8.2.
Setting via hardware (switches) or via software
The switch [S5] position determines whether the hardware settings (switches) or the
software settings (via AUMA CDT software) are currently active.
Figure 27: Switch [S5] = Hardware/software mode
Table 7:
Switch [S5] functions
Hardware mode (factory setting on delivery)
Settings of switches [S2] through [S4] and [S6] through [S10] are valid. The values
cannot be changed via AUMA CDT software.
OFF
(1)
Software mode (sliding switch at white dot)
Settings of switches [S2] through [S4] and [S6] through [S10] are NOT relevant.
Settings are defined via software parameters.
ON
(0)
8.3.
Type of seating: set
Valve damage due to incorrect setting!
→
The type of seating setting (limit or torque seating) must match the selection for
the valve.
→
Only change the setting with prior consent of the valve manufacturer.
Setting via switches
Condition: Switch [S5] is in position OFF (hardware mode).