circuit After the power supply is switched on temperature in the water jacket of the boiler stove fireplace is measured with the digital sensor the temperaturesignalcanbedividedinto...

Страница 10: ...e immersed in liquids or installedatthefireplacesmokeoutlets 4 1 4 Connecting the power supply cable to the valve or the second CH pump In the controller the valve s cable must be connected to the OUT3 terminal L N In the valve connect the green or yellow green wire grounding or protective zero to the terminal grounding symbol the bluewire tothe N terminal andthebrownwire tothe L terminal u 4 1 5 ...

Страница 11: ...ain When the CH set temperature indicator right of the valve or the second CH pump in the fireplace circuit starts blinking use the or button to set the desired temperature After the value is set approve it within 10 seconds by pressing the OK button Otherwise the changed valuewillnot be saved and the controller willreturntotheprevioussetting 4 2 4 Changing the hysteresis Press the B button under ...

Страница 12: ...anged setting willnotbesavedandthecontrollerwillreturntotheprevioussetting 4 2 6 Automatic operation The controller starts or stops the pump and the valve depending on the set temperature value In the CH system the pump and the valve are started when the temperature in the location of the sensor exceeds the set value and stopped when the temperature drops below the value set in the controller taki...

Страница 13: ...lementsnecessaryforproperoperationofthesystem 1 7 2 3 4 5 8 9 6 230V mains power supply 0 I A B C D SR1 SR2 SR3 OUT1 OUT2 OUT3 OUT4 OUT5 IN 1 Boiler stove fireplace 6 Radiator 2 Cut offvalve 7 Compressionvessel 3 Pump 8 Temperaturesensor 4 Exchanger 9 CHboiler 5 Automaticallyresetactuator NOTE When only the SR2 sensor is connected the remaining functions of the controller are inactive i e there is...

Страница 14: ...oller working with a hot domestic water HDW pump part C of the display C 4 5 1 2 3 5 5 1 Operation with the HDW over CH priority switched on If the HDW over CH priority function is switched on then the pump in the HDW circuit depends only on the setting and on the temperature measuredbytheSR3sensorinstalledinthetank 5 1 1 Settings range Temperature from 0 C to 99 C is measured by the SR3 sensor Th...

Страница 15: ...rinthetank 5 1 2 Programming of the HDW functions When the button is pressed the value of 50 C factory setting starts blinking Usethe or buttontosetthedesiredtemperature Once the desired temperature value is set it must be confirmed do not forget to do so within 10 seconds by pressing the button Otherwise the changed value will not be saved and the controller will returntotheprevioussetting After ...

Страница 16: ...sor On the controller side the temperature sensor must be connected to the SR3 terminals and then installed in the hot domestic water tank The sensor must not be immersed in liquids or installed at the fireplace smoke outlets Themaximummeasuredtemperaturevalueis99 C 5 2 1 Manual mode continuous operation In order to manually switch on the circulating pump regardless of thecurrent temperature at th...

Страница 17: ...ll not be saved and the controllerwillreturntotheprevioussetting 5 4 3 Changing the hysteresis Press the C button under the temperature setting The digits begin to blink and indicate the value of the current setting Display the hysteresis setting HI by pressing the C button again Using the or button set the required hysteresis value in the range of 2 C to 10 C with a 2 C increment After the value ...

Страница 18: ... displays the value of 85 C which means that above this temperature value measured by the SR1 sensor the CH pump will be started in the A section On the other hand section C setting value displays the value of 85 C which means that the tank will collect heat but only to the value of 85 C SR3 Also the forced operation indicator the CH pump is switched on is displayed After the value is set approve ...

Страница 19: ... indicator 11 Settimeunit S second MIN minute on hedoff ature of ding of begin to Display en press r hing the nd blink hen the button of 85 C the SR1 e other h means Also the splayed sing the and the ere the 5 C and In such mp in the p in the witched er supply V mains 0 IN 5 5 2 With the HDW tank Pump HDW sensor HDW tank 0 I A B C D SR1 SR2 SR3 OUT1 OUT2 OUT3 OUT4 OUT5 IN NOTE When only the SR3 se...

Страница 20: ...be connected to the OUT5 terminal L N In the blower connect the green or yellow green wire grounding or zero to the terminal the blue wire to the N terminal andthebrownwire tothe L terminal 6 1 1 Mounting the controller The controller must be mounted on a wall or another support using two screws the concrete anchors with screws are delivered with the controller The cables extending from the contro...

Страница 21: ...temperature value is set it must be confirmed do not forget to do so within 10 seconds by pressing the OK button Otherwise the changed value will not be saved and the controller will returntotheprevioussetting 6 2 4 Changing the operation time and the time of periodic breaks in the fan s operation Press the D button once The fan temperature will start blinking If you press the D button again withi...

Страница 22: ...emperature value Once the desired temperature value is set it must be confirmed saved within 10 seconds by pressing the OK button Otherwise the changed setting will not be saved and the controller will returntotheprevioussetting 6 2 6 Changing the hysteresis To change the hysteresis value press the D button and display the fan temperature If you press the D button again the fan operation time and ...

Страница 23: ...ere 100 is the maximum fan power value In order to change the fan power press the D button and display the fan temperature If you press the D button again the fan operation time and the break time settings will be displayed By pressing the D button yet again you will display the definitive fan switch off temperature and the STOP LO text Press the D button one more time and set the desired hysteres...

Страница 24: ...o switch off and then switch on again the controller using the switch in ordertostarttheignitionfunction 0 I 0 I 6 2 11 Adding fuel to the furnace During normal operation fuel can be added with the operation of the fan blocked intwoways Switch off the controller using the switch Add fuel and then ź switch on the controller and start the ignition function at the same time The second method consists...

Страница 25: ...ress and hold the OK button and the button for about 3 seconds The activation ofthepermanentilluminationisconfirmedwithasoundsignal The permanent illumination can be switched off by pressing the OK and button simultaneously The deactivation of the permanent illuminationisconfirmedwithasoundsignal NOTE The first time any function button is pressed the illumination is switchedonfirst ifthepermanenti...

Страница 26: ...t stop f 2 10 Supply voltage 230V 50Hz Maximum load for output sum 6A C C C C diff rom C to C A Data pertaining to the controller working in a CH circuit Temperature settings range 10 85 Range of measured values 0 99 Hysteresis start stop f 2 10 Supply voltage 230V 50Hz Maximum load for output sum 6A C C C C diff rom C to C B Data pertaining to the controller working with a CH pump and valve Z or ...

Страница 27: ...a pertaining to the controller working with a fan Cleaning and maintenance ź The outside of the controller must be cleaned with a clean cloth Do not use solvents suchasbenzene thinners oralcohol ź Do not touch the device with wet hands This can lead to electric shock or seriousdamagetothedevice ź Nonotexposethedevicetoexcessiveimpactofsmokeordust ź Donottouchthedisplaywithsharpobjects ź Avoidconta...

Страница 28: ...www auraton pl ...

Отзывы: