AUTO operation mode

During  normal  operation,  when  the  controller  attempts  to  reach  the 
temperature value set in the "

D

" section, the 

AUTO

 text is displayed. At 

that time, the fan is working at full power (programmed as a percentage) 
until the set value is reached. After the temperature is reached, the fan 
switches to periodic operation (with breaks between blow-throughs).

6.2.5. Furnace extinguishing function   

If the temperature on the

 SR1

 sensor drops below the preset value (the 

factory setting is 30°C) for at least 30 minutes, then the fan is stopped 
definitively  and  the  display  shows  the  blinking  text 

STOP  LO

.  The  fan 

leaves the definitive switch off state automatically when the temperature 
measured by the 

SR1

 sensor increases above 30 °C.

The definitive fan switch off temperature can be set in the range of 15 °C 
to 40°C. To do so, press the "

D

" button and display the fan temperature. If 

you press the "

D

" button again, the fan operation time and the break 

time settings will be displayed. By pressing the "

D

" button yet again (the 

shut-down temperature and the 

STOP LO

 text are displayed), you can set 

the definitive fan switch-off temperature. 
Using  the  "+"  (increase)  and  "-"  (decrease)  buttons,  you  can  set  the 
desired temperature value. Once the desired temperature value is set, it 
must  be  confirmed  (saved)  within  10  seconds  by  pressing  the  "

OK

button. 
Otherwise, the changed setting will not be saved and the controller will 
return to the previous setting.

6.2.6. Changing the hysteresis

To change the hysteresis value, press the "

D

" button and display the fan 

temperature. If you press the "

D

" button again, the fan operation time 

and the break time settings will be displayed. By pressing the  "

D

" button 

yet again, you will display the definitive fan switch-off temperature and 
the 

STOP LO

 text. Press the

 "D" 

button one more time and use the "+" or 

"-"  button  to  set  the  desired  hysteresis  value.  Once  the  desired 
temperature value is set, it must be confirmed (saved) within 10 seconds 
by pressing the "

OK

" button. Otherwise, the changed setting will not be 

saved and the controller will return to the previous setting.

Example: Then the temperature setting is 40°C and the hysteresis setting 
is 4°C, the fan is permanently switched on when the temperature drops 
below  38°C  and  moves  to  periodic  operation  when  the  temperature 
reaches 42 C.

6.2.8.  Setting the fan's soft start time  

AURATON S14

 enables setting the time within which, after its start, the 

fan will reach its full power (the percentage value that has been set - see 
item 6.2.7. Setting the maximum fan power value). It is possible to set the 
fan's soft start time in the range of 0 seconds (start with the full set power) 
to 15 seconds, after which the fan reaches its full preset power. The value 
can be set using the "+" (increase) or "-" (decrease) buttons. Once the 
desired temperature value is set, it must be confirmed (saved) within 10 
seconds by pressing the "

OK

" button. 

Otherwise, the changed setting will not be saved and the controller will 
return to the previous setting.

6.2.7.  Setting the maximum fan power value  

The controller has a function that enables fixing the maximum fan power 
as a percentage value. The fan power can be set in the range of 30% to 
100% (where 100% is the maximum fan power value). In order to change 
the fan power, press the "

D

" button and display the fan temperature. If 

you press the "

D

" button again, the fan operation time and the break 

time settings will be displayed. By pressing the "

D

" button yet again, you 

will display the definitive fan switch-off temperature and the 

STOP LO

 

text. Press the "

D

" button one more time and set the desired hysteresis 

value.
After  you  press  the  "

D

"  button  again,  you  can  set  the  maximum  fan 

power (the displayed factory-set value is 100%).
Use the "+" (increase) or "-" (decrease) buttons to set the desired value of 
fan  power.  Once  the  desired  temperature  value  is  set,  it  must  be 
confirmed  (saved)  within  10  seconds  by  pressing  the  "

OK

"  button. 

Otherwise, the changed setting will not be saved and the controller will 
return to the previous setting.

NOTE: Maximum fan power in the range of 30% to 100% means that the 
fan will also be in operation during ignition with the preset value of 
power.

6.2.9.  Manual mode - continuous operation      

In  order  to  manually  switch  on  the  fan  (regardless  of  the  current 
temperature at the 

SR1

 sensor), press the "

D

" button for 3 seconds. The 

display will then show the "     " sign next to the fan symbol. If you wish to 
switch off the fan's manual operation, press the "

D

" button again and 

hold it pressed for 3 seconds.

Содержание S14

Страница 1: ...User manual www auraton pl S14 dla oprogramowania w ver F03 oraz F0A ...

Страница 2: ...1 ThedisplayoftheAURATONS14controllerisdividedintofourparts Eachpartcorrespondstoaseparatedevicesupportedbythecontroller PartA Controlofthecentralheating CH pump PartB Control of the central heating CH pump the automatically reset actuator or the second central heating pump in the fireplacecircuit PartC Controlofthehotdomesticwater HDW circulatingpump PartD Controlofthefan blower ON OFF S MIN STOP...

