Figure 28: Switches for type of seating
[S9]
End position OPEN
[S10] End position CLOSED
Table 8:
Function of switches [S9], [S10]
Limit seating, sliding switch at white dot
ON
Torque seating
OFF
Setting via software parameters (AUMA CDT)
Condition: Switch [S5] is in position ON (software mode).
Setting parameters
Customer settings
Type of seating
End position CLOSED
End position OPEN
Default value:
Limit
Setting values:
Limit
Limit seating in end positions.
Torque
Torque seating in end positions.
8.4.
Torque switching: set
Valve damage due to excessive tripping torque limit setting!
→
The tripping torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Once the set tripping torque is reached, the controls automatically switch off the
actuator (overload protection of the valve).
Setting via switches
Condition: Switch [S5] is in position OFF (hardware mode).
30
SG 04.2 – SG 10.2
Basic settings for the actuator controls
with actuator controls MEC 03.1