Features and functions of actuator controls
Standard voltages:
1-phase AC current – Voltages/frequencies
230
115
Volt
50/60
50/60
Hz
Permissible variation of mains voltage: ±10 %
Permissible variation of mains frequency: ±5 %
For current consumption, current type, mains voltage and frequency, refer to the name plate
Mains voltage, mains frequency
24 V DC +20 %/–15 %
Current consumption: With options up to 200 mA
External supply of the electronics
(option)
Category III according to IEC 60364-4-443
Overvoltage category
Power electronics with integral motor controller
Power electronics
●
Maximum 4 digital inputs (via opto-isolator)
-
Control voltage 24 V DC, current consumption: approx. 15 mA per input
-
Minimum pulse duration for shortest operation pulse: 10 ms.
-
3 inputs on the same potential
-
1 input galvanically isolated
Assignment for open-close actuators:
-
OPEN, STOP, CLOSE (standard)
-
OPEN, STOP, CLOSE, EMERGENCY (option)
-
OPEN, STOP, CLOSE, MODE in combination with positioner (option)
Assignment for modulating actuators:
-
OPEN, STOP, CLOSE, MODE (standard)
●
Analogue input 0/4 – 20 mA (galvanically isolated)
Used as input signal for E1 position setpoint (in combination with positioner) or as input signal for
E3 motor speed.
Control
(input signals)
Up to 4 programmable semi-conductors or relay outputs are available, each with max. 30 V/1 A switching
power. They are preassigned with the signals as indicated below.
Status signals
(output signals)
Variants of semi-conductor output type:
4 outputs as NO with 19-pole signal connector:
Compatible with SG .2/SV .2 actuators
●
1 and 2 at one common, 3 and 4 respectively galvanically isolated
Assignment: CLOSE, OPEN, fault, REMOTE
Standard:
4 outputs as NO with 19-pole signal connector: Compatible with SG .2/SV .2 actuators
●
1, 2 and 3 at one common, 4 galvanically isolated
Assignment: CLOSE, OPEN, fault, REMOTE
Option:
Variants of relay output type:
3 outputs as NO/NC (change-over contact) with 17-pole signal connector:
Compatible with MEC 02.1 actuator controls
●
All on the same potential
Assignment: OPEN, CLOSE, fault
Standard:
3 outputs as NO with 19-pole signal connector:
●
All on the same potential
Assignment: OPEN, CLOSE, fault
Assignment (option): OPEN, CLOSE, system OK
●
4 outputs as NO with 19-pole signal connector:
1, 2 and 3 at one common, 4 galvanically isolated
Assignment: CLOSE, OPEN, fault, REMOTE
●
4 outputs as NC with 19-pole signal connector:
1, 2 and 3 at one common, 4 galvanically isolated
Assignment: CLOSE, OPEN, fault, REMOTE
Options:
Auxiliary voltage 24 V DC, max. 40 mA for supply of control inputs, galvanically isolated from internal
voltage supply
Not available for “external electronics supply” option.
Voltage output
46
SG 04.2 – SG 10.2
Technical data
with actuator controls MEC 03.1
Содержание SG 04.2
Страница 51: ...51 SG 04 2 SG 10 2 with actuator controls MEC 03 1...
Страница 52: ...52 SG 04 2 SG 10 2 with actuator controls MEC 03 1...