9.1.1.
End stop CLOSED: set
1.
Remove screw plug [3].
2.
Move valve to end position CLOSED with handwheel.
3.
If the valve end position is not reached:
→
Slightly turn setting screw [4] counterclockwise until valve end position
CLOSED can be safely set.
➥
Turning the setting screw [4] clockwise results in a smaller swing angle.
➥
Turning the setting screw [4] counterclockwise results in a larger swing
angle.
4.
Turn setting screw [4] clockwise to the stop.
➥
This completes the setting of end stop CLOSED.
5.
Check O-ring in screw plug and replace if damaged.
6.
Fasten and tighten screw plug [3].
Having completed this procedure, the end position detection CLOSED can be set
immediately.
9.1.2.
End stop OPEN: set
Information
In general, the end stop OPEN does not have to be set.
1.
Remove screw plug [1].
2.
Move valve to end position OPEN with handwheel.
3.
If the valve end position is not reached:
→
Slightly turn setting screw [2] counterclockwise until valve end position
OPEN can be safely set.
➥
Turning the setting screw [2] clockwise results in a smaller swing angle.
➥
Turning the setting screw [2] counterclockwise results in a larger swing
angle.
4.
Turn setting screw [2] clockwise to the stop.
➥
This completes the setting of end stop OPEN.
5.
Check O-ring in screw plug and replace if damaged.
6.
Fasten and tighten screw plug [1].
Having completed this procedure, the end position detection OPEN can be set
immediately.
9.2.
Switch compartment: open
The switch compartment must be opened to perform the following settings (options).
23
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Commissioning