Installation instruction 

RWA - Control Unit EMB 7300

I

nstAllAtIon

 

step

 8:

e

nabling

 o

Peration

 / C

omPleting

 i

nstallation

              

Functions of the license-free software version

The following overview lists the functions that are available for free on 

version VIEW

. We expressly reserve the right to make additions and 

alterations.
•  Setting ventilation from dead-man mode to latching (OPEN / CLOSE /   
  OPEN and CLOSE)
•  Disabling monitoring of the drive line (factory default setting = active)
•  Disabling EMERGENCY-OPEN in case of a failure (factory default 
  setting = active)
•  Selecting switching threshold of a wind sensor (factory default setting 
  = 5 m/s)
•  Setting time-controlled automatic closing (factory default setting = 
  not active)
•  Enabling closing in case of power failure (factory default setting =  
  not active)
•  Setting acoustic or optical warning signal (requires additional hard- 
 ware)
•  Indicating, saving and printing system status
•  Update of firmware

Functions of the software version subject to 
license

The following overview lists the functions that are only available after 
paid activation of the software. We expressly reserve the right to make 
additions and alterations. 

•  Setting service/maintenance date (setting protected by password)
•  Setting switch-on delay WIND (factory default setting 20 s)
•  Setting switch-off delay WIND (factory default setting 20 min)
•  Restoring the switching state before wind/rain control
•  Disabling drive retriggering function at RWA EMERGENCY-OPEN
•  Deactivating the line for breakglass units
•  Deactivating the line for smoke detectors (or triggering of the external 
  fire alarm system)
•  Fire alarm system function for smoke detector line
•  Smoke detector release overrides EMERGENCY-CLOSE
•  Drive line(s) cut-off time (factory default setting 300 s)
•  Drive run direction in case of alarm / EMERGENCY-OPEN (factory 
  default setting = open)
•  EMERGENCY-OPEN button in deadman mode
•  Line-related EMERGENCY-OPEN in case of drive line failure (only 
  reasonable with version 0102)
•  Setting / selecting functions of relay plug-in card REL 65
•  Integration into digital networks (LON or KNX) including network 
 options 

I

nstAllAtIon

 

step

 8: 

E

nABling

 

opERAtion

/

CoMplEting

 

instAllAtion

For safety reasons the Control Unit is supplied with 
„deadman“ pre-setting for ventilation. You require the 
software for switching over to „latching“. It is abso- 
lutely necessary to ensure that all safety-relevant re- 
quirements for the „latching“ mode are guaranteed 
according to the information provided by the manu- 
facturers of the connected opening components.

RWA systems require a logbook, in which all important master data have 
to be entered prior to operation enable and all operational events during 
the period in operation. The logbook is part of the system documents and 
must be stored and available to authorized staff at all times.

We advise to perform an insulation measurement of the cable network 
before enabling operation of the plant and to keep a written record of 
this test.

Provided that the factory default configuration has been changed using 
the system software, all alterations have to be taken into 
account in the operating manual. It might be required to prepare an ope-
rating manual for non-specialist users that is easy to follow and well 
understandable.

In case of fire the system saves lives. Therefore 
immediately remedy or have any fault or mal- 
function remedied by specialists!

Depending on the storage period the back-up accu- 
mulators require some time to be fully charged. There- 
fore, bridging time (see chapter „

d

ata

 

Sheet

“) for the 

power failure might not be ensured after connecting the 
back-up accumulators and the back-up accumulators 
first need some charging time in mains operation 
to reach the maximum charge status (min. 8 hours).
The Control Unit must not be enabled for operation 
unless 

all

 system components work properly. This also 

applies to system components that do not come under 
our producer responsibility or whose installation had not 
been commissioned but are still components of 
the RWA system. Upon completion of the installation, 
all functions of the Control Unit must be checked 
for correct functionality with utmost care. Even 
if there is no fault indication this does not mean that all 
components function faultlessly.

!

W

ARning

USB

Before the installer is allowed to enable the operation of the Control Unit, 
the complete performance range of the system must be checked with 
utmost care. The chapter „T

roublShooting

 

and

  r

epair

“ provides support 

for the localisation of possible faults and malfunctions. 
On the last page you find an overview of all external connections where 
the current assignments can be entered.
Modifications of the system using the system software should take place 
after the complete installation of the Control Unit and all components 
being connected. When required, the system configuration and status 
can be saved or printed using the system software. In the case of faults 
or malfunctions of system components it might also be necessary to 
thoroughly check the system configuration (computer to be connected 
using system software).