Страница 3: ...ors 2 User ssetting 3 Counted operation time of the fan and the duration of the interval betweentheblow throughs 4 Indicatorofextinguishedfireinthefurnace 5 Indicatorofemergencyshutdownofthefan 6 Indicatorofmanualactivationofthedevice 7 Indicatorofignition 8 Indicatoroffanpowerpercentagevalue 9 Indicatorofforcedoperation oftheCHpump 10 Indicatorofsustainedfireinthefurnace ...

Страница 4: ... provided with an approx 2 5 m long cable If an expanded functionality of the controller is required additional temperature sensors must be bought option If the length of the cable is inadequate a sensor with an approx 15 m long cable can be purchased 4 1 2 3 4 5 6 7 8 0 I A B C D SR1 SR2 SR3 OUT1 OUT2 OUT3 OUT4 OUT5 IN Description of buttons and cable terminals 2 NOTE Inordertoaccessthecabletermi...

Страница 5: ...to circulate in a CH system with a coal fired boiler or a gas boiler without a system controlling the operation of the pump The controller s sensor measures the temperatureofthewateronthesupplysideoftheCHsystem In a CH system with a coal fired boiler the controller switches off the circulation pump after the flame in the boiler is extinguished Pumping of water is not recommended when the flame is ...

Страница 6: ...ing them off In the controller connect the temperature sensor to the SR1 terminals Then install the sensor on an uncovered outlet pipe connected totheCHboiler asclosetotheboileraspossible NOTE If a coal fired boiler and a gas fired boiler work in the same CH system the sensor should be installed in a location where the two outletsmergeandmustbeinsulated 3 1 4 Connection check Checkifthewireisconne...

Страница 7: ...topat38 C 3 2 5 Changing the forced pump operation mode Press the A button under the temperature setting The digits begin to blink and indicate the value of the current setting Display the hysteresis setting HI by pressing the A button again After you press the A button one more time the value of 85 C will be displayed in the temperature section and on the right side of the display the symbol of f...

Страница 8: ...n again and hold it pressedfor3seconds NOTE When only the SR1 sensor is connected the remaining functions of the controller are inactive i e there is no indication of operation of CH pumps in the fire place circuit and of the control of the pump in the HDWcircuit h 3 3 Diagram of connection of the controller with the pump at the CH boiler 0 I A B C D SR1 SR2 SR3 OUT1 OUT2 OUT3 OUT4 OUT5 IN CH boil...

Страница 9: ... stove fireplace uses two control outputs oneforthewaterpumpinthefireplacecircuit ź one for an actuated valve or the second pump which is required for ź proper cooperation between the boiler stove fireplace with the CH circuit After the power supply is switched on temperature in the water jacket of the boiler stove fireplace is measured with the digital sensor the temperaturesignalcanbedividedinto...

Страница 10: ...e immersed in liquids or installedatthefireplacesmokeoutlets 4 1 4 Connecting the power supply cable to the valve or the second CH pump In the controller the valve s cable must be connected to the OUT3 terminal L N In the valve connect the green or yellow green wire grounding or protective zero to the terminal grounding symbol the bluewire tothe N terminal andthebrownwire tothe L terminal u 4 1 5 ...

Страница 11: ...ain When the CH set temperature indicator right of the valve or the second CH pump in the fireplace circuit starts blinking use the or button to set the desired temperature After the value is set approve it within 10 seconds by pressing the OK button Otherwise the changed valuewillnot be saved and the controller willreturntotheprevioussetting 4 2 4 Changing the hysteresis Press the B button under ...

Страница 12: ...anged setting willnotbesavedandthecontrollerwillreturntotheprevioussetting 4 2 6 Automatic operation The controller starts or stops the pump and the valve depending on the set temperature value In the CH system the pump and the valve are started when the temperature in the location of the sensor exceeds the set value and stopped when the temperature drops below the value set in the controller taki...

Страница 13: ...lementsnecessaryforproperoperationofthesystem 1 7 2 3 4 5 8 9 6 230V mains power supply 0 I A B C D SR1 SR2 SR3 OUT1 OUT2 OUT3 OUT4 OUT5 IN 1 Boiler stove fireplace 6 Radiator 2 Cut offvalve 7 Compressionvessel 3 Pump 8 Temperaturesensor 4 Exchanger 9 CHboiler 5 Automaticallyresetactuator NOTE When only the SR2 sensor is connected the remaining functions of the controller are inactive i e there is...

Страница 14: ...oller working with a hot domestic water HDW pump part C of the display C 4 5 1 2 3 5 5 1 Operation with the HDW over CH priority switched on If the HDW over CH priority function is switched on then the pump in the HDW circuit depends only on the setting and on the temperature measuredbytheSR3sensorinstalledinthetank 5 1 1 Settings range Temperature from 0 C to 99 C is measured by the SR3 sensor Th...

Страница 15: ...rinthetank 5 1 2 Programming of the HDW functions When the button is pressed the value of 50 C factory setting starts blinking Usethe or buttontosetthedesiredtemperature Once the desired temperature value is set it must be confirmed do not forget to do so within 10 seconds by pressing the button Otherwise the changed value will not be saved and the controller will returntotheprevioussetting After ...

Страница 16: ...sor On the controller side the temperature sensor must be connected to the SR3 terminals and then installed in the hot domestic water tank The sensor must not be immersed in liquids or installed at the fireplace smoke outlets Themaximummeasuredtemperaturevalueis99 C 5 2 1 Manual mode continuous operation In order to manually switch on the circulating pump regardless of thecurrent temperature at th...

Страница 17: ...ll not be saved and the controllerwillreturntotheprevioussetting 5 4 3 Changing the hysteresis Press the C button under the temperature setting The digits begin to blink and indicate the value of the current setting Display the hysteresis setting HI by pressing the C button again Using the or button set the required hysteresis value in the range of 2 C to 10 C with a 2 C increment After the value ...

Страница 18: ... displays the value of 85 C which means that above this temperature value measured by the SR1 sensor the CH pump will be started in the A section On the other hand section C setting value displays the value of 85 C which means that the tank will collect heat but only to the value of 85 C SR3 Also the forced operation indicator the CH pump is switched on is displayed After the value is set approve ...

Страница 19: ... indicator 11 Settimeunit S second MIN minute on hedoff ature of ding of begin to Display en press r hing the nd blink hen the button of 85 C the SR1 e other h means Also the splayed sing the and the ere the 5 C and In such mp in the p in the witched er supply V mains 0 IN 5 5 2 With the HDW tank Pump HDW sensor HDW tank 0 I A B C D SR1 SR2 SR3 OUT1 OUT2 OUT3 OUT4 OUT5 IN NOTE When only the SR3 se...

Страница 20: ...be connected to the OUT5 terminal L N In the blower connect the green or yellow green wire grounding or zero to the terminal the blue wire to the N terminal andthebrownwire tothe L terminal 6 1 1 Mounting the controller The controller must be mounted on a wall or another support using two screws the concrete anchors with screws are delivered with the controller The cables extending from the contro...

Страница 21: ...temperature value is set it must be confirmed do not forget to do so within 10 seconds by pressing the OK button Otherwise the changed value will not be saved and the controller will returntotheprevioussetting 6 2 4 Changing the operation time and the time of periodic breaks in the fan s operation Press the D button once The fan temperature will start blinking If you press the D button again withi...

Страница 22: ...emperature value Once the desired temperature value is set it must be confirmed saved within 10 seconds by pressing the OK button Otherwise the changed setting will not be saved and the controller will returntotheprevioussetting 6 2 6 Changing the hysteresis To change the hysteresis value press the D button and display the fan temperature If you press the D button again the fan operation time and ...

Страница 23: ...ere 100 is the maximum fan power value In order to change the fan power press the D button and display the fan temperature If you press the D button again the fan operation time and the break time settings will be displayed By pressing the D button yet again you will display the definitive fan switch off temperature and the STOP LO text Press the D button one more time and set the desired hysteres...

Страница 24: ...o switch off and then switch on again the controller using the switch in ordertostarttheignitionfunction 0 I 0 I 6 2 11 Adding fuel to the furnace During normal operation fuel can be added with the operation of the fan blocked intwoways Switch off the controller using the switch Add fuel and then ź switch on the controller and start the ignition function at the same time The second method consists...

Страница 25: ...ress and hold the OK button and the button for about 3 seconds The activation ofthepermanentilluminationisconfirmedwithasoundsignal The permanent illumination can be switched off by pressing the OK and button simultaneously The deactivation of the permanent illuminationisconfirmedwithasoundsignal NOTE The first time any function button is pressed the illumination is switchedonfirst ifthepermanenti...

Страница 26: ...t stop f 2 10 Supply voltage 230V 50Hz Maximum load for output sum 6A C C C C diff rom C to C A Data pertaining to the controller working in a CH circuit Temperature settings range 10 85 Range of measured values 0 99 Hysteresis start stop f 2 10 Supply voltage 230V 50Hz Maximum load for output sum 6A C C C C diff rom C to C B Data pertaining to the controller working with a CH pump and valve Z or ...

Страница 27: ...a pertaining to the controller working with a fan Cleaning and maintenance ź The outside of the controller must be cleaned with a clean cloth Do not use solvents suchasbenzene thinners oralcohol ź Do not touch the device with wet hands This can lead to electric shock or seriousdamagetothedevice ź Nonotexposethedevicetoexcessiveimpactofsmokeordust ź Donottouchthedisplaywithsharpobjects ź Avoidconta...

Страница 28: ...www auraton pl ...

Отзывы: