2.
Insert cable glands suitable for connecting cables.
Information: When selecting cable glands observe type of protection (with Ex d
approval) and enclosure protection NEMA... (refer to name tag).
➥
The type of protection stated on the name tag NEMA... is only ensured if suitable
cable glands are used.
Figure 21: Name tag, example with enclosure protection NEMA
5.3.3.
Motor terminal compartment: close
Figure 22:
[1]
Cover
[2]
Screws for cover
[3]
O-ring
[4]
Cable gland
1.
Clean sealing faces of cover [1] and housing.
2.
Check whether O-ring [3] is in good condition, replace if damaged.
3.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
4.
Fit cover [1] and fasten screws [2] evenly crosswise.
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
→
Handle cover and housing parts with care.
→
Joint surfaces must not be damaged or soiled in any way.
→
Do not jam cover during fitting.
5.
Fit cover [1] and fasten screws [2] evenly crosswise.
24
SAEx 25.1 – SAEx 35.1 / SAREx 25.1 – SAREx 30.1
Electrical connection
NORM (without controls)