!

!

!

Follow the instructions in the chapter „

S

afety

 

in

StructionS

“.

!

Before changing the operating mode check and pay 
attention to danger zones at the window!

06

Fault / Mal- 

function

Possible cause and their solution

No indicator 
lights up

•  no power supply available or fuse F1 / F2 defective

Indicator „S“ 
flashes

•  check power supply connection

Indicator „S“ 
blinks quickly

•  back-up accumulators are not correctly connected or 
   are not charged

Indicator „S“ 
has steady light

•  open circuit or short circuit in manual fire alarm
•  faulty power monitoring

Indicator „S“ 
blinks slowly

•  open circuit or short circuit in smoke detector line
•  faulty power monitoring

Indicator „S“ 
blinks 2 times

•  service required (indicator „B“ (green) lights up!)

Indicator „S“ 
blinks 3 times

•  fault bus module (e.g. radio module)

Indicator „S“ 
blinks 4 times

•  open circuit or short circuit in drive line 1
•  faulty power monitoring

Indicator „S“ 
blinks 5 times

•  only drive line 2, 

cause of fault analogue to drive line 1

Indicator „S“ 
blinks 6 times

•  EMERGENCY-CLOSE button (breakglass unit)  
      does not work properly and/or is not recognized

Drives do not 
respond

•  check fuse F2 / F3
•  check drive connections based on assembly 
      instructions
•  or, if the indicators (red / green) do not respond:  
      check ventilation control

Drives run incor-
rectly

•  The indicators for the drive run direction (red / green) 
      must comply with the actual running direction. 
      Otherwise swap connections on terminal 1 and 2
•  check drive connections based on their installation 
      instructions

Signal REL65 is 
not recognized

•  check relay plug-in card REL 65 for correct installationd

and connection

Содержание EMB 7300

Страница 1: ...g to EN12101 10 and control panel according to prEN12101 9 RWA Control Unit EMB 7300 2 5 A 5 A 10 A 20 A tested electrical control device EMB 7300 with recognition number G 514001 Installation and Commissioning Instructions ...

Страница 2: ...Maximal detector in drive line Installation step 3 Connection of automatic and manual smoke detectors Installation step 4 Connecting wind and rain sensors Installation step 5 Installing relay plug in card REL and BUS connection Installation step 6 Connecting power supply Installation step 7 System configuration using software EMB Kompakt Installation step 8 Enabling operation completing installati...

Страница 3: ... V Volts PU Packaging Units Vpp Residual ripple Voltage Peak Peak W Watts Ω k Ω Ohm Kilohms Figures AC Alternating current 50Hz 60Hz DC Direct current I Electric current L Length ME Module space unit 1 ME 23 mm NC Contact closed normally closed NO Contact opened normally opened P Electric power R Electrical resistance U Electric voltage Um Change over switch Colour abbreviation according to IEC 60...

Страница 4: ... lives and protect property Furthermore the electric window ensures fresh air supplied for natural ventilation of the building Intended use according to the Declaration of Con formity The control device is intended for stationary installation and electrical connection as part of a building In accordance with the attached Declaration of Con formity the control device in combination with electromoti...

Страница 5: ...e each intervention in the Control Unit of the system Clamping points must be checked for tightness of threa ded connections and cable ends Access to junction boxes clamping points and external drive control systems must be ensured for maintenance work Commissioning operation and maintenance After the installation and after each modification in the set up all functions must be checked with a trial...

Страница 6: ...issue of a Declaration of Conformity according to European guidelines The prerequisites of the system see chapter Systems confi guration of software must be checked prior to installation The Software clause for handing over the standard soft ware as part of shipments of the ZVEI German Electrical and Electronic Manufacturer s Association is accepted as legally binding upon installation See our hom...

Страница 7: ...ance free back up accumulators 2x 12 V 2 3 Ah Part No 541000 Application Compact Control Unit for smoke and heat exhaust ventilation systems operating with 24V DC voltage suitable for staircases TECHNICAL DATA Rated values Operating voltage 230V AC 195 253 V AC 50 60 Hz Max power consumption 460 W Output voltage 24V DC 20 28 V DC 0 5 Vpp Output current 5 0 A Ambient temperature range 5 C 40 C Prot...

