2.
Fasten cable glands with the specified torque to ensure required enclosure
protection.
3.
Strip wires.
4.
For flexible cables: Use wire end sleeves according to DIN 46228.
5.
Connect cables according to order-related wiring diagram.
In case of a fault: Hazardous voltage while protective earth conductor is NOT
connected!
Risk of electric shock.
→
Connect all protective earth conductors.
→
Connect PE connection to external protective earth conductor of connecting
cables.
→
Start running the device only after having connected the protective earth con-
ductor.
6.
Firmly tighten protective earth to PE connection (symbol:
).
7.
For shielded cables: Link the cable shield end via the cable gland to the housing
(grounding).
5.3.2.
Motor terminal compartment: open
Figure 20: Motor terminal compartment: open
[1]
Cover
[2]
Screws for cover
[3]
O-ring
[4]
Cable gland
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
→
Before opening, ensure that there is no explosive gas and no voltage.
1.
Loosen screws [2] and remove cover [1].
23
SAEx 25.1 – SAEx 35.1 / SAREx 25.1 – SAREx 30.1
NORM (without controls)
Electrical connection