Installation instruction
RWA - Control Unit EMB 7300
Electrical data and connected loads
Operating voltage, primary:
Frequency:
Nominal current (secundär) /
Current consumption (primär):
Current output
(short-time duty)
:
Constant current consumption:
Output voltage, drives:
Residual ripple:
Number of detectors
(manual / automatic):
Line output:
Accumulator voltage:
Accumulator nominal capactiy:
195…..253 V AC
50….60 Hz
Version
Version
Version
Version
Nominal current 30% max. duty ratio
30 % max. of nominal current
(depending on version)
24V DC nominal (20….28 V DC)
max. 2,0 Vpp (Version 2,5 A)
max. 0,5 Vpp (Version 5 A, 10 A, 20 A)
10 units per detector line
18….26 V (detector voltage)
2 x 12 V
2,3 or 7,0 Ah (depending on version)
2,5 A / 0,4 A
5A / 0,8 A
10 A / 1,3 A
20 A / 2,6A
Environmental Conditions (operation)
Ambient temperature
range:
Maximum relative air
humidity:
-5…+40 °C
(according to EN 12101 Class 1)
75 % (mean value over lifetime)
90 % (for max. 96 hours)
Mechanical Data
Surface mounted housing:
Protection class:
Housing dimensions
(W x H x D): all dimensi-
ons given without lock
steel plate painted in RAL 7035
IP 30 (Version 2,5A and 5A)
IP 54 (Version 10A and 20A), with wall
mounting brackets and seal (not tested).
225 x 285 x 122 mm (Version 2,5A + 5A)
400 x 300 x 150 mm (Version 10A)
400 x 400 x 200 mm (Version 20A)
p
REpARing
AssEMBly
t
EChniCAl
d
AtA
!
W
ARning
Important instructions for safe assembly:
Fully observe all instructions, incorrect assembly
may lead to serious injuries.
Before starting the installation please check with the delivery note that
the delivery is complete and correct, any complaints received later cannot
be considered. It is required to keep a logbook for the EMB 7300 which
must be accessible to authorized staff at all times.
The available internal emergency power supply (back-up
accumulators), if correctly rated and serviced at regular
intervals, ensures that the controller of the Control Unit
moves the connected drives open at least twice and clo-
se at least once after 72 hours of mains power supply
loss.
!
03
P
reParing
a
ssembly
Scope of delivery: RWA - Control Unit EMB 7300
without breakglass unit in the cover
• Installation and Commissioning Instructions
(german and english)
• Test report according to VDE 0113
• Label„Smoke Vent“
• Stickers „ maintenance instructions“
• Drive line end module
• Resistors
• Key
Scope of delivery: RWA - Control Unit EMB 7300
with breakglass unit in the cover
• Installation and Commissioning Instructions
(german and english)
• Test report according to VDE 0113
• Label„Smoke Vent“
• Stickers „ maintenance instructions“
• Drive line end module
• Resistors
• Key (2 unit)