Страница 8: ...ting steel sheet RAL 7035 light grey Dimensions WxHxD 400 x 300 x 150 mm Connection terminals 1 5 mm Drives 6 mm rigid wire Motherboard 1 RWA group 2 Vent groups Application Compact Control Unit for smoke and heat exhaust ventilation systems operating with 24V DC voltage suitable for staircases TECHNICAL DATA Rated values Operating voltage 230V AC 195 253 V AC 50 60 Hz Max power consumption 805 W ...

Страница 9: ...5 x 285 x 122 mm Version 2 5A 5A 400 x 300 x 150 mm Version 10A 400 x 400 x 200 mm Version 20A Preparing assembly Technical Data Warning Important instructions for safe assembly Fully observe all instructions incorrect assembly may lead to serious injuries Before starting the installation please check with the delivery note that the delivery is complete and correct any complaints received later ca...

Страница 10: ... exhausting natural ventilation Input for ventilation line 1 max 10 vent buttons Output for drive line 2 only for EMB 7300 5 A 0102 10 A 0102 20 A 0102 Input for ventilation line 2 max 10 vent buttons only for MB 7300 5 A 0102 10 A 0102 20 A 0102 Housing of Control Unit with or without integrated break glass unit and ventilation button Connections for wind and rain sensor disabled in case of alarm...

Страница 11: ...ine length and cross section A drives depend on the type of drive and on the number of drives Line length and cross section can be determined according to the following formula Formula to calculate the required wire cross section of a infeed line A cross section of line in mm2 L line length in m I current of connected drives in A U line voltage drop 2 V DC total length infeed line voltage drop Bef...

Страница 12: ... 5 A nominal current EMB 7300 10 A max 10 A nominal current EMB 7300 20 A 2x max 10 A nominal current RWA release in case of fire overrides ventilation No ventilation in the event of a mains power supply failure accumulator operation RWA release in case of fire overrides ventilation No ventilation in the event of a mains power supply failure accumulator operation Automatic ventilation control e g ...

Страница 13: ...ance with applicab le legal requirements The terminal cross section for the drive connection is EMB 7300 0101 max 2 5 mm flexible EMB 7300 0101 T max 4 0 mm rigid wire EMB 7300 0101 max 4 0 mm flexible EMB 7300 0101 T or EMB 7300 0102 max 6 0 mm rigid wire EMB 7300 0101 EMB 7300 0102 EMB 7300 0102 2 5A 2 5A 5A 5A 5A 10A 10A 20A Formula to calculate the required wire cross section of a infeed line ...

Страница 14: ...nection of automatic and manual smoke detectors 04 OK 11 10 9 8 7 6 5 4 3 2 1 1 1 1 22 5 71 1 13 14 15 16 17 18 19 A S B 1 72 OK 11 10 9 8 7 6 5 4 3 2 1 10 k IN C O M O UT IN C O M O UT IN C O M OU T BMA 1 2 3 4 5 1 22 1 22 COM OUT IN IN IN OUT OUT COM COM RE 1 13 14 15 16 18 19 1 2 3 4 5 6 7 8 9 10 11 2 5 A 5 A 20 A 10 A Automatic smoke detector Breakglass unit Buttons Indicators COM Indicators m...

Страница 15: ... rain sensors is deactivated Before mounting and positioning the wind rain sen sors carefully read the safety and assembly instructions provided with the products They are part of the system documentation and must be adhered to and kept accor dingly e g for servicing purposes Installation step 4 Connecting wind and rain sensors 2 5 A 5 A 20 A 10 A Installation step 4 Connecting Wind and Rain Senso...

Страница 16: ... installation an connect when disconnected from the mains power supply Switch off power supply and secure against reconnection The motherboard has two slots for using one relay plug in card REL 65 each order no 650200 so that external processing of messages via floating relay contact 1 x change over switch 42 V max 0 5 A is possible Cable installation must be in compliance with applicable legalreq...

Страница 17: ... AC 50 60 Hz On the version with front mounted push button the connector may be removed Routing via external fuse and switching component PE BU BU BU 2 x back up accumulator 2 3 Ah 12V Ensure correct polarity when connecting red blue Attachment of the accumulators with the optional accumulator holder set Part No 683250 only for compact housing The accumulator set may also be fastened to the housin...

Страница 18: ... A N N 1 72 N L V VGG N L USB Do not remove cover F1 F2 F3 Switching power supply 5A RD RD RD RD RD L L Cover SMOKE VENT N N 225 mm 400 mm 285 mm 300 mm 10 A oder 400 mm 20 A Wiring duct 230V AC 50 60 Hz 230V AC 50 60 Hz Version 0102 only Routing via external fuse and switching component Routing via external fuse and switching component PE PE BU BU BU BU Output DC 24V Switching power supply 10 A o...

Страница 19: ...free version of the system software version VIEW can be downloaded from the homepage www aumueller gmbh de The software can be installed on a computer notebook or net book Please pay regard to the hardware and system requirements see below Follow the instructionsdisplayed on the screen to install the program The software offers many features to adapt the system to your requirements However you sho...

Страница 20: ...s RWA systems require a logbook in which all important master data have to be entered prior to operation enable and all operational events during the period in operation The logbook is part of the system documents and must be stored and available to authorized staff at all times We advise to perform an insulation measurement of the cable network before enabling operation of the plant and to keep a...

Страница 21: ...ght open circuit or short circuit in manual fire alarm faulty power monitoring Indicator S blinks slowly open circuit or short circuit in smoke detector line faulty power monitoring Indicator S blinks 2 times service required indicator B green lights up Indicator S blinks 3 times fault bus module e g radio module Indicator S blinks 4 times open circuit or short circuit in drive line 1 faulty power...

Страница 22: ... 1 7 2 USB 1 REL65 2 REL65 BUS Module BUS Wind Rain RM HSE LT 2 F1 A A N N Drive 1 Stecker für Front Button Drive 2 A Z Reset LT 1 Indicators GN Operation YE Fault RD Alarm EMERGENCY OPEN Drive run direction and position A OPEN RD Z CLOSE GN Drive run direction A OPEN RD Z CLOSE GN Duo LED 2 x on version 0102 The Duo LED displays the current switched direction of the line vol tage for the duration...

Страница 23: ... contract with a specialist company authorized by the manufacturer A sample maintenance contract can be downloaded from the homepage of Firm Aumüller Aumatic GmbH www aumueller gmbh de After opening of the system housing voltage carrying parts are exposed Each time before performing main tenance work or making a modification of the structure e g replacement of the window drive the mains voltage an...

Страница 24: ...wing Improper use of the product Improper installation commissioning operation maintenance or repair of the product Operating the product by defect and improper installed or not functioning safety and protection devices Ignoring instructions and installation requirements in these in structions Unauthorized constructional modifications at the product or accessories Disaster situations due to effect...

Страница 25: ...25 Installation instruction RWA Control Unit EMB 7300 08 ...

Страница 26: ... different Control Unit versions Remark Terminals Drive 1 Drive 2 only version 0102 CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE ZU Operation Fault COM COM OPEN OPEN OPEN OPEN OPEN OPEN Buttons Buttons Buttons Indicators Indicators Indicators EMERGENCY EMERGENCY OPEN OPEN COM Line monitoring Line monitoring COM COM COM COM COM only version 0102 optional optional Ventilation 1 Ventilation 2 1 REL 65 2 REL 6...

Страница 27: ...rvices The publication of these assembly and commissioning instructions supersedes all previous editions The VdS approval includes the following Control Units EMB 7300 without RWA button EMB 7300 with orange RWA button EMB 7300 without RWA button EMB 7300 with orange RWA button EMB 7300 EMB 7300 2 5A 2 5A 5A 5A 10A 20A Certificate and Declaration of Conformity We declare under our sole responsibil...

Страница 28: ...en Tel 49 8271 8185 0 Fax 49 8271 8185 250 info aumueller gmbh de 9000017000_V0 1_KW05 14 www aumueller gmbh de AUMÜLLER AUMATIC GMBH Gemeindewald 11 86672 Thierhaupten Tel 49 8271 8185 0 Fax 49 8271 8185 250 info aumueller gmbh de 9000007401_V2 4_KW46 20 ...

Отзывы: