For loop topology, automatic termination is performed once the actuator controls
are connected to the power supply.
●
In case of a power outage of actuator controls, the two RS-485 loop segments
will be automatically connected so that the actuators following these segments
remain available.
●
When using a SIMA master station, a redundant loop topology may be estab-
lished.
Connect fieldbus cables:
1.
Connect bus cables.
2.
If the actuator is the final device in the fieldbus segment (line topology only):
2.1 Connect termination resistor for channel 1 through linking the terminals
31 - 33 and 32 - 34 (standard)
2.2 For AUMA redundancy I or II: Connect termination resistor for channel 2
through linking the terminals 35 - 37 and 36 - 38.
6.5.4.
Terminal compartment: close
Figure 45: Close terminal compartment
[1]
Cover (illustration shows type of protection Ex e)
[2]
Screws for cover
[3]
O-ring
[4]
Blanking plugs
[5]
Cable gland (example)
[6]
Connection frame
1.
Clean sealing faces of cover [1] and connection frame [6].
2.
For Ex plug/socket connector designed as KES flameproof: Preserve joint sur-
faces with an acid-free corrosion protection agent.
3.
Check whether O-ring [3] is in good condition, replace if damaged.
4.
Apply a thin film of non-acidic grease to the O-ring and insert it correctly.
Flameproof enclosure, risk of explosion!
Risk of death or serious injury!
→
Handle cover and housing parts with care.
→
Joint surfaces must not be damaged or soiled in any way.
→
Do not jam cover during fitting.
5.
Fit cover [1] and fasten screws [2] evenly crosswise.
42
SQVEx 05.2 – SQVEx 14.2/ SQRVEx 05.2 – SQRVEx 14.2 Control unit: electronic (MWG)
Electrical connection
ACVExC 01.2 Modbus RTU