5.6.2.
Cable connection
Table 14:
Terminal cross sections and terminal tightening torques
Tightening torques
Terminal cross sections
Designation
0.9 – 1.1 ft-lb [1.2 – 1.5
Nm]
1.0 – 6 mm
2
(flexible)
1.5 – 10 mm
2
(solid)
Power contacts (U, V, W)
0.9 – 1.6 ft-lb [1.2 – 2.2
Nm]
With ring lugs
1.0 – 6 mm
2
(flexible)
PE connection
With loops
1.5 – 10 mm
2
(solid)
0.49 – 0.5 ft-lb [0.5 – 0.7
Nm]
0.25 – 2.5 mm
2
(flexible)
0.34 – 2.5 mm
2
(solid)
Control contacts (1 to 50)
Without motor protection, impermissibly high temperatures at the actuator
may occur: Ignition hazard, risk of explosion!
Risk of death, serious injury or motor damage. Our warranty for the motor will lapse
if the motor protection is not connected.
→
Connect thermal switches to external controls.
1.
Remove cable sheathing.
2.
Insert the wires into the cable glands.
3.
Fasten cable glands with the specified torque to ensure required enclosure
protection.
4.
Strip wires.
→
Controls approx. 6 mm, motor approx. 10 mm
5.
For flexible cables: Use wire end sleeves.
6.
Connect cables according to order-related wiring diagram.
35
SAEx 25.1 – SAEx 35.1 / SAREx 25.1 – SAREx 30.1
NORM (without controls)
Electrical connection