Figure 29: Switches for tripping torque
[S6]
Tripping torque in direction OPEN
[S7]
Tripping torque in direction CLOSE
Default value: depending on the order
Setting range: in 8 steps (refer to tables), linear from 40 – 100 % of the maximum
tripping torque.
Table 9:
Tripping torques [Nm]
Switch steps
SG 10.2
SG 07.2
SG 05.2
SG 04.2
200
100
50
25
0
200
100
50
25
1
240
120
60
30
2
280
140
70
35
3
320
160
80
40
4
360
180
90
45
5
400
200
100
50
6
440
220
110
55
7
500
250
125
63
8
500
250
125
63
9
Setting via software parameters (AUMA CDT)
Condition: Switch [S5] is in position ON (software mode).
Setting parameters
Customer settings
Torque switching
Tripping torque CLOSE (S7)
Tripping torque OPEN (S6)
Default value: depending on the order
Setting ranges: adjustable between 40 – 100 % of the maximum tripping torque
8.5.
Operating time: set
Operating time is defined by the motor speed.
31
SG 04.2 – SG 10.2
with actuator controls MEC 03.1
Basic settings for the actuator controls